conditions: Printed as "AES RACKMOUNT 48-48-5120-H (Product Model 900-0067)" on Discover's product page and as the second battery module column of the AES RACKMOUNT sell sheet 885-0040 Rev E. Greentech lists the part as 48-48-5120H, without the hyphen.
Printed as "Chemistry LiFePO4" in Discover's AES RACKMOUNT Installation and Operation Manual (805-0043 REVD), Table 3-2, AES RACKMOUNT Mechanical Specifications. Re-cited on 1 October 2026 to the manufacturer's own document; previously cited to Discover Energy Systems (discoverenergysys.com), which stays listed as an additional source.
Where: PDF page 8, Table 3-2, AES RACKMOUNT Mechanical Specifications
Ground each module to the chassis ground using a #6 gauge wire or larger diameter. Ground the entire chassis to earth using a #4 gauge wire or larger diameter.
Printed as "Ground each module to the chassis ground using a #6 gauge wire or larger diameter. Ground the entire chassis to earth using a #4 gauge wire or larger diameter." in Discover's AES RACKMOUNT Installation and Operation Manual (805-0043 REVD), section 6.5 Equipment Ground.
Printed as "Terminal Connector Amphenol SurLok Plus" in Discover's AES RACKMOUNT Installation and Operation Manual (805-0043 REVD), Table 3-2, AES RACKMOUNT Mechanical Specifications. Positive and negative connector part numbers are printed as C10-730186-200 and C10-730186-100. Re-cited on 1 October 2026 to the manufacturer's own document; previously cited to Discover Energy Systems (discoverenergysys.com), which stays listed as an additional source.
Where: PDF page 8, Table 3-2, AES RACKMOUNT Mechanical Specifications
Printed as "Weight 44.0 kg (97.0 lb)" in Discover's AES RACKMOUNT Installation and Operation Manual (805-0043 REVD), Table 3-2, AES RACKMOUNT Mechanical Specifications. Re-cited on 1 October 2026 to the manufacturer's own document; previously cited to Discover Energy Systems (discoverenergysys.com); Discover (discoverbattery.com), which stays listed as an additional source.
Where: PDF page 8, Table 3-2, AES RACKMOUNT Mechanical Specifications
Printed as "Capacity 1 Hr 100 Ah" in Discover's AES RACKMOUNT Installation and Operation Manual (805-0043 REVD), Table 3-1, AES RACKMOUNT Electrical Specifications. Re-cited on 1 October 2026 to the manufacturer's own document; previously cited to Discover Energy Systems (discoverenergysys.com); Discover (discoverbattery.com), which stays listed as an additional source.
Where: PDF page 7, Table 3-1, AES RACKMOUNT Electrical Specifications
Printed as "The battery module with part number 48-48-5120-H is equipped with internal heating." in Discover's AES RACKMOUNT Installation and Operation Manual (805-0043 REVD), section 7.2 Internal Heating (48-48-5120-H). Re-cited on 1 October 2026 to the manufacturer's own document; previously cited to Discover (discoverbattery.com); Discover Energy Systems (discoverenergysys.com), which stays listed as an additional source.
Where: PDF page 16, section 7.2 Internal Heating (48-48-5120-H)
Printed as "Peak Discharge Current (3 seconds) 218 A RMS" in the Discover AES Rackmount installation and operation manual (page 7, Table 3-1 Electrical Specifications).
Where: PDF page 7, Table 3-1 Electrical Specifications
At least 44.45 mm (1.75 in) (1U) above the top cover, between battery modules, and to the sides for airflow
Printed as "Allow spacing of at least 44.45 mm (1.75 in) (1U) above the top cover, between battery modules, and to the sides for airflow." in Discover's AES RACKMOUNT Installation and Operation Manual (805-0043 REVD), section 9.2, Ventilation.
