Manufacturer claim; issuer verification pending. Applies to the exact inverter.
Photo sources
Manufacturer and seller images. Configuration examples may include additional equipment.
Image source: SunGoldPower SG11.4KHB-HV; official product image.Hybrid inverter
SunGoldPower SG11.4KHB-HV
Key specs
2 specs not documented yet: ac input breaker (manual), ac output breaker (manual)Help fill in ›
All specifications
Identity
SKU detail
No spec by that name.
| Field | Value | Conditions | Source |
|---|---|---|---|
| Phase | 240V Split-Phase | Printed as "240V Split-Phase". The manual's text layer lists the row labels and values in separate runs; the pairing was confirmed from the text positions on the page, where the value sits on the same line as the label. Where: SG11.4KHB-HV User Manual 20241115, section 8 Specifications, Technical Data table (printed pages 62 to 64), AC Output (Backup and Off-grid) Phase Power row | [2] |
| Cooling | Natural convection | Printed as "Natural convection". Where: SG11.4KHB-HV User Manual 20241115, section 8 Specifications, Technical Data table (printed pages 62 to 64), General data Cooling method row | [2] |
| Grounding | Ground bar in the wire box bonded to the chassis, from the main service panel ground bar; optional external ground point on the right side | Printed as "From the main service panel ground bar to the ground bar inside the inverter wire box", "An optional external ground connection point is available on the right side of inverter." and "The internal ground bar is grounded to the inverter chassis." Parallel units: "all inverters should be connected to the same ground point". SG11.4KHB-HV User Manual (Version 1.0, Release Date: 06/2024). Where: PDF page 29, Table 5.1 System Cable Connections, and PDF page 31, 5.6 External Grounding, SG11.4KHB-HV | [2] |
| Weight | 32.54 kg / 71.74 lb converted | Printed as "71.74 Ibs (32.54 kg)" ("Ibs" as printed); the kilogram figure is used as printed. Where: SG11.4KHB-HV User Manual 20241115, section 8 Specifications, Technical Data table (printed pages 62 to 64), General data Weight row | [2] |
| MPPT count | 4 | Printed as "4/1" (4 MPPTs, 1 string per MPPT). The product page says "Equipped with 4 MPPTs". The manual's text layer lists the row labels and values in separate runs; the pairing was confirmed from the text positions on the page, where the value sits on the same line as the label. Where: SG11.4KHB-HV User Manual 20241115, section 8 Specifications, Technical Data table (printed pages 62 to 64), Input DC (PV side) Number of MPPTs/Number of strings per MPPT row | [2] |
| Peak output | 18.2 kVA, 10 sec | Printed as "18.2 kVA, 10 sec" for the backup and off-grid output. The same table prints "Max. output current for 300 milliseconds 85.5A". Single-model table in the SG11.4KHB-HV User Manual (Version 1.0, Release Date: 06/2024); row pairing confirmed on the rendered page. Where: PDF page 66, 8. Specifications, AC Output (Backup and Off-grid), Max. apparent output power row, SG11.4KHB-HV column | [2] |
| Voltage thd | <3% | Printed as "<3%" for THDv at linear load. The manual's text layer lists the row labels and values in separate runs; the pairing was confirmed from the text positions on the page, where the value sits on the same line as the label. Where: SG11.4KHB-HV User Manual 20241115, section 8 Specifications, Technical Data table (printed pages 62 to 64), AC Output (Backup and Off-grid) THDv(@linear load) row | [2] |
| AC voltage | 240 V | Printed as "240 V"; the Phase Power row prints "240V Split-Phase". The product page says "Provides 120V/240V AC output". The manual's text layer lists the row labels and values in separate runs; the pairing was confirmed from the text positions on the page, where the value sits on the same line as the label. Where: SG11.4KHB-HV User Manual 20241115, section 8 Specifications, Technical Data table (printed pages 62 to 64), AC Output (Backup and Off-grid) Rated AC output voltage row | [2] |
| Max charge | 50 A | Printed as "50A" for Maximum charge/discharge current, one figure for both directions. Where: SG11.4KHB-HV User Manual 20241115, section 8 Specifications, Technical Data table (printed pages 62 to 64), Energy Storage Maximum charge/discharge current row | [2] |
| Clearances | 12 in. (305 mm) between inverter and other equipment; 20 in. (508 mm) from the bottom of the inverter to the ground | Printed as "A minimum clearance of 12 inches (305mm)should be kept between inverter & other equipment." and "20 inches (508mm) of clearance between the bottom of the inverter and the ground." SG11.4KHB-HV User Manual (Version 1.0, Release Date: 06/2024). Where: PDF page 26, 5.3 Mounting the Inverter, Figure 5.5 Inverter Mounting Clearances, SG11.4KHB-HV | [2] |
| Dimensions | W 560 × H 750 × D 220 mm / W 22 × H 29.5 × D 8.66 in converted | Printed as "29.53*22.05*8.66 in (750*560*220mm)" under the label Dimensions(H/W/D); the millimeter figures are used as printed, height first. The manual's text layer lists the row labels and values in separate runs; the pairing was confirmed from the text positions on the page, where the value sits on the same line as the label. Where: SG11.4KHB-HV User Manual 20241115, section 8 Specifications, Technical Data table (printed pages 62 to 64), General data Dimensions(H/W/D) row | [2] |
| PV disconnect | Integrated DC disconnect switch | Printed as "feature an integrated DC disconnect switch" and "This is the DC disconnect switch for the inverter". SG11.4KHB-HV User Manual (Version 1.0, Release Date: 06/2024). Where: PDF page 10, 2.2 General Safety Instructions, and PDF page 13, 3.2 Inverter Wire Box, SG11.4KHB-HV | [2] |
| Communications | RS485; Optional: Cellular, Wi-Fi, LAN; CAN/RS485 | Communication row printed as "RS485, Optional: Cellular, Wi-Fi, LAN"; the Battery Communication row prints "CAN/RS485" (battery link). Interface row prints "LED indicator lights, Bluetooth/Phone app". Where: SG11.4KHB-HV User Manual 20241115, section 8 Specifications, Technical Data table (printed pages 62 to 64), Features Communication row and Energy Storage Battery Communication row | [2] |
| Efficiency | 97.6 % | PV Max. efficiency, printed as "97.6%". PV CEC efficiency is printed as "97.0%" (listed as unmapped). The manual's text layer lists the row labels and values in separate runs; the pairing was confirmed from the text positions on the page, where the value sits on the same line as the label. Where: SG11.4KHB-HV User Manual 20241115, section 8 Specifications, Technical Data table (printed pages 62 to 64), Efficiency PV Max. efficiency row | [2] |
