Share a unified grounding grid with the PCS; connect PE wires to the dedicated grounding terminals with copper lugs
Printed as "The battery system shall share a unified grounding grid with PCS to ensure equipotential bonding and avoid ground loops." in the Growatt User Manual for the ALP 5.0L-E2 Battery System (GR-UM-479-A-03, Australian site, 202609) (pages 8 and 28). Section 4.5.3.6 continues: "Connect PE wires to dedicated grounding terminals marked with the "〨" symbol. Use copper lugs crimped with conductive paste to enhance contact." Section 2.2.2 adds "Ensure that the ground cable is securely connected."
Where: PDF pages 8 and 28, section 4.5.3.6 Battery System Grounding Requirements; section 2.2.2 Operation Precautions
At least 300 mm above and on each side of a column; 300 mm to 800 mm between two floor-mounted columns; wall-mounted columns at least 100 mm above the ground
Printed as "Ground 300mm ≤d≤800mm ≥300mm ≥300mm" in the Growatt User Manual for the ALP 5.0L-E2 Battery System (GR-UM-479-A-03, Australian site, 202609) (pages 15 and 16). Read with the rendered Figures 4.2 and 4.3: ≥300 mm above the column and at both sides, 300 mm ≤ d ≤ 800 mm between two floor-mounted columns, and ≥100 mm from the ground to the bottom of a wall-mounted column.
Where: PDF pages 15 and 16, section 4.2, Figure 4.2 Floor-mounted installation and Figure 4.3 Wall-mounted Installation
Charged Reviews classified this product from the documents it is based on. It is our own grouping, not a manufacturer claim.
Printed as "Easy installation with modular and stacked design" and "Floor/Wall mount". Classified as Stackable from the maker's own words for this model; the maker also prints wall/floor mounting, quoted here.
Location: ALP LV Battery System ALP 5.0L-E2 AU datasheet (Growatt, file dated 202601), page 1, feature list (image-only page, read by OCR); page 2, Installation method row (image-only page, read by OCR)
Communications
CAN
Printed as "Communication port CAN".
Where: Chapter 7 Technical Specifications, PDF page 39, row "Communication port", second column (ALP 50.0L-E2)
Printed as "50kWh" in the datasheet's Usable capacity row for ALP 50.0L-E2; read from the rendered image-only page. The manual prints no usable-energy row.
Where: Page 2, row "Usable capacity", column ALP 50.0L-E2
Printed as "IFpP/51/161/11 9/[(1P16S)10P] M/-10+50/100" in the Growatt User Manual for the ALP 5.0L-E2 Battery System (GR-UM-479-A-03, Australian site, 202609) (page 39). The ALP 50.0L-E2 is 10 ALP 5.0L modules in parallel ("Number of parallel battery systems 10" in the same table); each module is "sixteen serial connection (1P16S)" (section 1.1).
Where: PDF page 39, chapter 7 Technical Specifications, Battery Designation row, ALP 50.0L-E2 column
Printed as "1000Ah/50kWh" in the ALP 50.0L-E2 column of the manual's Nominal Capacity/Energy row; the Rated Capacity/Energy row prints the same figures.
Where: Chapter 7 Technical Specifications, PDF page 39, row "Nominal Capacity/Energy", second column (ALP 50.0L-E2)
PCS: CAN communication; LINK-IN: CAN communication; LINK-OUT: CAN communication; USB interface; Cluster-in communication; Cluster-out communication
Printed as "2 PCS CAN communication" in the Growatt User Manual for the ALP 5.0L-E2 Battery System (GR-UM-479-A-03, Australian site, 202609) (page 5). Ports of each ALP 5.0L battery module's operation panel. The ALP 50.0L-E2 is built from 10 such modules.
Where: PDF page 5, section 1.2.2 Introduction to the battery operation panel
Do not turn the PACK upside down, and ensure that the floor is level; wall: -3°≤δ≤3°
Printed as "Do not turn the PACK upside down, and ensure that the floor is level." in the Growatt User Manual for the ALP 5.0L-E2 Battery System (GR-UM-479-A-03, Australian site, 202609) (pages 15 and 16). Figure 4.3 (page 16) marks the wall-mounted column angle as "-3°≤δ≤3°".
Where: PDF pages 15 and 16, section 4.2 Basic installation requirements; Figure 4.3 Wall-mounted Installation
Printed as three storage bands: -20 to 25 ℃ for 12 months, 25 to 35 ℃ for 9 months and 35 to 50 ℃ for 6 months, humidity 5% to 95% RH; the range recorded spans the three bands, each with its own time limit.
Where: Chapter 7 Technical Specifications, PDF page 39, row "Storage conditions", second column (ALP 50.0L-E2)
Printed as "The whole battery system communicates to Power Conversion System (PCS) via CAN." in the Growatt User Manual for the ALP 5.0L-E2 Battery System (GR-UM-479-A-03, Australian site, 202609) (page 6). The PCS port pin definition (section 4.5.3.1) lists CAN_H and CAN_L.
Where: PDF page 6, section 1.3 Working Principle and Function
376.57 L* (Calculated enclosure volume: W × H × D in mm ÷ 1,000,000)W: 690 × H: 2,950 × D: 185 mm / W: 27.2 × H: 116.1 × D: 7.28 in440 kg / 970 lb0.13 kWh/L* (Rated or usable capacity shown on this card ÷ enclosure volume)
Evidence score
13/100Missing details20% documented
The Evidence score uses the priorities you choose. It counts published documents, such as certificates and warranty terms, and it compares a documented figure with the best documented figure of the same kind. It does not count owner reviews, and it is not a verdict on product quality or on how many people have reviewed it. A low score can mean little is documented, or that a documented figure is below the best of its kind. Undisclosed data scores 0.
