Charged ReviewsSaved 0Compare 0Login
Discover AES RACKMOUNT 48-48-5120-H
Discover
DC battery module

Discover AES RACKMOUNT 48-48-5120-H

Key specs

Nominal voltage51.2 V
Capacity100 Ah
Weight44 kg / 97 lb converted
Nominal energy5.12 kWh
Continuous discharge70 A
Maximum charge95 A

All specifications

Identity

BrandDiscover · Website
Model48-48-5120-H
MarketUS
Manufacturer SKU48-48-5120-H
SKU detail
locator: Product page heading; sell sheet battery module columns
conditions: Printed as "AES RACKMOUNT 48-48-5120-H (Product Model 900-0067)" on Discover's product page and as the second battery module column of the AES RACKMOUNT sell sheet 885-0040 Rev E. Greentech lists the part as 48-48-5120H, without the hyphen.
Sources: [1] [2]
FieldValueConditionsSource
ChemistryLiFePO4
Printed as "Chemistry LiFePO4" in Discover's AES RACKMOUNT Installation and Operation Manual (805-0043 REVD), Table 3-2, AES RACKMOUNT Mechanical Specifications. Re-cited on 1 October 2026 to the manufacturer's own document; previously cited to Discover Energy Systems (discoverenergysys.com), which stays listed as an additional source.
Where: PDF page 8, Table 3-2, AES RACKMOUNT Mechanical Specifications
[3] [1]
GroundingGround each module to the chassis ground using a #6 gauge wire or larger diameter. Ground the entire chassis to earth using a #4 gauge wire or larger diameter.
Printed as "Ground each module to the chassis ground using a #6 gauge wire or larger diameter. Ground the entire chassis to earth using a #4 gauge wire or larger diameter." in Discover's AES RACKMOUNT Installation and Operation Manual (805-0043 REVD), section 6.5 Equipment Ground.
Where: PDF page 16, section 6.5 Equipment Ground
[3]
TerminalsAmphenol SurLok Plus
Printed as "Terminal Connector Amphenol SurLok Plus" in Discover's AES RACKMOUNT Installation and Operation Manual (805-0043 REVD), Table 3-2, AES RACKMOUNT Mechanical Specifications. Positive and negative connector part numbers are printed as C10-730186-200 and C10-730186-100. Re-cited on 1 October 2026 to the manufacturer's own document; previously cited to Discover Energy Systems (discoverenergysys.com), which stays listed as an additional source.
Where: PDF page 8, Table 3-2, AES RACKMOUNT Mechanical Specifications
[3] [1]
Weight44 kg / 97 lb converted
Printed as "Weight 44.0 kg (97.0 lb)" in Discover's AES RACKMOUNT Installation and Operation Manual (805-0043 REVD), Table 3-2, AES RACKMOUNT Mechanical Specifications. Re-cited on 1 October 2026 to the manufacturer's own document; previously cited to Discover Energy Systems (discoverenergysys.com); Discover (discoverbattery.com), which stays listed as an additional source.
Where: PDF page 8, Table 3-2, AES RACKMOUNT Mechanical Specifications
[3] [1] [2]
Capacity100 Ah
Printed as "Capacity 1 Hr 100 Ah" in Discover's AES RACKMOUNT Installation and Operation Manual (805-0043 REVD), Table 3-1, AES RACKMOUNT Electrical Specifications. Re-cited on 1 October 2026 to the manufacturer's own document; previously cited to Discover Energy Systems (discoverenergysys.com); Discover (discoverbattery.com), which stays listed as an additional source.
Where: PDF page 7, Table 3-1, AES RACKMOUNT Electrical Specifications
[3] [1] [2]
Self heatingyes
Printed as "The battery module with part number 48-48-5120-H is equipped with internal heating." in Discover's AES RACKMOUNT Installation and Operation Manual (805-0043 REVD), section 7.2 Internal Heating (48-48-5120-H). Re-cited on 1 October 2026 to the manufacturer's own document; previously cited to Discover (discoverbattery.com); Discover Energy Systems (discoverenergysys.com), which stays listed as an additional source.
Where: PDF page 16, section 7.2 Internal Heating (48-48-5120-H)
[3] [2] [1]
Surge output218 A for 3 s
Printed as "Peak Discharge Current (3 seconds) 218 A RMS" in the Discover AES Rackmount installation and operation manual (page 7, Table 3-1 Electrical Specifications).
Where: PDF page 7, Table 3-1 Electrical Specifications
[3]
Case materialGalvanized steel sheet
Printed as "Case Material Galvanized Steel Sheet".
Where: Product page Mechanical Specifications, Case Material
[1]
ClearancesAt least 44.45 mm (1.75 in) (1U) above the top cover, between battery modules, and to the sides for airflow
Printed as "Allow spacing of at least 44.45 mm (1.75 in) (1U) above the top cover, between battery modules, and to the sides for airflow." in Discover's AES RACKMOUNT Installation and Operation Manual (805-0043 REVD), section 9.2, Ventilation.
Where: PDF page 21, section 9.2, Ventilation
[3]
DimensionsW 439.2 × H 133.5 × L 497.3 mm / W 17.29 × H 5.26 × L 19.58 in converted
Printed as "Total Length 497.3 mm (19.6 in) Body Width 439.2 mm (17.3 in)" in Discover's AES RACKMOUNT Installation and Operation Manual (805-0043 REVD), Table 3-2, AES RACKMOUNT Mechanical Specifications. Printed as "Height 133.5 mm (5.3 in) (3U)" there as well. The front face is printed as 482.6 mm (19 in) wide. Re-cited on 1 October 2026 to the manufacturer's own document; previously cited to Discover Energy Systems (discoverenergysys.com), which stays listed as an additional source.
Where: PDF page 8, Table 3-2, AES RACKMOUNT Mechanical Specifications
[3] [1]
Battery format
Server rack
Site classificationBased onOfficial document
Details