| MPPT voltage | 80 to 550 V | Printed as "80-550V". A separate Full load MPPT voltage range row prints "245-450V". The manual's text layer lists the row labels and values in separate runs; the pairing was confirmed from the text positions on the page, where the value sits on the same line as the label. Where: SG11.4KHB-HV User Manual 20241115, section 8 Specifications, Technical Data table (printed pages 62 to 64), Input DC (PV side) MPPT voltage range row | [2] |
| Solar array | 18.24 kWConverted: 18,240 W / 1000 = 18.24 kW | Manual and product page print different PV array figures. The SG11.4KHB-HV user manual prints Recommended max. PV power as 18,240 W; the SunGoldPower product page prints 18kW PV input. Printed as "18,240W" in the Recommended max. PV power row; converted to kW. SG11.4KHB-HV User Manual (Version 1.0, Release Date: 06/2024). Revised on 1 October 2026: The model's own user manual prints the recommended maximum PV power as 18,240 W; the recorded 18 kW comes from the product page.Where: PDF page 65, 8. Specifications, Input DC (PV side), Recommended max. PV power row, SG11.4KHB-HV column SourcesConverted: 18,240 W / 1000 = 18.24 kW 18 kW Printed on the product page as "18kW PV input" and "a maximum PV input of 18KW". The manual instead prints "Recommended max. PV power" as "18,240W". [3] | [2] |
| AC frequency | 60 Hz | Printed as "60 Hz" for the backup and grid outputs. The manual's text layer lists the row labels and values in separate runs; the pairing was confirmed from the text positions on the page, where the value sits on the same line as the label. Where: SG11.4KHB-HV User Manual 20241115, section 8 Specifications, Technical Data table (printed pages 62 to 64), AC Output (Backup and Off-grid) Rated frequency row | [2] |
| Grid connection | On-grid and off-grid | Printed as "This inverter can operate in both on-grid and off-grid applications." The specification table prints Backup support configurations as "Dedicated loads and whole-home". SG11.4KHB-HV User Manual (Version 1.0, Release Date: 06/2024). Where: PDF page 4, 1.1 Inverter Description, SG11.4KHB-HV | [2] |
| Max discharge | 50 A | Printed as "Maximum charge/discharge current 50A", one figure for both directions. SG11.4KHB-HV User Manual (Version 1.0, Release Date: 06/2024). Where: PDF page 65, 8. Specifications, Energy Storage, Maximum charge/discharge current row, SG11.4KHB-HV column | [2] |
| AC input breaker | Unknown | The manual prints no AC input breaker rating, only the current ratings to size the overcurrent device from: Grid Max Input Current 71.3A. Printed as "SG11.4KHB-HV 47.5A 71.3A 47.5A 76A" under the columns Grid Max Output Current, Grid Max Input Current, Backup Rated Output Current and Backup Max Output Current (10 sec), with "we recommend installing a device for protection against over-current and leakage, based on the following current ratings". The manual prints no breaker rating; sizing is per NEC and local code. SG11.4KHB-HV User Manual (Version 1.0, Release Date: 06/2024). Where: PDF page 36, 5.10.1 AC Terminals, Table 5.4 Current ratings for sizing the OCPD, Grid Max Input Current column, SG11.4KHB-HV row | [2] |
| Enclosure rating | TYPE 4X (IP66) | Printed as "TYPE 4X (IP66)". The manual's text layer lists the row labels and values in separate runs; the pairing was confirmed from the text positions on the page, where the value sits on the same line as the label. Where: SG11.4KHB-HV User Manual 20241115, section 8 Specifications, Technical Data table (printed pages 62 to 64), General data Ingress protection row | [2] |
| Max PV current | 16A | Printed as "16A" per string; the table prints 1 string per MPPT. Max. short circuit current per string is "25.6A". The manual's text layer lists the row labels and values in separate runs; the pairing was confirmed from the text positions on the page, where the value sits on the same line as the label. Where: SG11.4KHB-HV User Manual 20241115, section 8 Specifications, Technical Data table (printed pages 62 to 64), Input DC (PV side) Max. input current per string row | [2] |
| Max PV voltage | 600 V | Printed as "600V". The product page says "supports up to 600V PV Input". The manual's text layer lists the row labels and values in separate runs; the pairing was confirmed from the text positions on the page, where the value sits on the same line as the label. Where: SG11.4KHB-HV User Manual 20241115, section 8 Specifications, Technical Data table (printed pages 62 to 64), Input DC (PV side) Max. input voltage row | [2] |
| Transfer time | <10 ms ms | Printed as "<10 ms" for Back-up switch time. The manual's text layer lists the row labels and values in separate runs; the pairing was confirmed from the text positions on the page, where the value sits on the same line as the label. Where: SG11.4KHB-HV User Manual 20241115, section 8 Specifications, Technical Data table (printed pages 62 to 64), AC Output (Backup and Off-grid) Back-up switch time row | [2] |
| AC output breaker | Unknown | The manual prints no AC output breaker rating, only the current ratings to size the overcurrent device from: Backup Rated Output Current 47.5A and Backup Max Output Current (10 sec) 76A. Printed as "SG11.4KHB-HV 47.5A 71.3A 47.5A 76A" (Grid Max Output, Grid Max Input, Backup Rated Output, Backup Max Output (10 sec)). The manual prints no breaker rating; sizing is per NEC and local code. SG11.4KHB-HV User Manual (Version 1.0, Release Date: 06/2024). Where: PDF page 36, 5.10.1 AC Terminals, Table 5.4 Current ratings for sizing the OCPD, Backup columns, SG11.4KHB-HV row | [2] |
| Battery wire size | 6 AWG max. (largest accepted by terminal) | Printed as "Battery Cable Max. Wire Size Accepted by Terminal Model SG11.4KHB-HV 6 AWG". This is the terminal limit, not a recommended size. SG11.4KHB-HV User Manual (Version 1.0, Release Date: 06/2024). Where: PDF page 35, 5.9 Battery Installation, Table 5.2 Battery cable size limitations, Battery Cable Max. Wire Size Accepted by Terminal row, SG11.4KHB-HV column | [2] |
| Extended warranty | Extendable to 20 years | Printed as "10 years standard (Extendable to 20 years)"; the extension terms are not stated in the manual. SG11.4KHB-HV User Manual (Version 1.0, Release Date: 06/2024). Where: PDF page 67, 8. Specifications, Features, Warranty row, SG11.4KHB-HV column | [2] |
| Generator support | Yes, on the grid side (dry contact or ATS start signal) | Printed as "The generator must be connected to the grid-side of the inverter." and "Connect the generator dry contact to pins Dry_con_A and Dry_con_B of the inverter." An ATS uses "a 12-24V start wire". Page 36 also prints "Generator support will be available in Summer 2023." SG11.4KHB-HV User Manual (Version 1.0, Release Date: 06/2024). Where: PDF page 40, 5.10.6 Generator Integration, SG11.4KHB-HV | [2] |