W 439.2 × H 133.5 × L 497.3 mm / W 17.29 × H 5.26 × L 19.58 in converted
Printed as "Total Length 497.3 mm (19.6 in) Body Width 439.2 mm (17.3 in)" in Discover's AES RACKMOUNT Installation and Operation Manual (805-0043 REVD), Table 3-2, AES RACKMOUNT Mechanical Specifications. Printed as "Height 133.5 mm (5.3 in) (3U)" there as well. The front face is printed as 482.6 mm (19 in) wide. Re-cited on 1 October 2026 to the manufacturer's own document; previously cited to Discover Energy Systems (discoverenergysys.com), which stays listed as an additional source.
Where: PDF page 8, Table 3-2, AES RACKMOUNT Mechanical Specifications
Charged Reviews classified this product from the documents it is based on. It is our own grouping, not a manufacturer claim.
Printed as "Form Factor 19 Inch Rack Mount 3U 19 Inch Rack Mount 3U" and "950-0050 Quick Stack Rack (3U) Brackets for stacking Battery Modules". Classified as Server rack from the maker's own words for this model; the maker's "Quick Stack Rack" brackets let the modules be stacked, quoted here (PM decision 2026-10-13: a 3U, 19-inch rack chassis that can also be stacked is Server rack).
Printed as "The LYNK Port enables multiple Discover battery modules to communicate"; "4 CAN Low 5 CAN High" in the Discover AES Rackmount installation and operation manual (page 15, section 6.4 LYNK Port).
Printed as "IP Rating IP20" in Discover's AES RACKMOUNT Installation and Operation Manual (805-0043 REVD), Table 3-2, AES RACKMOUNT Mechanical Specifications. Re-cited on 1 October 2026 to the manufacturer's own document; previously cited to Discover Energy Systems (discoverenergysys.com); Discover (discoverbattery.com), which stays listed as an additional source.
Where: PDF page 8, Table 3-2, AES RACKMOUNT Mechanical Specifications
Printed as "Max Charge Current (1 hour) 95 A" in Discover's AES RACKMOUNT Installation and Operation Manual (805-0043 REVD), Table 3-1, AES RACKMOUNT Electrical Specifications. A one hour rating; the continuous rating is 70 A.
Where: PDF page 7, Table 3-1, AES RACKMOUNT Electrical Specifications
Printed as "Peak Discharge Current (3 seconds) 218 A RMS" in Discover's AES RACKMOUNT Installation and Operation Manual (805-0043 REVD), Table 3-1, AES RACKMOUNT Electrical Specifications. For 3 seconds, RMS. Re-cited on 1 October 2026 to the manufacturer's own document; previously cited to Discover Energy Systems (discoverenergysys.com); Discover (discoverbattery.com), which stays listed as an additional source.
Where: PDF page 7, Table 3-1, AES RACKMOUNT Electrical Specifications
Printed as "Appropriate cable gauge (3 AWG, 26.5 mm2. 4AWG, 25 mm2 is also acceptable.)" in Discover's AES RACKMOUNT Installation and Operation Manual (805-0043 REVD), section 9.3 DC Cables. DC cables must be stranded copper rated 90 °C minimum.
Printed as "Nominal Voltage 51.2 V" in Discover's AES RACKMOUNT Installation and Operation Manual (805-0043 REVD), Table 3-1, AES RACKMOUNT Electrical Specifications. The table covers the 48-48-5120 and the 48-48-5120-H together. Re-cited on 1 October 2026 to the manufacturer's own document; previously cited to Discover (discoverbattery.com), which stays listed as an additional source.
Where: PDF page 7, Table 3-1, AES RACKMOUNT Electrical Specifications
Printed as "Do not install the battery module in series." in Discover's AES RACKMOUNT Installation and Operation Manual (805-0043 REVD), section 1, Electric shock and fire hazard warning.
Where: PDF page 4, section 1, Electric shock and fire hazard warning
Printed as "Usable Capacity 1 battery module 218 A 95 A 70 A 95 A 70 A 5,120 Wh" in Discover's AES RACKMOUNT Installation and Operation Manual (805-0043 REVD), Table 3-7, DC Capacity Values for Sample Battery Module Systems, 1 battery module row. The last figure of the one module row is the usable capacity, printed in watt hours at 25°C (77°F); it is shown here in kilowatt hours.