Charged Reviews classified this product from the documents it is based on. It is our own grouping, not a manufacturer claim.

Printed as "Form Factor 19 Inch Rack Mount 3U 19 Inch Rack Mount 3U" and "950-0050 Quick Stack Rack (3U) Brackets for stacking Battery Modules". Classified as Server rack from the maker's own words for this model; the maker's "Quick Stack Rack" brackets let the modules be stacked, quoted here (PM decision 2026-10-13: a 3U, 19-inch rack chassis that can also be stacked is Server rack).

Official document: Discover AES RACKMOUNT sell sheet

Location: AES RACKMOUNT sell sheet (Discover, 885-0040 Rev E), page 2, specification table (Form Factor row, columns 48-48-5120 and 48-48-5120-H) and accessory table

CommunicationsCAN (LYNK Port)
Printed as "The LYNK Port enables multiple Discover battery modules to communicate"; "4 CAN Low 5 CAN High" in the Discover AES Rackmount installation and operation manual (page 15, section 6.4 LYNK Port).
Where: PDF page 15, section 6.4 LYNK Port
[3]
Enclosure ratingIP20
Printed as "IP Rating IP20" in Discover's AES RACKMOUNT Installation and Operation Manual (805-0043 REVD), Table 3-2, AES RACKMOUNT Mechanical Specifications. Re-cited on 1 October 2026 to the manufacturer's own document; previously cited to Discover Energy Systems (discoverenergysys.com); Discover (discoverbattery.com), which stays listed as an additional source.
Where: PDF page 8, Table 3-2, AES RACKMOUNT Mechanical Specifications
[3] [1] [2]
Maximum charge95 A
Printed as "Max Charge Current (1 hour) 95 A" in Discover's AES RACKMOUNT Installation and Operation Manual (805-0043 REVD), Table 3-1, AES RACKMOUNT Electrical Specifications. A one hour rating; the continuous rating is 70 A.
Where: PDF page 7, Table 3-1, AES RACKMOUNT Electrical Specifications
[3]
Peak discharge218 A
Printed as "Peak Discharge Current (3 seconds) 218 A RMS" in Discover's AES RACKMOUNT Installation and Operation Manual (805-0043 REVD), Table 3-1, AES RACKMOUNT Electrical Specifications. For 3 seconds, RMS. Re-cited on 1 October 2026 to the manufacturer's own document; previously cited to Discover Energy Systems (discoverenergysys.com); Discover (discoverbattery.com), which stays listed as an additional source.
Where: PDF page 7, Table 3-1, AES RACKMOUNT Electrical Specifications
[3] [1] [2]
Battery wire size3 AWG, 26.5 mm2. 4AWG, 25 mm2 is also acceptable.
Printed as "Appropriate cable gauge (3 AWG, 26.5 mm2. 4AWG, 25 mm2 is also acceptable.)" in Discover's AES RACKMOUNT Installation and Operation Manual (805-0043 REVD), section 9.3 DC Cables. DC cables must be stranded copper rated 90 °C minimum.
Where: PDF page 21, section 9.3 DC Cables
[3]
Nominal voltage51.2 V
Printed as "Nominal Voltage 51.2 V" in Discover's AES RACKMOUNT Installation and Operation Manual (805-0043 REVD), Table 3-1, AES RACKMOUNT Electrical Specifications. The table covers the 48-48-5120 and the 48-48-5120-H together. Re-cited on 1 October 2026 to the manufacturer's own document; previously cited to Discover (discoverbattery.com), which stays listed as an additional source.
Where: PDF page 7, Table 3-1, AES RACKMOUNT Electrical Specifications
[3] [2]
Series connectionno
Printed as "Do not install the battery module in series." in Discover's AES RACKMOUNT Installation and Operation Manual (805-0043 REVD), section 1, Electric shock and fire hazard warning.
Where: PDF page 4, section 1, Electric shock and fire hazard warning
[3]
Usable energy5.12 kWh
Converted: 5,120 Wh / 1000 = 5.12 kWh
Printed as "Usable Capacity 1 battery module 218 A 95 A 70 A 95 A 70 A 5,120 Wh" in Discover's AES RACKMOUNT Installation and Operation Manual (805-0043 REVD), Table 3-7, DC Capacity Values for Sample Battery Module Systems, 1 battery module row. The last figure of the one module row is the usable capacity, printed in watt hours at 25°C (77°F); it is shown here in kilowatt hours.