| AC input voltage | 211-264V | Printed as "211-264V". The manual's text layer lists the row labels and values in separate runs; the pairing was confirmed from the text positions on the page, where the value sits on the same line as the label. Where: SG11.4KHB-HV User Manual 20241115, section 8 Specifications, Technical Data table (printed pages 62 to 64), AC Input (Grid) Input voltage range row | [2] |
| AC input wire size | 4 AWG max. (largest accepted by terminal) | Printed as "4 AWG" in the AC Grid Cable Max. Wire Size Accepted by Terminal row (table header text "Table 5.3 AC cable size limitations"; row pairing read from rendered page 36). This is the terminal limit, not a recommended size. SG11.4KHB-HV User Manual (Version 1.0, Release Date: 06/2024). Where: PDF page 36, 5.10.1 AC Terminals, Table 5.3 AC cable size limitations, AC Grid Cable Max. Wire Size Accepted by Terminal row, SG11.4KHB-HV column | [2] |
| Battery protection | Replaceable battery fuse in the wire box, 750V, 63A | Printed as "The battery fuse in the inverter wire box is replaceable." and "Fuse specification: 750V, 63A." Replacement only by a technician authorized by Sun Gold Power. SG11.4KHB-HV User Manual (Version 1.0, Release Date: 06/2024). Where: PDF page 35, 5.9 Battery Installation, note, SG11.4KHB-HV | [2] |
| Grid passthrough | 11.4kW maximum | Printed as "The 11.4kW models can pass through 11.4kW maximum." with the AC bypass switch in the Bypass position. The manual states this as power, not current; no ampere figure is printed for pass-through. SG11.4KHB-HV User Manual (Version 1.0, Release Date: 06/2024). Where: PDF page 38, 5.10.4 AC Bypass Switch, Pass-Through Power paragraph, SG11.4KHB-HV | [2] |
| Max parallel units | 3 | Printed as "Up to three hybrid inverters can be installed together in parallel on the backup side of the system." and again on page 45 as "Up to three hybrid inverters can be installed together in parallel." SG11.4KHB-HV User Manual (Version 1.0, Release Date: 06/2024). Re-cited on 1 October 2026 to the manufacturer's own document; previously cited to SunGoldPower (sungoldpower.com), which stays listed as an additional source. Where: PDF page 39, 5.10.5 Paralleling Multiple Hybrid Inverters, SG11.4KHB-HV | [2] [3] |
| PV start voltage | 80 V | Printed as "80V". The manual's text layer lists the row labels and values in separate runs; the pairing was confirmed from the text positions on the page, where the value sits on the same line as the label. Where: SG11.4KHB-HV User Manual 20241115, section 8 Specifications, Technical Data table (printed pages 62 to 64), Input DC (PV side) Start-up voltage row | [2] |
| AC output wire size | 6 AWG | Printed as "6 AWG" in the AC Backup Cable Cross Sectional Area row (table title "Table 5.3 AC cable size limitations"; row pairing read from rendered page 36). SG11.4KHB-HV User Manual (Version 1.0, Release Date: 06/2024). Where: PDF page 36, 5.10.1 AC Terminals, Table 5.3 AC cable size limitations, AC Backup Cable Cross Sectional Area row, SG11.4KHB-HV column | [2] |
| Communication ports | Meter_A/Meter_B (RS485 to energy meter); BMS_CAN_H/BMS_CAN_L; BMS485_A/BMS485_B; ENABLE/Enable_GND; EPO_IN/EPO_OUT; Dry con_A/Dry con_B (generator); ATS24V/GEN GND; RSD_IN/RSD_OUT; Parallel_IN/Parallel_OUT (RJ45); RS485-IN/RS485-OUT (RJ45); Logger USB port; Bluetooth antenna | Port names as printed in Table 5.5 ("The inverter communication terminal block consists of 16 ports."), acceptable wire size printed as "22-16 AWG", plus the Logger USB port and Bluetooth antenna from the wire box overview. SG11.4KHB-HV User Manual (Version 1.0, Release Date: 06/2024). Where: PDF page 42, 5.11.1 Communication Terminals Overview, Table 5.5 Inverter communication terminals explained, SG11.4KHB-HV | [2] |
| Operating noise | 30 dBA <30 dB as printed | Printed as "<30 dB (A)", typical noise emission; the value is an upper bound (less than 30). Where: SG11.4KHB-HV User Manual 20241115, section 8 Specifications, Technical Data table (printed pages 62 to 64), General data Noise emission (Typical) row | [2] |
| PV strings per MPPT | 1 | Printed as "4/1" (4 MPPTs, 1 string per MPPT); the PV section adds "Note: Each PV string input is a separate MPPT". Row pairing confirmed on the rendered page. SG11.4KHB-HV User Manual (Version 1.0, Release Date: 06/2024). Where: PDF page 65, 8. Specifications, Input DC (PV side), Number of MPPTs/Number of strings per MPPT row, SG11.4KHB-HV column | [2] |
| Continuous output | 11.4 kW | Printed as "11.4kW" for both the grid output and the backup/off-grid output. The product page also says "11.4KW continuous". The manual's text layer lists the row labels and values in separate runs; the pairing was confirmed from the text positions on the page, where the value sits on the same line as the label. Where: SG11.4KHB-HV User Manual 20241115, section 8 Specifications, Technical Data table (printed pages 62 to 64), AC Output (Grid) Rated output power row and AC Output (Backup and Off-grid) Rated output power row | [2] |
| Mounting orientation | Vertical, 90° tilt | Printed as "The inverter must be mounted vertically at a 90° angle." Page 26 adds "A tilt greater or less than 90° may cause the inverter output power to derate." SG11.4KHB-HV User Manual (Version 1.0, Release Date: 06/2024). Where: PDF page 28, 5.3 Mounting the Inverter, note, SG11.4KHB-HV | [2] |
| Single leg output | 0-0.5 times the rated output power for each phase | Printed as "of 0-0.5 times the rated output power for each phase" and "If a single phase load exceeds 50% of the rated power, an overload alarm will be triggered". No per-leg kW figure is printed, so none is computed. SG11.4KHB-HV User Manual (Version 1.0, Release Date: 06/2024). Where: PDF page 16, 4.2.2 Backup Power, unbalanced loads paragraph, SG11.4KHB-HV | [2] |
| Battery compatibility | Lithium-ion (see Battery Compatibility Sheet) | Printed as "Battery type Lithium-ion"; the Number of batteries per inverter row prints "See Battery Compatibility Sheet", and the battery section says "This inverter only works with specific battery models." SG11.4KHB-HV User Manual (Version 1.0, Release Date: 06/2024). Where: PDF page 65, 8. Specifications, Energy Storage, Battery type and Number of batteries per inverter rows, SG11.4KHB-HV column | [2] |
| Battery efficiency | 97 % | Maximum efficiency for battery charged/discharged to AC, printed as "97.0%" (the fourth figure in the Efficiency block). BAT charged by PV Max. efficiency is printed as "98.5%" (listed as unmapped). The manual's text layer lists the row labels and values in separate runs; the pairing was confirmed from the text positions on the page, where the value sits on the same line as the label. Where: SG11.4KHB-HV User Manual 20241115, section 8 Specifications, Technical Data table (printed pages 62 to 64), Efficiency BAT charged/discharged to AC Max. efficiency row | [2] |