Where: PDF page 12, Table 3-7, DC Capacity Values for Sample Battery Module Systems, 1 battery module row
Printed as "Breaker (K-Curve) Dual 100 A (2-Pole ganged)" in the Discover AES Rackmount installation and operation manual (page 7, Table 3-1 Electrical Specifications).
Where: PDF page 7, Table 3-1 Electrical Specifications
Printed as "The maximum number of battery modules installed in a parallel configuration is 24." in Discover's AES RACKMOUNT Installation and Operation Manual (805-0043 REVD), section 3.6, note.
Printed as "Nominal Energy (kWh) 5.12" on the product page and "Nominal Energy 5.12 kWh 5.12 kWh" on the sell sheet, whose second column is 48-48-5120-H. Specifications at 25 °C.
Where: Product page Electrical Specifications; sell sheet Nominal Energy row
Printed as "LYNK Port x 2" in Discover's AES RACKMOUNT Installation and Operation Manual (805-0043 REVD), section 6 Features, Figure 3 item 7. Section 6.4.1 prints the LYNK Port as an RJ45 connector carrying CAN Low and CAN High.
Printed as "Max Continuous Charge Current (c) 70 A" in Discover's AES RACKMOUNT Installation and Operation Manual (805-0043 REVD), Table 3-1, AES RACKMOUNT Electrical Specifications. Note (c): the rating the battery withstands for two back-to-back full charge and discharge cycles without tripping overtemperature protection at 25°C (77°F) ambient. The table also prints "Max Charge Current (1 hour) 95 A". Re-cited on 1 October 2026 to the manufacturer's own document; previously cited to Discover Energy Systems (discoverenergysys.com), which stays listed as an additional source.
Where: PDF page 7, Table 3-1, AES RACKMOUNT Electrical Specifications
Printed as "Max Discharge Current (1 hour) 95 A" in Discover's AES RACKMOUNT Installation and Operation Manual (805-0043 REVD), Table 3-1, AES RACKMOUNT Electrical Specifications. A one hour rating; the continuous rating is 70 A.
Where: PDF page 7, Table 3-1, AES RACKMOUNT Electrical Specifications
Printed as "Charge Operating Temperature Range (a)(b) 4°C to 52°C (39.2°F to 125.6°F)" in Discover's AES RACKMOUNT Installation and Operation Manual (805-0043 REVD), Table 3-3, AES RACKMOUNT Environmental Specifications. Cell temperature, not ambient temperature. Re-cited on 1 October 2026 to the manufacturer's own document; previously cited to Discover Energy Systems (discoverenergysys.com), which stays listed as an additional source.
Where: PDF page 9, Table 3-3, AES RACKMOUNT Environmental Specifications
Printed as "internal temperature is below 5°C (41°F) and the battery module is either connected to a charging source" in Discover's AES RACKMOUNT Installation and Operation Manual (805-0043 REVD), section 7.2 Internal Heating (48-48-5120-H). Heating stops when the internal temperature reaches 8°C (46.4°F).
Where: PDF page 16, section 7.2 Internal Heating (48-48-5120-H)
Printed as "Charge Absorption Voltage - U1 MAX 55.2 V" in the Discover AES Rackmount installation and operation manual (page 7, Table 3-1 Electrical Specifications).
Where: PDF page 7, Table 3-1 Electrical Specifications
Install the battery module in any direction other than face down. Do not install face-down.
Printed as "Install the battery module in any direction other than face down. Do not install face-down." in Discover's AES RACKMOUNT Installation and Operation Manual (805-0043 REVD), section 9.2, Orientation.
Printed as "Storage Temperature (1 month) (d) -20°C to 55°C (-4°F to 131°F)" in Discover's AES RACKMOUNT Installation and Operation Manual (805-0043 REVD), Table 3-3, AES RACKMOUNT Environmental Specifications. The one month storage range; the table also prints "Storage Temperature (6 months) (d) -10°C to 30°C (14°F to 86°F)". Re-cited on 1 October 2026 to the manufacturer's own document; previously cited to Discover Energy Systems (discoverenergysys.com), which stays listed as an additional source.
