Printed as "BOS-GL60" in the Model row of Deye's BOS-GL60 & BOS-GH60 series brochure for North America (20260707 v1.0). Deye publishes no separate stock keeping number; the model designation is recorded, as on the catalog's other Deye records. Revised on 1 October 2026: The recorded "BOS-GH/BOS-GL" is the family designation on Deye's product page and covers both models; this record now covers the BOS-GL60 only.
Location: Brochure page 2, Rack-Mounted Battery table, Model row
Documented
Also listed as
BOS-GH/BOS-GL
Deye publishes the family designation BOS-GH / BOS-GL and names the North American builds BOS-GL60, BOS-GH40 and BOS-GH60; it publishes no stock keeping number. The seller's own SKU is DEB60K.Official product pageSources
Deye publishes the family designation BOS-GH / BOS-GL and names the North American builds BOS-GL60, BOS-GH40 and BOS-GH60; it publishes no stock keeping number. The seller's own SKU is DEB60K.
Printed as "LiFePO4" in the Cell Chemistry row of Deye's BOS-GL60 & BOS-GH60 series brochure for North America (20260707 v1.0), in a cell the table shares across the BOS-GL60, BOS-GH40 and BOS-GH60 columns. Deye's BOS-GL & BOS-GH (NA) product page prints "Battery Chemistry LiFePO4". Revised on 1 October 2026: The value is unchanged; it is now cited first to Deye's North America brochure, which ranks above the product page.
Printed as "61.44" in the System Energy ( kWh ) row of Deye's BOS-GL60 & BOS-GH60 series brochure for North America (20260707 v1.0), read from the BOS-GL60 column of the rendered page 2 table. Deye's BOS-GL & BOS-GH (NA) product page prints "BOS-GL60 combines twelve modules in a 2P6S configuration, delivering 61.44 kWh of total energy at a nominal system voltage of 307.2 V." Revised on 1 October 2026: The value is unchanged; it is now cited first to Deye's North America brochure, which ranks above the product page.
Printed as "55.29" in the System Usable Energy ( kWh ) row of Deye's BOS-GL60 & BOS-GH60 series brochure for North America (20260707 v1.0), read from the BOS-GL60 column of the rendered page 2 table; footnote 1 reads "DC Usable Energy, test conditions : 90% DOD, 0.3C charge & discharge at 25°C. System usable energy may vary due to system configuration parameters." Revised on 1 October 2026: The value is unchanged; the record now covers the BOS-GL60 only, and the note quotes that model's column and footnote.
Printed as "307.2" in the System Nominal Voltage ( V ) row of Deye's BOS-GL60 & BOS-GH60 series brochure for North America (20260707 v1.0), BOS-GL60 column (the row prints 307.2, 409.6 and 614.4 for BOS-GL60, BOS-GH40 and BOS-GH60). Deye's BOS-GL and BOS-GH installation and operation instructions (English edition, Issue 02), 4.3 Technical Data, print the same figure: "System Nominal Voltage (V) 614.4 307.2" for BOS-GH and BOS-GL. Deye's product page prints "a nominal system voltage of 307.2 V" for the BOS-GL60. Revised on October 5, 2026: the earlier 51.2 V is the voltage the brochure prints for one module ("Module Nominal Voltage ( V ) 51.2"), not for the BOS-GL60 system whose energy this record gives.
Printed as "Charge/Discharge Current (A)² Recommend 50 100 Nominal 100 100" in the Deye Installation and Operation Instructions, Lithium Storage System BOS-GL BOS-GH (Issue 02, 20250709; English edition) (page 15, 4.3 Technical Data, Charge/Discharge Current (A), Nominal row). The BOS-GL value is the second of the two columns (BOS-GH, BOS-GL); printed as the Nominal charge/discharge current. The manual notes the current is affected by temperature and SOC.
Printed as "Charge/Discharge Current (A)² Recommend 50 100 Nominal 100 100" in the Deye Installation and Operation Instructions, Lithium Storage System BOS-GL BOS-GH (Issue 02, 20250709; English edition) (page 15, 4.3 Technical Data, Charge/Discharge Current (A), Nominal row). The BOS-GL value is the second of the two columns (BOS-GH, BOS-GL); printed as the Nominal charge/discharge current. The manual notes the current is affected by temperature and SOC.