| Ground terminal torque | 2 N·m | Printed as "tighten it with a torque wrench screwdriver to 2N.m." for the external grounding terminal screw on the heat sink. SG11.4KHB-HV User Manual (Version 1.0, Release Date: 06/2024). Where: PDF page 31, 5.6 External Grounding, step 4, SG11.4KHB-HV | [2] |
| Max PV short circuit | 25.6 A | Printed as "Max. short circuit current per string 25.6A"; each string is a separate MPPT. SG11.4KHB-HV User Manual (Version 1.0, Release Date: 06/2024). Where: PDF page 65, 8. Specifications, Input DC (PV side), Max. short circuit current per string row, SG11.4KHB-HV column | [2] |
| Battery voltage range | 120 to 500 V | Printed as "120 - 500V". The product page prints "battery voltage range of 120V-500V". The manual's text layer lists the row labels and values in separate runs; the pairing was confirmed from the text positions on the page, where the value sits on the same line as the label. Where: SG11.4KHB-HV User Manual 20241115, section 8 Specifications, Technical Data table (printed pages 62 to 64), Energy Storage Battery voltage range row | [2] |
| Operating temperature | -25 to 60 °C / -13 to 140 °F converted | Printed as "-25~+60 ℃/-13~+140 ℉". The manual's text layer lists the row labels and values in separate runs; the pairing was confirmed from the text positions on the page, where the value sits on the same line as the label. Where: SG11.4KHB-HV User Manual 20241115, section 8 Specifications, Technical Data table (printed pages 62 to 64), General data Operation temperature range row | [2] |
| Other compliance claims | UL1741 SB, UL1741 SA, IEEE1547.1-2020, UL1699B, UL1998, FCC Part15 Class B, California Rule 21, HECO Rule 14H (pending), NEC 690.12-2020,CAN/CSA C22.2107.1-1 | Exact Compliance line; the product page prints the identical line. Where: SG11.4KHB-HV User Manual 20241115, section 8 Specifications, Technical Data table (printed pages 62 to 64), Features Compliance row | [2] |
| Weighted efficiency | 97 % | Printed as "97.0%" in the PV CEC efficiency row (the four efficiency values print in row order "97.6% 97.0% 98.5% 97.0%"; pairing confirmed on the rendered page). SG11.4KHB-HV User Manual (Version 1.0, Release Date: 06/2024). Where: PDF page 66, 8. Specifications, Efficiency, PV CEC efficiency row, SG11.4KHB-HV column | [2] |
Owner reviews
Write a reviewSellers
Lowest first. Each price is the date we last read it; it may have changed. Stock isn't shown.
| Store | Price | Read | Details | Source | |
|---|---|---|---|---|---|
| SunGoldPower | $1,550 | Oct 31, 2026 | Price SunGoldPower's product data prints for this exact variant (only option "Default Title", SKU SG11.4KHB-HV) on October 31, 2026: "price":"1550.00", $1,550.00. The data also prints a compare-at price, not recorded as a price. One unit as listed; shipping and tax are not included. · Store SKU SG11.4KHB-HVPrice readings (1)
| [4] | View now Paid link |
Price history
Prices we read at SunGoldPower · 1 reading from to
Chart, listings & data
Since · Listing price (USD)
A break in a line is a gap in our readings: no price is drawn for days we did not read.
Price data
| Checked | Seller | Price |
|---|---|---|
| Oct 31, 2026, 2:37 PM PDT | SunGoldPower Paid link | $1,550 |
Quick reference sheet
- Continuous output
- 11.4 kW
- Battery voltage
- 120 to 500 V
- Solar input
- 18.24 kWMPPT trackers 4MPPT range 80 to 550 V
- AC output
- 240 V
- Warranty
- 10 years
- Size
- 92.4 L* (Calculated from published dimensions)W: 560 × H: 750 × D: 220 mm / W: 22 × H: 29.5 × D: 8.66 inWeight 32.54 kg / 71.74 lb
Evidence score
The Evidence score uses the priorities you choose. It counts published documents, such as certificates and warranty terms, and it compares a documented figure with the best documented figure of the same kind. It does not count owner reviews, and it is not a verdict on product quality or on how many people have reviewed it. A low score can mean little is documented, or that a documented figure is below the best of its kind. Undisclosed data scores 0.
Missing details. This number counts only the evidence recorded so far. The source review for this product is not finished, or the maker has not disclosed enough, so the number can only go up.
Missing for this product: Idle consumption needed.
Each input is scored against the best documented value for an inverter: warranty term and battery conversion efficiency against every published inverter, idle consumption (lower is better) against the inverters in the same output band, or against every published inverter when the output is not documented. A documented value always earns points; an undisclosed one earns 0 and is listed as missing. Researched products receive a score. Certificates earn points for the evidence itself. Size and weight do not affect scores.
10 of 25 years, the best documented for an inverter (printed by the maker): APsystems DS3
Printed as "10 years standard (Extendable to 20 years)"; the extension terms are not stated in the table.
97 of 98.2 %, the best documented for an inverter (printed by the maker): GoodWe GW100K-ET-G10
Maximum efficiency for battery charged/discharged to AC, printed as "97.0%" (the fourth figure in the Efficiency block). BAT charged by PV Max. efficiency is printed as "98.5%" (listed as unmapped). The manual's text layer lists the row labels and values in separate runs; the pairing was confirmed from the text positions on the page, where the value sits on the same line as the label.
Research pending, 0 points: Idle consumption.
Warranty term and battery conversion efficiency are compared with every published inverter; idle consumption with the inverters in the same 7 to 15 kW output band. · Method version 0.5
How it worksCertificates
California Rule 21manufacturer claimpresent at observation[2] [3]
- Scope
- equipment listing
- Covered models
- SG11.4KHB-HV
- Limitations
- SunGoldPower's own statement, recorded exactly as printed: "UL1741 SB, UL1741 SA, IEEE1547.1-2020, UL1699B, UL1998, FCC Part15 Class B, California Rule 21, HECO Rule 14H (pending), NEC 690.12-2020,CAN/CSA C22.2107.1-1" (Sun_Gold_Power_manual_SG11.4KHB-HV_-_20241115_2.pdf); "Compliance: UL1741 SB, UL1741 SA, IEEE1547.1-2020, UL1699B, UL1998, FCC Part15 Class B, California Rule 21, HECO Rule 14H (pending), NEC 690.12-2020,CAN/CSA C22.2107.1-1" (products-high-voltage-11-4kw-hybrid-split-phase-inverter-with-aps-transmitter-sg11-4khb-hv.html). A manufacturer statement names no certificate number or issuer and is not evidence of a listing; certificate documents SunGoldPower serves are recorded separately.