Where: PDF page 12, Table 3-7, DC Capacity Values for Sample Battery Module Systems, 1 battery module row
Sources
Converted: 5,120 Wh / 1000 = 5.12 kWh
[3]
Battery protectionBreaker (K-curve), dual 100 A (2-pole ganged)
Printed as "Breaker (K-Curve) Dual 100 A (2-Pole ganged)" in the Discover AES Rackmount installation and operation manual (page 7, Table 3-1 Electrical Specifications).
Where: PDF page 7, Table 3-1 Electrical Specifications
[3]
Included equipmentBattery module, CAT6 cable (12 in), 4 M6 mounting screws, #6 ground wire (200 mm), 5 serial number labels; spares: 2 M6 mounting screws, 6 M5 cage nuts
Printed as "1 Battery Module 1 CAT6 Cable (30.48 mm, 12 inch)"; "4 Mounting Screw (M6) 1 #6 Ground Wire (200 mm, 7.87 inch)"; "Spares: Mounting Screws M6 (2), Cage Nuts M5 (6)" in the Discover AES Rackmount installation and operation manual (page 6, Table 2-1 AES RACKMOUNT box contents). The box contents table prints the CAT6 cable length as 30.48 mm and 12 inch.
Where: PDF page 6, Table 2-1 AES RACKMOUNT box contents
[3]
Max parallel units24 count
Printed as "The maximum number of battery modules installed in a parallel configuration is 24." in Discover's AES RACKMOUNT Installation and Operation Manual (805-0043 REVD), section 3.6, note.
Where: PDF page 12, section 3.6, note
[3]
Nominal energy5.12 kWh
Printed as "Nominal Energy (kWh) 5.12" on the product page and "Nominal Energy 5.12 kWh 5.12 kWh" on the sell sheet, whose second column is 48-48-5120-H. Specifications at 25 °C.
Where: Product page Electrical Specifications; sell sheet Nominal Energy row
[1] [2]
Communication portsLYNK Port x 2
Printed as "LYNK Port x 2" in Discover's AES RACKMOUNT Installation and Operation Manual (805-0043 REVD), section 6 Features, Figure 3 item 7. Section 6.4.1 prints the LYNK Port as an RJ45 connector carrying CAN Low and CAN High.
Where: PDF page 13, section 6 Features, Figure 3 item 7
[3]
Continuous charge70 A
Printed as "Max Continuous Charge Current (c) 70 A" in Discover's AES RACKMOUNT Installation and Operation Manual (805-0043 REVD), Table 3-1, AES RACKMOUNT Electrical Specifications. Note (c): the rating the battery withstands for two back-to-back full charge and discharge cycles without tripping overtemperature protection at 25°C (77°F) ambient. The table also prints "Max Charge Current (1 hour) 95 A". Re-cited on 1 October 2026 to the manufacturer's own document; previously cited to Discover Energy Systems (discoverenergysys.com), which stays listed as an additional source.
Where: PDF page 7, Table 3-1, AES RACKMOUNT Electrical Specifications
[3] [1]
Maximum discharge95 A
Printed as "Max Discharge Current (1 hour) 95 A" in Discover's AES RACKMOUNT Installation and Operation Manual (805-0043 REVD), Table 3-1, AES RACKMOUNT Electrical Specifications. A one hour rating; the continuous rating is 70 A.
Where: PDF page 7, Table 3-1, AES RACKMOUNT Electrical Specifications
[3]
Charge temperature4 to 52 °C / 39 to 126 °F converted
Printed as "Charge Operating Temperature Range (a)(b) 4°C to 52°C (39.2°F to 125.6°F)" in Discover's AES RACKMOUNT Installation and Operation Manual (805-0043 REVD), Table 3-3, AES RACKMOUNT Environmental Specifications. Cell temperature, not ambient temperature. Re-cited on 1 October 2026 to the manufacturer's own document; previously cited to Discover Energy Systems (discoverenergysys.com), which stays listed as an additional source.
Where: PDF page 9, Table 3-3, AES RACKMOUNT Environmental Specifications
[3] [1]
Heating activation5 °C / 41 °F converted
Printed as "internal temperature is below 5°C (41°F) and the battery module is either connected to a charging source" in Discover's AES RACKMOUNT Installation and Operation Manual (805-0043 REVD), section 7.2 Internal Heating (48-48-5120-H). Heating stops when the internal temperature reaches 8°C (46.4°F).