Where: PDF page 9, Table 3-3, AES RACKMOUNT Environmental Specifications
Printed as "Max Continuous Discharge Current (c) 70 A" in Discover's AES RACKMOUNT Installation and Operation Manual (805-0043 REVD), Table 3-1, AES RACKMOUNT Electrical Specifications. Note (c) applies as for the charge current. The table also prints "Max Discharge Current (1 hour) 95 A". Re-cited on 1 October 2026 to the manufacturer's own document; previously cited to Discover Energy Systems (discoverenergysys.com); Discover (discoverbattery.com), which stays listed as an additional source.
Where: PDF page 7, Table 3-1, AES RACKMOUNT Electrical Specifications
Additional external DC fusing is required to protect the battery cables
Printed as "Additional external DC fusing is required to protect the battery cables" in the Discover AES Rackmount installation and operation manual (page 14, section 6.1 Battery Module Breaker).
Where: PDF page 14, section 6.1 Battery Module Breaker
Printed as "Discharge Operating Temperature Range (a) -17°C to 52°C (1.4°F to 125.6°F)" in Discover's AES RACKMOUNT Installation and Operation Manual (805-0043 REVD), Table 3-3, AES RACKMOUNT Environmental Specifications. Cell temperature, not ambient temperature. Re-cited on 1 October 2026 to the manufacturer's own document; previously cited to Discover Energy Systems (discoverenergysys.com), which stays listed as an additional source.
Where: PDF page 9, Table 3-3, AES RACKMOUNT Environmental Specifications
Printed as "Low Voltage Disconnect Recommended 48.0 V" in Discover's AES RACKMOUNT Installation and Operation Manual (805-0043 REVD), Table 3-1, AES RACKMOUNT Electrical Specifications. The recommended setting; the battery module itself disconnects at "Low Voltage Disconnect (b) 40.0 V".
Where: PDF page 7, Table 3-1, AES RACKMOUNT Electrical Specifications
Printed as "Charge Bulk Voltage - Bulk Vdc 55.2 V" in Discover's AES RACKMOUNT Installation and Operation Manual (805-0043 REVD), Table 3-1, AES RACKMOUNT Electrical Specifications. The table also prints "Charge Float Voltage - U2 53.6 V". Re-cited on 1 October 2026 to the manufacturer's own document; previously cited to Discover Energy Systems (discoverenergysys.com), which stays listed as an additional source.
Where: PDF page 7, Table 3-1, AES RACKMOUNT Electrical Specifications
29.16 L* (Calculated enclosure volume: W × H × D in mm ÷ 1,000,000)W: 439.2 × H: 133.5 × L: 497.3 mm / W: 17.29 × H: 5.26 × L: 19.58 in44 kg / 97 lb0.18 kWh/L* (Rated or usable capacity shown on this card ÷ enclosure volume)
Evidence score
45/100Missing details45% documented
The Evidence score uses the priorities you choose. It counts published documents, such as certificates and warranty terms, and it compares a documented figure with the best documented figure of the same kind. It does not count owner reviews, and it is not a verdict on product quality or on how many people have reviewed it. A low score can mean little is documented, or that a documented figure is below the best of its kind. Undisclosed data scores 0.
Missing details. This number counts only the evidence recorded so far. The source review for this product is not finished, or the maker has not disclosed enough, so the number can only go up.
Missing for this product: Warranty term needed; Warranty energy disclosure evidence needed; Lifetime / capacity evidence needed; Cell model disclosure evidence needed.
48 V · Server rack · Rated capacity
The warranty term and the lifetime energy are each scored against the best documented value for a home storage battery: a value earns its share of that best, times the weight. A documented value always earns points; an undisclosed one earns 0.
CertificatesCEC · IEC 62619 +4CEC listed45 / 45
100 evidence points · 45% weight
CEC listing: full credit for the certificate criterion. Exact model found in the dated CEC equipment list. This is not a safety certification or system approval. Applies: CEC; UL 9540; UL 1973.