- Record detail
- Issued: Not statedValid from: Not statedExpiry: Not statedNot checked
- Source
- [2] [3]
CAN/CSA C22.2107.1-1manufacturer claimpresent at observation[2] [3]
- Scope
- equipment listing
- Covered models
- SG11.4KHB-HV
- Limitations
- SunGoldPower's own statement, recorded exactly as printed: "UL1741 SB, UL1741 SA, IEEE1547.1-2020, UL1699B, UL1998, FCC Part15 Class B, California Rule 21, HECO Rule 14H (pending), NEC 690.12-2020,CAN/CSA C22.2107.1-1" (Sun_Gold_Power_manual_SG11.4KHB-HV_-_20241115_2.pdf); "Compliance: UL1741 SB, UL1741 SA, IEEE1547.1-2020, UL1699B, UL1998, FCC Part15 Class B, California Rule 21, HECO Rule 14H (pending), NEC 690.12-2020,CAN/CSA C22.2107.1-1" (products-high-voltage-11-4kw-hybrid-split-phase-inverter-with-aps-transmitter-sg11-4khb-hv.html). A manufacturer statement names no certificate number or issuer and is not evidence of a listing; certificate documents SunGoldPower serves are recorded separately.
- Record detail
- Issued: Not statedValid from: Not statedExpiry: Not statedNot checked
- Source
- [2] [3]
FCC Part15 Class Bmanufacturer claimpresent at observation[2] [3]
- Scope
- equipment listing
- Covered models
- SG11.4KHB-HV
- Limitations
- SunGoldPower's own statement, recorded exactly as printed: "UL1741 SB, UL1741 SA, IEEE1547.1-2020, UL1699B, UL1998, FCC Part15 Class B, California Rule 21, HECO Rule 14H (pending), NEC 690.12-2020,CAN/CSA C22.2107.1-1" (Sun_Gold_Power_manual_SG11.4KHB-HV_-_20241115_2.pdf); "Compliance: UL1741 SB, UL1741 SA, IEEE1547.1-2020, UL1699B, UL1998, FCC Part15 Class B, California Rule 21, HECO Rule 14H (pending), NEC 690.12-2020,CAN/CSA C22.2107.1-1" (products-high-voltage-11-4kw-hybrid-split-phase-inverter-with-aps-transmitter-sg11-4khb-hv.html). A manufacturer statement names no certificate number or issuer and is not evidence of a listing; certificate documents SunGoldPower serves are recorded separately.
- Record detail
- Issued: Not statedValid from: Not statedExpiry: Not statedNot checked
- Source
- [2] [3]
HECO Rule 14H (pending)manufacturer claimpresent at observation[2] [3]
- Scope
- equipment listing
- Covered models
- SG11.4KHB-HV
- Limitations
- SunGoldPower's own statement, recorded exactly as printed: "UL1741 SB, UL1741 SA, IEEE1547.1-2020, UL1699B, UL1998, FCC Part15 Class B, California Rule 21, HECO Rule 14H (pending), NEC 690.12-2020,CAN/CSA C22.2107.1-1" (Sun_Gold_Power_manual_SG11.4KHB-HV_-_20241115_2.pdf); "Compliance: UL1741 SB, UL1741 SA, IEEE1547.1-2020, UL1699B, UL1998, FCC Part15 Class B, California Rule 21, HECO Rule 14H (pending), NEC 690.12-2020,CAN/CSA C22.2107.1-1" (products-high-voltage-11-4kw-hybrid-split-phase-inverter-with-aps-transmitter-sg11-4khb-hv.html). A manufacturer statement names no certificate number or issuer and is not evidence of a listing; certificate documents SunGoldPower serves are recorded separately.
- Record detail
- Issued: Not statedValid from: Not statedExpiry: Not statedNot checked
- Source
- [2] [3]
IEEE1547.1-2020manufacturer claimpresent at observation[2] [3]
- Scope
- equipment listing
- Covered models
- SG11.4KHB-HV
- Limitations
- SunGoldPower's own statement, recorded exactly as printed: "UL1741 SB, UL1741 SA, IEEE1547.1-2020, UL1699B, UL1998, FCC Part15 Class B, California Rule 21, HECO Rule 14H (pending), NEC 690.12-2020,CAN/CSA C22.2107.1-1" (Sun_Gold_Power_manual_SG11.4KHB-HV_-_20241115_2.pdf); "Compliance: UL1741 SB, UL1741 SA, IEEE1547.1-2020, UL1699B, UL1998, FCC Part15 Class B, California Rule 21, HECO Rule 14H (pending), NEC 690.12-2020,CAN/CSA C22.2107.1-1" (products-high-voltage-11-4kw-hybrid-split-phase-inverter-with-aps-transmitter-sg11-4khb-hv.html). A manufacturer statement names no certificate number or issuer and is not evidence of a listing; certificate documents SunGoldPower serves are recorded separately.
- Record detail
- Issued: Not statedValid from: Not statedExpiry: Not statedNot checked
- Source
- [2] [3]
NEC 690.12-2020manufacturer claimpresent at observation[2] [3]
- Scope
- equipment listing
- Covered models
- SG11.4KHB-HV
- Limitations
- SunGoldPower's own statement, recorded exactly as printed: "UL1741 SB, UL1741 SA, IEEE1547.1-2020, UL1699B, UL1998, FCC Part15 Class B, California Rule 21, HECO Rule 14H (pending), NEC 690.12-2020,CAN/CSA C22.2107.1-1" (Sun_Gold_Power_manual_SG11.4KHB-HV_-_20241115_2.pdf); "Compliance: UL1741 SB, UL1741 SA, IEEE1547.1-2020, UL1699B, UL1998, FCC Part15 Class B, California Rule 21, HECO Rule 14H (pending), NEC 690.12-2020,CAN/CSA C22.2107.1-1" (products-high-voltage-11-4kw-hybrid-split-phase-inverter-with-aps-transmitter-sg11-4khb-hv.html). A manufacturer statement names no certificate number or issuer and is not evidence of a listing; certificate documents SunGoldPower serves are recorded separately.
- Record detail
- Issued: Not statedValid from: Not statedExpiry: Not statedNot checked
- Source
- [2] [3]
UL1699Bmanufacturer claimpresent at observation[2] [3]
- Scope
- equipment listing
- Covered models
- SG11.4KHB-HV
- Limitations
- SunGoldPower's own statement, recorded exactly as printed: "UL1741 SB, UL1741 SA, IEEE1547.1-2020, UL1699B, UL1998, FCC Part15 Class B, California Rule 21, HECO Rule 14H (pending), NEC 690.12-2020,CAN/CSA C22.2107.1-1" (Sun_Gold_Power_manual_SG11.4KHB-HV_-_20241115_2.pdf); "Compliance: UL1741 SB, UL1741 SA, IEEE1547.1-2020, UL1699B, UL1998, FCC Part15 Class B, California Rule 21, HECO Rule 14H (pending), NEC 690.12-2020,CAN/CSA C22.2107.1-1" (products-high-voltage-11-4kw-hybrid-split-phase-inverter-with-aps-transmitter-sg11-4khb-hv.html). A manufacturer statement names no certificate number or issuer and is not evidence of a listing; certificate documents SunGoldPower serves are recorded separately.