Where: PDF page 16, section 7.2 Internal Heating (48-48-5120-H)
[3]
Max charge voltage55.2 V
Printed as "Charge Absorption Voltage - U1 MAX 55.2 V" in the Discover AES Rackmount installation and operation manual (page 7, Table 3-1 Electrical Specifications).
Where: PDF page 7, Table 3-1 Electrical Specifications
[3]
Mounting orientationInstall the battery module in any direction other than face down. Do not install face-down.
Printed as "Install the battery module in any direction other than face down. Do not install face-down." in Discover's AES RACKMOUNT Installation and Operation Manual (805-0043 REVD), section 9.2, Orientation.
Where: PDF page 21, section 9.2, Orientation
[3]
Storage temperature-20 to 55 °C / -4 to 131 °F converted
Printed as "Storage Temperature (1 month) (d) -20°C to 55°C (-4°F to 131°F)" in Discover's AES RACKMOUNT Installation and Operation Manual (805-0043 REVD), Table 3-3, AES RACKMOUNT Environmental Specifications. The one month storage range; the table also prints "Storage Temperature (6 months) (d) -10°C to 30°C (14°F to 86°F)". Re-cited on 1 October 2026 to the manufacturer's own document; previously cited to Discover Energy Systems (discoverenergysys.com), which stays listed as an additional source.
Where: PDF page 9, Table 3-3, AES RACKMOUNT Environmental Specifications
[3] [1]
Continuous discharge70 A
Printed as "Max Continuous Discharge Current (c) 70 A" in Discover's AES RACKMOUNT Installation and Operation Manual (805-0043 REVD), Table 3-1, AES RACKMOUNT Electrical Specifications. Note (c) applies as for the charge current. The table also prints "Max Discharge Current (1 hour) 95 A". Re-cited on 1 October 2026 to the manufacturer's own document; previously cited to Discover Energy Systems (discoverenergysys.com); Discover (discoverbattery.com), which stays listed as an additional source.
Where: PDF page 7, Table 3-1, AES RACKMOUNT Electrical Specifications
[3] [1] [2]
Recommended protectionAdditional external DC fusing is required to protect the battery cables
Printed as "Additional external DC fusing is required to protect the battery cables" in the Discover AES Rackmount installation and operation manual (page 14, section 6.1 Battery Module Breaker).
Where: PDF page 14, section 6.1 Battery Module Breaker
[3]
Discharge temperature-17 to 52 °C / 1 to 126 °F converted
Printed as "Discharge Operating Temperature Range (a) -17°C to 52°C (1.4°F to 125.6°F)" in Discover's AES RACKMOUNT Installation and Operation Manual (805-0043 REVD), Table 3-3, AES RACKMOUNT Environmental Specifications. Cell temperature, not ambient temperature. Re-cited on 1 October 2026 to the manufacturer's own document; previously cited to Discover Energy Systems (discoverenergysys.com), which stays listed as an additional source.
Where: PDF page 9, Table 3-3, AES RACKMOUNT Environmental Specifications
[3] [1]
Discharge cutoff voltage48 V
Printed as "Low Voltage Disconnect Recommended 48.0 V" in Discover's AES RACKMOUNT Installation and Operation Manual (805-0043 REVD), Table 3-1, AES RACKMOUNT Electrical Specifications. The recommended setting; the battery module itself disconnects at "Low Voltage Disconnect (b) 40.0 V".
Where: PDF page 7, Table 3-1, AES RACKMOUNT Electrical Specifications
[3]
Recommended charge voltage55.2 V
Printed as "Charge Bulk Voltage - Bulk Vdc 55.2 V" in Discover's AES RACKMOUNT Installation and Operation Manual (805-0043 REVD), Table 3-1, AES RACKMOUNT Electrical Specifications. The table also prints "Charge Float Voltage - U2 53.6 V". Re-cited on 1 October 2026 to the manufacturer's own document; previously cited to Discover Energy Systems (discoverenergysys.com), which stays listed as an additional source.
Where: PDF page 7, Table 3-1, AES RACKMOUNT Electrical Specifications
[3] [1]