Missing details. This number counts only the evidence recorded so far. The source review for this product is not finished, or the maker has not disclosed enough, so the number can only go up.
Missing for this product: Certificates evidence needed; Warranty energy disclosure evidence needed; Lifetime / capacity evidence needed; Cell model disclosure evidence needed.
48 V · Stackable · Rated capacity
The warranty term and the lifetime energy are each scored against the best documented value for a home storage battery: a value earns its share of that best, times the weight. A documented value always earns points; an undisclosed one earns 0.
Printed as a 10-year warranty in the datasheet table ("Warranty 10 years" for E1; "Warranty: 10 years Yes" for E2); read from the rendered image-only page. The datasheet does not state what the term covers or its conditions.
Research pending, 0 points: Certificates, Warranty energy disclosure, Cell model disclosure.
Computed from public specifications and evidence records. Warranty duration is not service quality; certificate evidence points are not a safety rating. Compatibility and installation limits still apply.
What this shows: what each record says and how far it reaches. It does not mean the product is approved.
StandardEvidenceStatusSource
UL 1973manufacturer claimpresent at observation[1]
Scope
cell
Covered models
ALP 50.0L-E2
Limitations
A manufacturer claim at cell level, not a listing or certificate. Printed as "Cell safety certification IEC62619/UL1973" (row 21) in chapter 7, Technical Specifications, of Growatt's ALP 5.0L-E2 Battery System User Manual (GR-UM-479-A-03, file dated 202609, au.growatt.com), page 36 (PDF page 39), in the table whose Battery Model columns are ALP 45.0L-E2 and ALP 50.0L-E2; the row spans both columns. The table's separate PACK certification row (row 22) does not list UL 1973. Captured September 29, 2026. Cell scope does not certify the assembled battery. No issuer, certificate or report number is printed; the issuer's record was not checked.
Printed as a 10-year warranty in the datasheet table ("Warranty 10 years" for E1; "Warranty: 10 years Yes" for E2); read from the rendered image-only page. The datasheet does not state what the term covers or its conditions.
UL 1973Manufacturer claim · cellClaimedListed when checked
A manufacturer claim at cell level, not a listing or certificate. Printed as "Cell safety certification IEC62619/UL1973" (row 21) in chapter 7, Technical Specifications, of Growatt's ALP 5.0L-E2 Battery System User Manual (GR-UM-479-A-03, file dated 202609, au.growatt.com), page 36 (PDF page 39), in the table whose Battery Model columns are ALP 45.0L-E2 and ALP 50.0L-E2; the row spans both columns. The table's separate PACK certification row (row 22) does not list UL 1973. Captured September 29, 2026. Cell scope does not certify the assembled battery. No issuer, certificate or report number is printed; the issuer's record was not checked.
Captured by scripts/prepare-brand-sweep-sep21.mjs on 2026-09-29.
Location: Chapter 7, Technical Specifications (PDF pages 35 to 39)
Retrieved Sep 28, 2026
Growatt's English user manual for the ALP 5.0L-E2 battery system, linked from the Australian ALP 5.0L-E2 page and served from au.growatt.com, captured September 29, 2026. Chapter 7 prints one technical table per pair of configurations, ALP 5.0L-E2 to ALP 50.0L-E2. The primary source for the Australian records. Manufacturer claims, not independently verified.
Archived copies
Archived copy of a document published by Shenzhen Growatt New Energy Co., Ltd.. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email [email protected].
Captured by scripts/prepare-brand-sweep-sep21.mjs on 2026-09-29.
Location: Page text and download list
Retrieved Sep 28, 2026
Growatt's Australian product page for the ALP LV Battery (ALP 5.0L-E2), captured September 29, 2026. Cited for the product name, the market it is published for and the links to the AU datasheet and the user manual. Manufacturer claims, not independently verified.
Earlier revisions, archived captures and copies published by someone other than the manufacturer. Every one stays reachable.
Archived documents
User Manual, ALP 5.0L-E2 Battery System (Growatt, GR-UM-479-A-03, file dated 202609)
Archived copy of a document published by Shenzhen Growatt New Energy Co., Ltd.. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email [email protected].
ALP LV Battery System ALP 5.0L-E2 AU datasheet (Growatt, file dated 202601)
Archived copy of a document published by Shenzhen Growatt New Energy Co., Ltd.. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email [email protected].
No sourced accessories or replacement parts listed yet.
Model history
Model identity
Model
ALP 50.0L-E2
Manufacturer SKU unknown · AU market
Observed Sep 29, 2026
UL 1973: claimed
Cell / component only. A manufacturer claim at cell level, not a listing or certificate. Printed as "Cell safety certification IEC62619/UL1973" (row 21) in chapter 7, Technical Specifications, of Growatt's ALP 5.0L-E2 Battery System User Manual (GR-UM-479-A-03, file dated 202609, au.growatt.com), page 36 (PDF page 39), in the table whose Battery Model columns are ALP 45.0L-E2 and ALP 50.0L-E2; the row spans both columns. The table's separate PACK certification row (row 22) does not list UL 1973. Captured September 29, 2026. Cell scope does not certify the assembled battery. No issuer, certificate or report number is printed; the issuer's record was not checked.