Research pending, 0 points: Warranty term, Warranty energy disclosure, Cell model disclosure.
Computed from public specifications and evidence records. Warranty duration is not service quality; certificate evidence points are not a safety rating. Compatibility and installation limits still apply.
What this shows: what each record says and how far it reaches. It does not mean the product is approved.
StandardEvidenceStatusSource
IEC 62619manufacturer claimpresent at observation[1]
Scope
unresolved document set
Covered models
48-48-5120-H
Limitations
Printed as "IEC 62619" under Certification Standards on Discover's 48-48-5120-H page. No certificate was read. The sell sheet 885-0040 Rev E prints its regulatory row as "(PENDING)". Recorded as the manufacturer's claim.
UL 1973manufacturer claimpresent at observation[1]
Scope
battery pack scope unverified
Covered models
48-48-5120-H
Limitations
Printed as "UL 1973" under Certification Standards on Discover's 48-48-5120-H page. No certificate or directory listing was read, and the sell sheet prints its regulatory row as "(PENDING)". Recorded as the manufacturer's claim.
Discover conditions this claim on installation in the AES Slimline Enclosure 950-0053 ("UL9540 (when installed using the AES Slimline Enclosure 950-0053)"), and its Quick Stack Rack text states that installation method is not certified to UL9540. No certificate was read. Recorded as the manufacturer's claim.
UL 1973authority listing reportedlisted as of snapshot[4]
Scope
equipment listing
Covered models
48-48-5120-H
Limitations
Listed on the California Energy Commission Battery List (data unchanged since October 1, 2026; downloaded October 11, 2026) as Discover Energy Systems Corp. "48-48-5120-H": UL 1973, certifying entity TUV Rheinland, certificate date 2023-11-02, Ed. 2 : 2018, CEC listing date 2023-12-21. A state equipment list entry, not the certification body's own record.
CECauthority listing reportedlisted as of snapshot[4]
Scope
equipment listing
Covered models
48-48-5120-H
Limitations
Model 48-48-5120-H listed on the California Energy Commission Battery List (data unchanged since October 1, 2026; downloaded October 11, 2026) under Discover Energy Systems Corp., as "48-48-5120-H", CEC listing date 2023-12-21. This is an equipment listing, not UL certification or complete-system approval.
Archived copy of a document published by Discover Energy Systems. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email [email protected].
Archived copy of a document published by Discover. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email [email protected].
Captured by scripts/prepare-brand-sweep-sep21.mjs on 2026-09-24.
Location: Heading; Mechanical and Electrical Specifications tables; Certification Standards
Retrieved Sep 23, 2026
Discover Energy Systems' own product page for the heated AES RACKMOUNT module, captured on September 24, 2026. It prints the model with Discover's product model number 900-0067, mechanical and electrical specification tables at 25 °C and a certification list. The page carries no revision; its print footer shows the capture date.
Archived copy of a document published by Discover. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email [email protected].
Discover AES Rackmount installation and operation manual
Archived copy of a document published by Discover Energy Systems. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email [email protected].
Product / system scope unresolved. Listed on the California Energy Commission Battery List (data unchanged since October 1, 2026; downloaded October 11, 2026) as Discover Energy Systems Corp. "48-48-5120-H": UL 1973, certifying entity TUV Rheinland, certificate date 2023-11-02, Ed. 2 : 2018, CEC listing date 2023-12-21. A state equipment list entry, not the certification body's own record.
Product / system scope unresolved. Model 48-48-5120-H listed on the California Energy Commission Battery List (data unchanged since October 1, 2026; downloaded October 11, 2026) under Discover Energy Systems Corp., as "48-48-5120-H", CEC listing date 2023-12-21. This is an equipment listing, not UL certification or complete-system approval.
note: CEC listing: full credit for the certificate criterion. Exact model found in the dated CEC equipment list. This is not a safety certification or system approval. Applies: CEC; UL 9540; UL 1973.