Owner reviews

No owner reviews yet
Write a review

Sellers

No listed sellers in this data.

Price history

No seller price history.

Included with bundles 2

Each price below is for the whole bundle, not for this product on its own.

Quick reference sheet

Basic specs
5.12 kWhDischarge 70 ACharge 70 APeak current: 218 A
$ / rated kWh
Unavailable
Warranty
UnknownSee terms
Lifetime production
Not published
Size
29.16 L* (Calculated enclosure volume: W × H × D in mm ÷ 1,000,000)W: 439.2 × H: 133.5 × L: 497.3 mm / W: 17.29 × H: 5.26 × L: 19.58 in44 kg / 97 lb0.18 kWh/L* (Rated or usable capacity shown on this card ÷ enclosure volume)

Evidence score

45/100Missing details45% documented

The Evidence score uses the priorities you choose. It counts published documents, such as certificates and warranty terms, and it compares a documented figure with the best documented figure of the same kind. It does not count owner reviews, and it is not a verdict on product quality or on how many people have reviewed it. A low score can mean little is documented, or that a documented figure is below the best of its kind. Undisclosed data scores 0.

Missing details. This number counts only the evidence recorded so far. The source review for this product is not finished, or the maker has not disclosed enough, so the number can only go up.

Missing for this product: Warranty term needed; Warranty energy disclosure evidence needed; Lifetime / capacity evidence needed; Cell model disclosure evidence needed.

48 V · Server rack · Rated capacity

The warranty term and the lifetime energy are each scored against the best documented value for a home storage battery: a value earns its share of that best, times the weight. A documented value always earns points; an undisclosed one earns 0.

CertificatesCEC · IEC 62619 +4CEC listed45 / 45

100 evidence points · 45% weight

CEC listing: full credit for the certificate criterion. Exact model found in the dated CEC equipment list. This is not a safety certification or system approval. Applies: CEC; UL 9540; UL 1973.

100 / 100 × 45 = 45 points.

[4]

Lifetime / capacityResearch pending0 / 20

No qualifying figure · 20% weight

Not published. No lifetime-production bonus.

Not documented. Undisclosed data scores 0.

[1] [2]

Research pending, 0 points: Warranty term, Warranty energy disclosure, Cell model disclosure.

Computed from public specifications and evidence records. Warranty duration is not service quality; certificate evidence points are not a safety rating. Compatibility and installation limits still apply.