- Record detail
- Issued: Not statedValid from: Not statedExpiry: Not statedNot checked
- Source
- [2] [3]
UL1741 SAmanufacturer claimpresent at observation[2] [3]
- Scope
- equipment listing
- Covered models
- SG11.4KHB-HV
- Limitations
- SunGoldPower's own statement, recorded exactly as printed: "UL1741 SB, UL1741 SA, IEEE1547.1-2020, UL1699B, UL1998, FCC Part15 Class B, California Rule 21, HECO Rule 14H (pending), NEC 690.12-2020,CAN/CSA C22.2107.1-1" (Sun_Gold_Power_manual_SG11.4KHB-HV_-_20241115_2.pdf); "Compliance: UL1741 SB, UL1741 SA, IEEE1547.1-2020, UL1699B, UL1998, FCC Part15 Class B, California Rule 21, HECO Rule 14H (pending), NEC 690.12-2020,CAN/CSA C22.2107.1-1" (products-high-voltage-11-4kw-hybrid-split-phase-inverter-with-aps-transmitter-sg11-4khb-hv.html). A manufacturer statement names no certificate number or issuer and is not evidence of a listing; certificate documents SunGoldPower serves are recorded separately.
- Record detail
- Issued: Not statedValid from: Not statedExpiry: Not statedNot checked
- Source
- [2] [3]
UL1741 SBmanufacturer claimpresent at observation[2] [3]
- Scope
- equipment listing
- Covered models
- SG11.4KHB-HV
- Limitations
- SunGoldPower's own statement, recorded exactly as printed: "UL1741 SB, UL1741 SA, IEEE1547.1-2020, UL1699B, UL1998, FCC Part15 Class B, California Rule 21, HECO Rule 14H (pending), NEC 690.12-2020,CAN/CSA C22.2107.1-1" (Sun_Gold_Power_manual_SG11.4KHB-HV_-_20241115_2.pdf); "Compliance: UL1741 SB, UL1741 SA, IEEE1547.1-2020, UL1699B, UL1998, FCC Part15 Class B, California Rule 21, HECO Rule 14H (pending), NEC 690.12-2020,CAN/CSA C22.2107.1-1" (products-high-voltage-11-4kw-hybrid-split-phase-inverter-with-aps-transmitter-sg11-4khb-hv.html). A manufacturer statement names no certificate number or issuer and is not evidence of a listing; certificate documents SunGoldPower serves are recorded separately.
- Record detail
- Issued: Not statedValid from: Not statedExpiry: Not statedNot checked
- Source
- [2] [3]
UL1998manufacturer claimpresent at observation[2] [3]
- Scope
- equipment listing
- Covered models
- SG11.4KHB-HV
- Limitations
- SunGoldPower's own statement, recorded exactly as printed: "UL1741 SB, UL1741 SA, IEEE1547.1-2020, UL1699B, UL1998, FCC Part15 Class B, California Rule 21, HECO Rule 14H (pending), NEC 690.12-2020,CAN/CSA C22.2107.1-1" (Sun_Gold_Power_manual_SG11.4KHB-HV_-_20241115_2.pdf); "Compliance: UL1741 SB, UL1741 SA, IEEE1547.1-2020, UL1699B, UL1998, FCC Part15 Class B, California Rule 21, HECO Rule 14H (pending), NEC 690.12-2020,CAN/CSA C22.2107.1-1" (products-high-voltage-11-4kw-hybrid-split-phase-inverter-with-aps-transmitter-sg11-4khb-hv.html). A manufacturer statement names no certificate number or issuer and is not evidence of a listing; certificate documents SunGoldPower serves are recorded separately.
- Record detail
- Issued: Not statedValid from: Not statedExpiry: Not statedNot checked
- Source
- [2] [3]
Warranty
| Field | Value | Conditions | Source |
|---|---|---|---|
| Warranty term | 10 years | Printed as "10 years standard (Extendable to 20 years)"; the extension terms are not stated in the table. Where: SG11.4KHB-HV User Manual 20241115, section 8 Specifications, Technical Data table (printed pages 62 to 64), Features Warranty row | [2] |
Recalls / legal notices
No recalls on file. All notices · Report a notice
This register is incomplete. A missing notice does not establish that a product has no recalls.
Documents
Manuals
- High Voltage 11.4KW Hybrid Split Phase Inverter User ManualOpen
Certificate & compliance claims (10)
UL1741 SBManufacturer claim · equipment listingClaimedListed when checked
SunGoldPower's own statement, recorded exactly as printed: "UL1741 SB, UL1741 SA, IEEE1547.1-2020, UL1699B, UL1998, FCC Part15 Class B, California Rule 21, HECO Rule 14H (pending), NEC 690.12-2020,CAN/CSA C22.2107.1-1" (Sun_Gold_Power_manual_SG11.4KHB-HV_-_20241115_2.pdf); "Compliance: UL1741 SB, UL1741 SA, IEEE1547.1-2020, UL1699B, UL1998, FCC Part15 Class B, California Rule 21, HECO Rule 14H (pending), NEC 690.12-2020,CAN/CSA C22.2107.1-1" (products-high-voltage-11-4kw-hybrid-split-phase-inverter-with-aps-transmitter-sg11-4khb-hv.html). A manufacturer statement names no certificate number or issuer and is not evidence of a listing; certificate documents SunGoldPower serves are recorded separately.
Manufacturer document
Official instruction manual: High Voltage 11.4KW Hybrid Split Phase Inverter User ManualUL1741 SAManufacturer claim · equipment listingClaimedListed when checked
SunGoldPower's own statement, recorded exactly as printed: "UL1741 SB, UL1741 SA, IEEE1547.1-2020, UL1699B, UL1998, FCC Part15 Class B, California Rule 21, HECO Rule 14H (pending), NEC 690.12-2020,CAN/CSA C22.2107.1-1" (Sun_Gold_Power_manual_SG11.4KHB-HV_-_20241115_2.pdf); "Compliance: UL1741 SB, UL1741 SA, IEEE1547.1-2020, UL1699B, UL1998, FCC Part15 Class B, California Rule 21, HECO Rule 14H (pending), NEC 690.12-2020,CAN/CSA C22.2107.1-1" (products-high-voltage-11-4kw-hybrid-split-phase-inverter-with-aps-transmitter-sg11-4khb-hv.html). A manufacturer statement names no certificate number or issuer and is not evidence of a listing; certificate documents SunGoldPower serves are recorded separately.
Manufacturer document
Official instruction manual: High Voltage 11.4KW Hybrid Split Phase Inverter User ManualIEEE1547.1-2020Manufacturer claim · equipment listingClaimedListed when checked
SunGoldPower's own statement, recorded exactly as printed: "UL1741 SB, UL1741 SA, IEEE1547.1-2020, UL1699B, UL1998, FCC Part15 Class B, California Rule 21, HECO Rule 14H (pending), NEC 690.12-2020,CAN/CSA C22.2107.1-1" (Sun_Gold_Power_manual_SG11.4KHB-HV_-_20241115_2.pdf); "Compliance: UL1741 SB, UL1741 SA, IEEE1547.1-2020, UL1699B, UL1998, FCC Part15 Class B, California Rule 21, HECO Rule 14H (pending), NEC 690.12-2020,CAN/CSA C22.2107.1-1" (products-high-voltage-11-4kw-hybrid-split-phase-inverter-with-aps-transmitter-sg11-4khb-hv.html). A manufacturer statement names no certificate number or issuer and is not evidence of a listing; certificate documents SunGoldPower serves are recorded separately.
