Ensure that the ground cable is securely connected; install the ground wire
Printed as "Ensure that the ground cable is securely connected." in the Growatt User Manual for the ALP 5.0L-E2 Battery System (GR-UM-317-A-03, German site, 202605) (pages 8 and 25). Section 4.5.3.4 adds "To ensure system security, do not forget to install the ground wire."
Where: PDF pages 8 and 25, section 2.2.2 Operation Precautions; section 4.5.3.4 Single-column wiring
At least 300 mm above and on each side of a column; 300 mm to 800 mm between two floor-mounted columns; wall-mounted columns at least 100 mm above the ground
Printed as "Ground 300mm ≤d≤800mm ≥300mm ≥300mm" in the Growatt User Manual for the ALP 5.0L-E2 Battery System (GR-UM-317-A-03, German site, 202605) (pages 14 and 15). Read with the rendered Figures 4.2 and 4.3: ≥300 mm above the column and at both sides, 300 mm ≤ d ≤ 800 mm between two floor-mounted columns, and ≥100 mm from the ground to the bottom of a wall-mounted column.
Where: PDF pages 14 and 15, section 4.2, Figure 4.2 Floor-mounted installation and Figure 4.3 Wall-mounted Installation
Charged Reviews classified this product from the documents it is based on. It is our own grouping, not a manufacturer claim.
Printed as "Einfache Installation dank modularem und stapelbarem Design" and "Boden-/Wandmontage". Classified as Stackable from the maker's own words for this model; the maker also prints wall/floor mounting, quoted here.
Printed as "IFpP/51/161/119/ [(1P16S)3P]M/ -10+50/90" in the Growatt User Manual for the ALP 5.0L-E2 Battery System (GR-UM-317-A-03, German site, 202605) (page 33). The ALP 15.0L-E2 is 3 ALP 5.0L modules in parallel ("Number of parallel battery systems 3" in the same table); each module is "sixteen serial connection (1P16S)" (section 1.1).
Where: PDF page 33, chapter 7 Technical Specifications, Battery Designation row, ALP 15.0L-E2 column
Printed as "300Ah/15kWh" in the ALP 15.0L-E2 column of the manual's Nominal Capacity/Energy row; the Rated Capacity/Energy row prints the same figures.
Where: Chapter 7 Technical Specifications, PDF page 33, row "Nominal Capacity/Energy", first column (ALP 15.0L-E2)
PCS: CAN communication; LINK-IN: CAN communication; LINK-OUT: CAN communication; USB interface; Cluster-in communication; Cluster-out communication
Printed as "8 PCS CAN communication" in the Growatt User Manual for the ALP 5.0L-E2 Battery System (GR-UM-317-A-03, German site, 202605) (page 5). Ports of each ALP 5.0L battery module's operation panel. The ALP 15.0L-E2 is built from 3 such modules.
Where: PDF page 5, section 1.2.2 Introduction to the battery operation panel
Do not turn the PACK upside down, and ensure that the floor is level
Printed as "Do not turn the PACK upside down, and ensure that the floor is level." in the Growatt User Manual for the ALP 5.0L-E2 Battery System (GR-UM-317-A-03, German site, 202605) (page 14). Figure 4.2 shows the floor-mounted column at 90° to the ground.
Where: PDF page 14, section 4.2 Basic installation requirements
The German datasheet prints a narrower storage range. The user manual prints storage bands up to 35 to 50 °C for 6 months; Growatt's German datasheet (202607) prints -20 °C to 40 °C, at most 6 months. The manual's range is shown and the datasheet range is kept beside it.
Printed as three storage bands: -20 to 25 ℃ for 12 months, 25 to 35 ℃ for 9 months and 35 to 50 ℃ for 6 months, humidity 5% to 95% RH; the range recorded spans the three bands, each with its own time limit.
Where: Chapter 7 Technical Specifications, PDF page 33, row "Storage conditions", first column (ALP 15.0L-E2)
Sources
-20 to 40 °C
Printed as "-20 °C bis 40 °C; max. 6 Monate; 95 % r. F." in the German datasheet.
Printed as "The whole battery system communicates to Power Conversion System (PCS) via CAN." in the Growatt User Manual for the ALP 5.0L-E2 Battery System (GR-UM-317-A-03, German site, 202605) (page 6). The PCS port pin definition (section 4.5.3.1) lists CAN_H and CAN_L.