Certificates

What this shows: what each record says and how far it reaches. It does not mean the product is approved.
IEC 62619manufacturer claimpresent at observation[1]
Scope
unresolved document set
Covered models
48-48-5120-H
Limitations
Printed as "IEC 62619" under Certification Standards on Discover's 48-48-5120-H page. No certificate was read. The sell sheet 885-0040 Rev E prints its regulatory row as "(PENDING)". Recorded as the manufacturer's claim.
Record detail
Issued: Not stated
Valid from: Not stated
Expiry: Not stated
Not checked
Source
[1]
UL 1973manufacturer claimpresent at observation[1]
Scope
battery pack scope unverified
Covered models
48-48-5120-H
Limitations
Printed as "UL 1973" under Certification Standards on Discover's 48-48-5120-H page. No certificate or directory listing was read, and the sell sheet prints its regulatory row as "(PENDING)". Recorded as the manufacturer's claim.
Record detail
Issued: Not stated
Valid from: Not stated
Expiry: Not stated
Not checked
Source
[1]
UL9540manufacturer claimpresent at observation[1]
Scope
system configuration
Covered models
48-48-5120-H in AES Slimline Enclosure 950-0053
Limitations
Discover conditions this claim on installation in the AES Slimline Enclosure 950-0053 ("UL9540 (when installed using the AES Slimline Enclosure 950-0053)"), and its Quick Stack Rack text states that installation method is not certified to UL9540. No certificate was read. Recorded as the manufacturer's claim.
Record detail
Issued: Not stated
Valid from: Not stated
Expiry: Not stated
Not checked
Edition as printed: Not printed
Source
[1]
UL 9540amanufacturer claimpresent at observation[1]
Scope
unresolved document set
Covered models
48-48-5120-H
Limitations
Printed as "UL 9540a" on Discover's 48-48-5120-H page. UL 9540A is a test method; no report was read. Recorded as the manufacturer's claim.
Record detail
Issued: Not stated
Valid from: Not stated
Expiry: Not stated
Not checked
Edition as printed: Not printed
Source
[1]
UN 38.3manufacturer claimpresent at observation[1]
Scope
unresolved document set
Covered models
48-48-5120-H
Limitations
Printed under Shipping Classification on Discover's 48-48-5120-H page. No test summary was read. Recorded as the manufacturer's claim.
Record detail
Issued: Not stated
Valid from: Not stated
Expiry: Not stated
Not checked
Source
[1]
UL 1973authority listing reportedlisted as of snapshot[4]
Scope
equipment listing
Covered models
48-48-5120-H
Limitations
Listed on the California Energy Commission Battery List (data unchanged since October 1, 2026; downloaded October 11, 2026) as Discover Energy Systems Corp. "48-48-5120-H": UL 1973, certifying entity TUV Rheinland, certificate date 2023-11-02, Ed. 2 : 2018, CEC listing date 2023-12-21. A state equipment list entry, not the certification body's own record.
Record detail
Issued: Not stated
Valid from: Nov 2, 2023
Expiry: Not stated
Issuer checked: Oct 11, 2026
Source
[4]
CECauthority listing reportedlisted as of snapshot[4]
Scope
equipment listing
Covered models
48-48-5120-H
Limitations
Model 48-48-5120-H listed on the California Energy Commission Battery List (data unchanged since October 1, 2026; downloaded October 11, 2026) under Discover Energy Systems Corp., as "48-48-5120-H", CEC listing date 2023-12-21. This is an equipment listing, not UL certification or complete-system approval.
Record detail
Issued: Not stated
Valid from: Dec 21, 2023
Expiry: Not stated
Issuer checked: Oct 11, 2026
Source
[4]

Warranty

Unknown: no warranty facts recorded.

Recalls / legal notices

No recalls on file. All notices · Report a notice

This register is incomplete. A missing notice does not establish that a product has no recalls.

Documents

  • Manuals

  • Discover AES Rackmount installation and operation manualOfficial · Discover Energy Systems · Official instruction manual · PDF
    Source details
    Revision
    805-0043 Rev D
    Revision date
    Not stated

    Exact-model document linked from the manufacturer. Revision date is taken from the document when stated.