Manufacturer document
Official instruction manual: High Voltage 11.4KW Hybrid Split Phase Inverter User ManualUL1699BManufacturer claim · equipment listingClaimedListed when checked
SunGoldPower's own statement, recorded exactly as printed: "UL1741 SB, UL1741 SA, IEEE1547.1-2020, UL1699B, UL1998, FCC Part15 Class B, California Rule 21, HECO Rule 14H (pending), NEC 690.12-2020,CAN/CSA C22.2107.1-1" (Sun_Gold_Power_manual_SG11.4KHB-HV_-_20241115_2.pdf); "Compliance: UL1741 SB, UL1741 SA, IEEE1547.1-2020, UL1699B, UL1998, FCC Part15 Class B, California Rule 21, HECO Rule 14H (pending), NEC 690.12-2020,CAN/CSA C22.2107.1-1" (products-high-voltage-11-4kw-hybrid-split-phase-inverter-with-aps-transmitter-sg11-4khb-hv.html). A manufacturer statement names no certificate number or issuer and is not evidence of a listing; certificate documents SunGoldPower serves are recorded separately.
Manufacturer document
Official instruction manual: High Voltage 11.4KW Hybrid Split Phase Inverter User ManualUL1998Manufacturer claim · equipment listingClaimedListed when checked
SunGoldPower's own statement, recorded exactly as printed: "UL1741 SB, UL1741 SA, IEEE1547.1-2020, UL1699B, UL1998, FCC Part15 Class B, California Rule 21, HECO Rule 14H (pending), NEC 690.12-2020,CAN/CSA C22.2107.1-1" (Sun_Gold_Power_manual_SG11.4KHB-HV_-_20241115_2.pdf); "Compliance: UL1741 SB, UL1741 SA, IEEE1547.1-2020, UL1699B, UL1998, FCC Part15 Class B, California Rule 21, HECO Rule 14H (pending), NEC 690.12-2020,CAN/CSA C22.2107.1-1" (products-high-voltage-11-4kw-hybrid-split-phase-inverter-with-aps-transmitter-sg11-4khb-hv.html). A manufacturer statement names no certificate number or issuer and is not evidence of a listing; certificate documents SunGoldPower serves are recorded separately.
Manufacturer document
Official instruction manual: High Voltage 11.4KW Hybrid Split Phase Inverter User ManualFCC Part15 Class BManufacturer claim · equipment listingClaimedListed when checked
SunGoldPower's own statement, recorded exactly as printed: "UL1741 SB, UL1741 SA, IEEE1547.1-2020, UL1699B, UL1998, FCC Part15 Class B, California Rule 21, HECO Rule 14H (pending), NEC 690.12-2020,CAN/CSA C22.2107.1-1" (Sun_Gold_Power_manual_SG11.4KHB-HV_-_20241115_2.pdf); "Compliance: UL1741 SB, UL1741 SA, IEEE1547.1-2020, UL1699B, UL1998, FCC Part15 Class B, California Rule 21, HECO Rule 14H (pending), NEC 690.12-2020,CAN/CSA C22.2107.1-1" (products-high-voltage-11-4kw-hybrid-split-phase-inverter-with-aps-transmitter-sg11-4khb-hv.html). A manufacturer statement names no certificate number or issuer and is not evidence of a listing; certificate documents SunGoldPower serves are recorded separately.
Manufacturer document
Official instruction manual: High Voltage 11.4KW Hybrid Split Phase Inverter User ManualCalifornia Rule 21Manufacturer claim · equipment listingClaimedListed when checked
SunGoldPower's own statement, recorded exactly as printed: "UL1741 SB, UL1741 SA, IEEE1547.1-2020, UL1699B, UL1998, FCC Part15 Class B, California Rule 21, HECO Rule 14H (pending), NEC 690.12-2020,CAN/CSA C22.2107.1-1" (Sun_Gold_Power_manual_SG11.4KHB-HV_-_20241115_2.pdf); "Compliance: UL1741 SB, UL1741 SA, IEEE1547.1-2020, UL1699B, UL1998, FCC Part15 Class B, California Rule 21, HECO Rule 14H (pending), NEC 690.12-2020,CAN/CSA C22.2107.1-1" (products-high-voltage-11-4kw-hybrid-split-phase-inverter-with-aps-transmitter-sg11-4khb-hv.html). A manufacturer statement names no certificate number or issuer and is not evidence of a listing; certificate documents SunGoldPower serves are recorded separately.
Manufacturer document
Official instruction manual: High Voltage 11.4KW Hybrid Split Phase Inverter User ManualHECO Rule 14H (pending)Manufacturer claim · equipment listingClaimedListed when checked
SunGoldPower's own statement, recorded exactly as printed: "UL1741 SB, UL1741 SA, IEEE1547.1-2020, UL1699B, UL1998, FCC Part15 Class B, California Rule 21, HECO Rule 14H (pending), NEC 690.12-2020,CAN/CSA C22.2107.1-1" (Sun_Gold_Power_manual_SG11.4KHB-HV_-_20241115_2.pdf); "Compliance: UL1741 SB, UL1741 SA, IEEE1547.1-2020, UL1699B, UL1998, FCC Part15 Class B, California Rule 21, HECO Rule 14H (pending), NEC 690.12-2020,CAN/CSA C22.2107.1-1" (products-high-voltage-11-4kw-hybrid-split-phase-inverter-with-aps-transmitter-sg11-4khb-hv.html). A manufacturer statement names no certificate number or issuer and is not evidence of a listing; certificate documents SunGoldPower serves are recorded separately.
Manufacturer document
Official instruction manual: High Voltage 11.4KW Hybrid Split Phase Inverter User ManualNEC 690.12-2020Manufacturer claim · equipment listingClaimedListed when checked
SunGoldPower's own statement, recorded exactly as printed: "UL1741 SB, UL1741 SA, IEEE1547.1-2020, UL1699B, UL1998, FCC Part15 Class B, California Rule 21, HECO Rule 14H (pending), NEC 690.12-2020,CAN/CSA C22.2107.1-1" (Sun_Gold_Power_manual_SG11.4KHB-HV_-_20241115_2.pdf); "Compliance: UL1741 SB, UL1741 SA, IEEE1547.1-2020, UL1699B, UL1998, FCC Part15 Class B, California Rule 21, HECO Rule 14H (pending), NEC 690.12-2020,CAN/CSA C22.2107.1-1" (products-high-voltage-11-4kw-hybrid-split-phase-inverter-with-aps-transmitter-sg11-4khb-hv.html). A manufacturer statement names no certificate number or issuer and is not evidence of a listing; certificate documents SunGoldPower serves are recorded separately.