Where: PDF page 6, section 1.3 Working Principle and Function
112.97 L* (Calculated enclosure volume: W × H × D in mm ÷ 1,000,000)W: 690 × H: 885 × D: 185 mm / W: 27.2 × H: 34.8 × D: 7.28 in132 kg / 291 lb0.13 kWh/L* (Rated or usable capacity shown on this card ÷ enclosure volume)
Evidence score
13/100Missing details20% documented
The Evidence score uses the priorities you choose. It counts published documents, such as certificates and warranty terms, and it compares a documented figure with the best documented figure of the same kind. It does not count owner reviews, and it is not a verdict on product quality or on how many people have reviewed it. A low score can mean little is documented, or that a documented figure is below the best of its kind. Undisclosed data scores 0.
Missing details. This number counts only the evidence recorded so far. The source review for this product is not finished, or the maker has not disclosed enough, so the number can only go up.
Missing for this product: Certificates evidence needed; Warranty energy disclosure evidence needed; Lifetime / capacity evidence needed; Cell model disclosure evidence needed.
48 V · Stackable · Rated capacity
The warranty term and the lifetime energy are each scored against the best documented value for a home storage battery: a value earns its share of that best, times the weight. A documented value always earns points; an undisclosed one earns 0.
Research pending, 0 points: Certificates, Warranty energy disclosure, Cell model disclosure.
Computed from public specifications and evidence records. Warranty duration is not service quality; certificate evidence points are not a safety rating. Compatibility and installation limits still apply.
What this shows: what each record says and how far it reaches. It does not mean the product is approved.
StandardEvidenceStatusSource
UL 1973manufacturer claimpresent at observation[1][2]
Scope
cell
Covered models
ALP 15.0L-E2
Limitations
A manufacturer claim at cell level, not a listing or certificate. Printed as "Cell safety certification IEC62619/UL1973" (row 21) in chapter 7, Technical Specifications, of Growatt's ALP 5.0L-E2 Battery System User Manual (GR-UM-317-A-03, file dated 202605, de.growatt.com), page 30 (PDF page 33), in the table whose Battery Model columns are ALP 15.0L-E2 and ALP 20.0L-E2; the row spans both columns. The table's separate PACK certification row (row 22) does not list UL 1973. Captured September 29, 2026. Growatt's German ALP LV datasheet (file dated 202607, page 2, captured September 29, 2026), whose columns include ALP 15.0L-E2, also prints "UL1973" in its certification line ("IEC62619, IEC63056, IEC 62040, UL1973, CE+FCC,UKCA, UN38.3, ROHS, AU-CEC") without saying whether it covers the cells or the pack; this row follows the manual, which places UL 1973 under cell safety. Cell scope does not certify the assembled battery. No issuer, certificate or report number is printed; the issuer's record was not checked.
UL 1973Manufacturer claim · cellClaimedListed when checked
A manufacturer claim at cell level, not a listing or certificate. Printed as "Cell safety certification IEC62619/UL1973" (row 21) in chapter 7, Technical Specifications, of Growatt's ALP 5.0L-E2 Battery System User Manual (GR-UM-317-A-03, file dated 202605, de.growatt.com), page 30 (PDF page 33), in the table whose Battery Model columns are ALP 15.0L-E2 and ALP 20.0L-E2; the row spans both columns. The table's separate PACK certification row (row 22) does not list UL 1973. Captured September 29, 2026. Growatt's German ALP LV datasheet (file dated 202607, page 2, captured September 29, 2026), whose columns include ALP 15.0L-E2, also prints "UL1973" in its certification line ("IEC62619, IEC63056, IEC 62040, UL1973, CE+FCC,UKCA, UN38.3, ROHS, AU-CEC") without saying whether it covers the cells or the pack; this row follows the manual, which places UL 1973 under cell safety. Cell scope does not certify the assembled battery. No issuer, certificate or report number is printed; the issuer's record was not checked.
Captured by scripts/prepare-brand-sweep-sep21.mjs on 2026-09-29.