    Location: Cover / revision history

    Retrieved Sep 8, 2026

    SHA-256: 569299a9be91bb754e8add81b28458b44f53c833015436f95d3c8c09791c030f

    Archived copies

    Archived copy of a document published by Discover Energy Systems. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email [email protected].

    Archived backup805-0043 Rev D · 1.37 MB

    Archived copy, unaltered, kept as a record of what Discover Energy Systems published. Original address: https://discoverbattery.com/s4x_files/resources/des-aes-rackmount-user-manual.pdf. Copyright and takedown

    Source first found
    This copy captured
    Archived
    File detailsOriginal source
    Embedded creation date
    Embedded modification date
    Pages
    36

    Embedded dates are file metadata, not independent proof of publication.

    SHA-256: 569299a9be91bb754e8add81b28458b44f53c833015436f95d3c8c09791c030f

    Open
  • Other documents

  • Discover AES RACKMOUNT sell sheetOfficial · Discover · Official document · PDF
    Source details
    Revision
    885-0040 Rev E
    Revision date
    Not stated

    Revision date not established.

    Location: Original source record

    Retrieved Sep 7, 2026

    Archived copies

    Archived copy of a document published by Discover. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email [email protected].

    Archived backupRevision not recorded · 1.70 MB

    Archived copy, unaltered, kept as a record of what Discover published. Original address: https://discoverbattery.com/s4x_files/resources/des-aes-rackmount-sell-sheet.pdf. Copyright and takedown

    Source first found
    This copy captured
    Archived
    File detailsOriginal source
    Embedded creation date
    Embedded modification date
    Pages
    2

    Embedded dates are file metadata, not independent proof of publication.

    SHA-256: 4a050bfaf4584bd6ef8ce095f682e907a01043d7d74adea590a97f8729f94b64

    Open

Archive and older revisions

Archive and older revisions1

Earlier revisions, archived captures and copies published by someone other than the manufacturer. Every one stays reachable.

  • Discover Energy Systems AES RACKMOUNT 48-48-5120-H product page (September 24, 2026 capture)Official · Discover Energy Systems · Official product page · Web page
    Source details
    Revision
    Not stated
    Revision date
    Not stated

    Captured by scripts/prepare-brand-sweep-sep21.mjs on 2026-09-24.

    Location: Heading; Mechanical and Electrical Specifications tables; Certification Standards

    Retrieved Sep 23, 2026

    Discover Energy Systems' own product page for the heated AES RACKMOUNT module, captured on September 24, 2026. It prints the model with Discover's product model number 900-0067, mechanical and electrical specification tables at 25 °C and a certification list. The page carries no revision; its print footer shows the capture date.

    Open

Archived documents

Discover AES RACKMOUNT sell sheet

Archived copy of a document published by Discover. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email [email protected].

Archived backupRevision not recorded · 1.70 MB

Archived copy, unaltered, kept as a record of what Discover published. Original address: https://discoverbattery.com/s4x_files/resources/des-aes-rackmount-sell-sheet.pdf. Copyright and takedown

Source first found
This copy captured
Archived
File detailsOriginal source
Embedded creation date
Embedded modification date
Pages
2

Embedded dates are file metadata, not independent proof of publication.

SHA-256: 4a050bfaf4584bd6ef8ce095f682e907a01043d7d74adea590a97f8729f94b64

Discover AES Rackmount installation and operation manual

Archived copy of a document published by Discover Energy Systems. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email [email protected].

Archived backup805-0043 Rev D · 1.37 MB

Archived copy, unaltered, kept as a record of what Discover Energy Systems published. Original address: https://discoverbattery.com/s4x_files/resources/des-aes-rackmount-user-manual.pdf. Copyright and takedown

Source first found
This copy captured
Archived
File detailsOriginal source
Embedded creation date
Embedded modification date
Pages
36

Embedded dates are file metadata, not independent proof of publication.

SHA-256: 569299a9be91bb754e8add81b28458b44f53c833015436f95d3c8c09791c030f

Submit a document

Parts and accessories

No sourced accessories or replacement parts listed yet.

Model history

Model identity

Model
48-48-5120-H
Published model / SKU
900-0067

Discover's product model number, printed on the product page heading "AES RACKMOUNT 48-48-5120-H (Product Model 900-0067)".