Manufacturer document
Official instruction manual: High Voltage 11.4KW Hybrid Split Phase Inverter User ManualCAN/CSA C22.2107.1-1Manufacturer claim · equipment listingClaimedListed when checked
SunGoldPower's own statement, recorded exactly as printed: "UL1741 SB, UL1741 SA, IEEE1547.1-2020, UL1699B, UL1998, FCC Part15 Class B, California Rule 21, HECO Rule 14H (pending), NEC 690.12-2020,CAN/CSA C22.2107.1-1" (Sun_Gold_Power_manual_SG11.4KHB-HV_-_20241115_2.pdf); "Compliance: UL1741 SB, UL1741 SA, IEEE1547.1-2020, UL1699B, UL1998, FCC Part15 Class B, California Rule 21, HECO Rule 14H (pending), NEC 690.12-2020,CAN/CSA C22.2107.1-1" (products-high-voltage-11-4kw-hybrid-split-phase-inverter-with-aps-transmitter-sg11-4khb-hv.html). A manufacturer statement names no certificate number or issuer and is not evidence of a listing; certificate documents SunGoldPower serves are recorded separately.
Manufacturer document
Official instruction manual: High Voltage 11.4KW Hybrid Split Phase Inverter User ManualSource details
SunGoldPower publishes this instruction manual for SG11.4KHB-HV and names no other model in this catalog on it. Read from https://sungoldpower.com/collections/power-inverter on 2026-09-19. It establishes only what it prints; no issuer, laboratory or revision-currency check was made.
Location: Document title as published
Retrieved Sep 19, 2026
SunGoldPower publishes this instruction manual for SG11.4KHB-HV and names no other model in this catalog on it. Read from https://sungoldpower.com/collections/power-inverter on 2026-09-19. It establishes only what it prints; no issuer, laboratory or revision-currency check was made.
SHA-256: 0b8e9c2719fe51d58cc7bf7ba824bd94653539a5539e995e4def0a15cca0d8ee
Archived copies
Archived copy of a document published by SunGoldPower. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email [email protected].
Archived backupRevision not recorded · 6.91 MBArchived copy, unaltered, kept as a record of what SunGoldPower published. Original address: https://cdn.shopify.com/s/files/1/0323/4090/2025/files/Sun_Gold_Power_manual_SG11.4KHB-HV_-_20241115_2.pdf. Copyright and takedown
File details
Original sourceEmbedded dates are file metadata, not independent proof of publication.
SHA-256: 0b8e9c2719fe51d58cc7bf7ba824bd94653539a5539e995e4def0a15cca0d8ee
Other documents
- High Voltage 11.4KW Hybrid Split Phase Inverter with APS Transmitter SG11.4KHB-HV, SunGoldPower product page (September 23, 2026 capture)Open
Source details
Captured by scripts/prepare-brand-sweep-sep21.mjs on 2026-09-23.
Location: Product heading; Highlight list; Specification and User Manual tabs (manual-download-button links)
Retrieved Sep 22, 2026
SunGoldPower's own product page, captured byte for byte on September 23, 2026. It establishes what SunGoldPower published for SG11.4KHB-HV on that date: the page heading, the Highlight text, the variant selector (SKUs SG11.4KHB-HV) and the 1 document link(s) under its User Manual tab. Prices and stock on the page are the state of a promotional storefront and are not recorded from it. A specification quoted from the page is SunGoldPower's own published figure, not a test result.
Archive and older revisions
Archive and older revisions0
Earlier revisions, archived captures and copies published by someone other than the manufacturer. Every one stays reachable.
Archived documents
High Voltage 11.4KW Hybrid Split Phase Inverter User Manual
Archived copy of a document published by SunGoldPower. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email [email protected].
Archived copy, unaltered, kept as a record of what SunGoldPower published. Original address: https://cdn.shopify.com/s/files/1/0323/4090/2025/files/Sun_Gold_Power_manual_SG11.4KHB-HV_-_20241115_2.pdf. Copyright and takedown
File details
Original sourceEmbedded dates are file metadata, not independent proof of publication.
SHA-256: 0b8e9c2719fe51d58cc7bf7ba824bd94653539a5539e995e4def0a15cca0d8ee
Parts and accessories
No sourced accessories or replacement parts listed yet.
Model history
Model identity
- Model
- SG11.4KHB-HV
Manufacturer SKU SG11.4KHB-HV
No historical observations recorded yet.
Other recorded fields
| Field | Value | Conditions | Source |
|---|---|---|---|
| Evidence breakdown | method version: inverters-0.5-personal documented pct: 90 basis: Unknown missing: Idle consumption needed criteria: key: certificates label: Certificates value: 31.5 unit: Unknown shown: UL1741 SB · UL1741 SA +7 shown detail: Claimed state: claimed points: 14.2 ceiling: 45 weight: 45 share: 31.5 covered: yes missing: no folded: no reason: Unknown reason text: Unknown note: Manufacturer claim; issuer verification pending. Applies to the exact inverter. display note: Unknown key: warranty label: Warranty term value: 10 unit: Unknown shown: 10 years shown detail: Unknown state: documented points: 12 ceiling: 30 weight: 30 share: 40 covered: yes missing: no folded: no reason: Unknown reason text: Unknown note: display note: Unknown Sources: [2] key: efficiency label: Battery conversion efficiency value: 97 unit: Unknown shown: 97 % shown detail: Unknown state: documented points: 14.8 ceiling: 15 weight: 15 share: 98.8 covered: yes missing: no folded: no reason: Unknown reason text: Unknown note: display note: Unknown Sources: [2] key: idle label: Idle consumption value: Unknown unit: Unknown shown: Research pending shown detail: Unknown state: pending points: 0 ceiling: 10 weight: 10 share: Unknown covered: no missing: yes folded: yes reason: undocumented reason text: Not documented. Undisclosed data scores 0. note: Not documented. display note: Unknown Sources: No source on record | ||
Community discussions
No discussions linked yet. Search DIY Solar Forum
Sources
- SunGoldPower store product data (products.json page 1, 2026-10-27 capture) Paid link (SunGoldPower · manufacturer · observed Oct 27, 2026)
- High Voltage 11.4KW Hybrid Split Phase Inverter User Manual (SunGoldPower · manufacturer · observed Sep 19, 2026)
- High Voltage 11.4KW Hybrid Split Phase Inverter with APS Transmitter SG11.4KHB-HV, SunGoldPower product page (September 23, 2026 capture) Paid link (SunGoldPower · manufacturer · observed Sep 22, 2026)
- SunGoldPower store product data (sungoldpower.com products.json, page 1, October 31, 2026 capture) Paid link (SunGoldPower · seller · observed Oct 31, 2026)
Sign in to report an error on this page
Similar products
All with a priceGoodWe GW11K4-ES-US20
Growatt MIN 11400TL-XH-US
Solis S6-EH1P11.4K-H-US
SunGoldPower SGN-11K15PRO
* Missing details