Location: Chapter 7, Technical Specifications (PDF pages 32 to 36)
Retrieved Sep 28, 2026
Growatt's English user manual for the ALP 5.0L-E2 battery system in the revision linked from the German ALP page and served from de.growatt.com, captured September 29, 2026. Chapter 7 prints one technical table per pair of configurations, ALP 5.0L-E2 to ALP 50.0L-E2. The primary source for the European records. Manufacturer claims, not independently verified.
Archived copies
Archived copy of a document published by Shenzhen Growatt New Energy Co., Ltd.. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email [email protected].
UL 1973Manufacturer claim · cellClaimedListed when checked
A manufacturer claim at cell level, not a listing or certificate. Printed as "Cell safety certification IEC62619/UL1973" (row 21) in chapter 7, Technical Specifications, of Growatt's ALP 5.0L-E2 Battery System User Manual (GR-UM-317-A-03, file dated 202605, de.growatt.com), page 30 (PDF page 33), in the table whose Battery Model columns are ALP 15.0L-E2 and ALP 20.0L-E2; the row spans both columns. The table's separate PACK certification row (row 22) does not list UL 1973. Captured September 29, 2026. Growatt's German ALP LV datasheet (file dated 202607, page 2, captured September 29, 2026), whose columns include ALP 15.0L-E2, also prints "UL1973" in its certification line ("IEC62619, IEC63056, IEC 62040, UL1973, CE+FCC,UKCA, UN38.3, ROHS, AU-CEC") without saying whether it covers the cells or the pack; this row follows the manual, which places UL 1973 under cell safety. Cell scope does not certify the assembled battery. No issuer, certificate or report number is printed; the issuer's record was not checked.
Captured by scripts/prepare-brand-sweep-sep21.mjs on 2026-09-29.
Location: Page 2, Datenblatt table
Retrieved Sep 28, 2026
Growatt's German-language datasheet for the ALP LV battery system (columns ALP 5.0L to ALP 50.0L, models ALP 5.0L-E2 to ALP 50.0L-E2), linked from the German ALP page, captured September 29, 2026. Its text layer prints the table cells out of order, so column-specific values were read from a local rendering of the unaltered page 2; quotes are given only where the text layer prints them in one piece. Manufacturer claims, not independently verified.
Archived copies
Archived copy of a document published by Shenzhen Growatt New Energy Co., Ltd.. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email [email protected].
Captured by scripts/prepare-brand-sweep-sep21.mjs on 2026-09-29.
Location: Page text and download list
Retrieved Sep 28, 2026
Growatt's German product page for the ALP LV battery, captured September 29, 2026. Cited for the links to the German datasheet, the user manual and the EU quick guide. Manufacturer claims, not independently verified.
Earlier revisions, archived captures and copies published by someone other than the manufacturer. Every one stays reachable.
Archived documents
User Manual, ALP 5.0L-E2 Battery System (Growatt, GR-UM-317-A-03, file dated 202605)
Archived copy of a document published by Shenzhen Growatt New Energy Co., Ltd.. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email [email protected].
ALP LV Batteriesystem Datenblatt (Growatt, German, file dated 202607)
Archived copy of a document published by Shenzhen Growatt New Energy Co., Ltd.. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email [email protected].
No sourced accessories or replacement parts listed yet.
Model history
Model identity
Model
ALP 15.0L-E2
Manufacturer SKU unknown · EU market
Observed Sep 29, 2026
UL 1973: claimed
Cell / component only. A manufacturer claim at cell level, not a listing or certificate. Printed as "Cell safety certification IEC62619/UL1973" (row 21) in chapter 7, Technical Specifications, of Growatt's ALP 5.0L-E2 Battery System User Manual (GR-UM-317-A-03, file dated 202605, de.growatt.com), page 30 (PDF page 33), in the table whose Battery Model columns are ALP 15.0L-E2 and ALP 20.0L-E2; the row spans both columns. The table's separate PACK certification row (row 22) does not list UL 1973. Captured September 29, 2026. Growatt's German ALP LV datasheet (file dated 202607, page 2, captured September 29, 2026), whose columns include ALP 15.0L-E2, also prints "UL1973" in its certification line ("IEC62619, IEC63056, IEC 62040, UL1973, CE+FCC,UKCA, UN38.3, ROHS, AU-CEC") without saying whether it covers the cells or the pack; this row follows the manual, which places UL 1973 under cell safety. Cell scope does not certify the assembled battery. No issuer, certificate or report number is printed; the issuer's record was not checked.