[1]

Manufacturer SKU 48-48-5120-H · US market

  1. Observed Oct 11, 2026

    UL 1973: claimed

    Product / system scope unresolved. Listed on the California Energy Commission Battery List (data unchanged since October 1, 2026; downloaded October 11, 2026) as Discover Energy Systems Corp. "48-48-5120-H": UL 1973, certifying entity TUV Rheinland, certificate date 2023-11-02, Ed. 2 : 2018, CEC listing date 2023-12-21. A state equipment list entry, not the certification body's own record.

    [4]

  2. Observed Oct 11, 2026

    CEC: claimed

    Product / system scope unresolved. Model 48-48-5120-H listed on the California Energy Commission Battery List (data unchanged since October 1, 2026; downloaded October 11, 2026) under Discover Energy Systems Corp., as "48-48-5120-H", CEC listing date 2023-12-21. This is an equipment listing, not UL certification or complete-system approval.

    [4]

Other recorded fields

FieldValueConditionsSource
Evidence breakdown
method version: 0.21-personal
documented pct: 45
basis: nominal
missing:
Warranty term needed
Warranty energy disclosure evidence needed
Lifetime / capacity evidence needed
Cell model disclosure evidence needed
criteria:
key: certificateEvidence
label: Certificates
value: 100
unit: evidence points
shown: CEC · IEC 62619 +4
shown detail: CEC listed
state: verified
points: 45
ceiling: 45
weight: 45
share: 100
covered: yes
missing: no
folded: no
reason: Unknown
reason text: Unknown
note: CEC listing: full credit for the certificate criterion. Exact model found in the dated CEC equipment list. This is not a safety certification or system approval. Applies: CEC; UL 9540; UL 1973.
display note: Unknown
Sources: [4] [4]
key: years
label: Warranty term
value: Unknown
unit: years
shown: Research pending
shown detail: Unknown
state: pending
points: 0
ceiling: 20
weight: 20
share: Unknown
covered: no
missing: yes
folded: yes
reason: undocumented
reason text: Not documented. Undisclosed data scores 0.
note: Not documented.
display note: Unknown
Sources: No source on record
key: throughputEvidence
label: Warranty energy disclosure
value: 0
unit: evidence points
shown: Research pending
shown detail: Unknown
state: pending
points: 0
ceiling: 10
weight: 10
share: 0
covered: no
missing: yes
folded: yes
reason: Unknown
reason text: Unknown
note: No qualifying quantified warranty energy recorded. This is an evidence gap, not a performance judgment.
display note: Unknown
Sources: No source on record
key: lifetime
label: Lifetime / capacity
value: Unknown
unit: MWh/kWh
shown: Research pending
shown detail: Unknown
state: pending
points: 0
ceiling: 20
weight: 20
share: Unknown
covered: no
missing: yes
folded: no
reason: undocumented
reason text: Not documented. Undisclosed data scores 0.
note: Not published. No lifetime-production bonus.
display note: Unknown
Sources: [1] [2]
key: cellDisclosure
label: Cell model disclosure
value: 0
unit: disclosure points
shown: Research pending
shown detail: Unknown
state: pending
points: 0
ceiling: 5
weight: 5
share: 0
covered: no
missing: yes
folded: yes
reason: Unknown
reason text: Unknown
note: A sourced cell manufacturer and model are needed. Grade A, chemistry and cell capacity alone do not identify a cell model.
display note: Unknown
Sources: No source on record

Community discussions

No discussions linked yet. Search DIY Solar Forum

Sources

  1. Discover Energy Systems AES RACKMOUNT 48-48-5120-H product page (September 24, 2026 capture) (Discover Energy Systems · manufacturer · observed Sep 23, 2026)
  2. Discover AES RACKMOUNT sell sheet (Discover · manufacturer · 885-0040 Rev E · observed Sep 7, 2026)
  3. Discover AES Rackmount installation and operation manual (Discover Energy Systems · manufacturer · 805-0043 Rev D · observed Sep 8, 2026)
  4. CEC Battery List, official spreadsheet (data unchanged since October 1, 2026; downloaded October 11, 2026) (California Energy Commission · government equipment registry · Data unchanged since October 1, 2026 · observed Oct 10, 2026 · effective Oct 1, 2026)

Sign in to report an error on this page

Similar products

All with a price

* Missing details