Printed as "125" in the "Peak Discharge ( 5S, 25℃ )" row of Deye's BOS-GL60 & BOS-GH60 series brochure for North America (20260707 v1.0), in a cell the table shares across the BOS-GL60, BOS-GH40 and BOS-GH60 columns: a five-second peak at 25°C.
The English edition manual prints a different value
Deye's BOS-GL60 & BOS-GH60 series brochure for North America prints the recorded operating voltage range (240 to 350.4 V); Deye's English (EN) edition of the BOS-GL and BOS-GH installation and operation instructions (Issue 02, 20250709) prints 268.8 to 350.4 V. Deye's product page also lists a separate UL edition of the user manual, which was not obtained.
Printed as "240 ~ 350.4" in the System Operating Voltage ( V ) row of Deye's BOS-GL60 & BOS-GH60 series brochure for North America (20260707 v1.0), read from the BOS-GL60 column of the rendered page 2 table.
268.8 to 350.4 V
Printed as "System Operating Voltage (V) 537.6~700.8 268.8~350.4" in Deye's Installation and Operation Instructions, Lithium Storage System BOS-GL BOS-GH (English edition, Issue 02, 20250709), 4.3 Technical Data, System Operating Voltage row. The row prints 537.6~700.8 for BOS-GH and 268.8~350.4 for BOS-GL (columns checked on rendered page 15). This record is the North American version. The English edition manual may describe different hardware, so the North American brochure's operating voltage range stays primary and the manual's range is kept here as an alternative.
Printed as "LiFePO4" in the Cell Chemistry row of Deye's BOS-GL60 & BOS-GH60 series brochure for North America (20260707 v1.0), in a cell the table shares across the BOS-GL60, BOS-GH40 and BOS-GH60 columns. Deye's BOS-GL & BOS-GH (NA) product page prints "Battery Chemistry LiFePO4". Revised on 1 October 2026: The value is unchanged; it is now cited first to Deye's North America brochure, which ranks above the product page.
Printed as "61.44" in the System Energy ( kWh ) row of Deye's BOS-GL60 & BOS-GH60 series brochure for North America (20260707 v1.0), read from the BOS-GL60 column of the rendered page 2 table. Deye's BOS-GL & BOS-GH (NA) product page prints "BOS-GL60 combines twelve modules in a 2P6S configuration, delivering 61.44 kWh of total energy at a nominal system voltage of 307.2 V." Revised on 1 October 2026: The value is unchanged; it is now cited first to Deye's North America brochure, which ranks above the product page.
Printed as "55.29" in the System Usable Energy ( kWh ) row of Deye's BOS-GL60 & BOS-GH60 series brochure for North America (20260707 v1.0), read from the BOS-GL60 column of the rendered page 2 table; footnote 1 reads "DC Usable Energy, test conditions : 90% DOD, 0.3C charge & discharge at 25°C. System usable energy may vary due to system configuration parameters." Revised on 1 October 2026: The value is unchanged; the record now covers the BOS-GL60 only, and the note quotes that model's column and footnote.
Printed as "307.2" in the System Nominal Voltage ( V ) row of Deye's BOS-GL60 & BOS-GH60 series brochure for North America (20260707 v1.0), BOS-GL60 column (the row prints 307.2, 409.6 and 614.4 for BOS-GL60, BOS-GH40 and BOS-GH60). Deye's BOS-GL and BOS-GH installation and operation instructions (English edition, Issue 02), 4.3 Technical Data, print the same figure: "System Nominal Voltage (V) 614.4 307.2" for BOS-GH and BOS-GL. Deye's product page prints "a nominal system voltage of 307.2 V" for the BOS-GL60. Revised on October 5, 2026: the earlier 51.2 V is the voltage the brochure prints for one module ("Module Nominal Voltage ( V ) 51.2"), not for the BOS-GL60 system whose energy this record gives.
Location: Brochure page 2, Rack-Mounted Battery table, System Nominal Voltage ( V ) row, BOS-GL60 column
Documented
Rated capacity
Not documented
Details
Deye prints no capacity in Ah for the BOS-GL60 system. The North America brochure prints "Module Capacity ( Ah ) 100" for one 5.12 kWh module and "12(2P6S)" modules for the BOS-GL60. Revised on October 5, 2026: the earlier 100 Ah was that module figure, recorded beside the system's energy; it is left unfilled rather than derived.
Printed as "Charge/Discharge Current (A)² Recommend 50 100 Nominal 100 100" in the Deye Installation and Operation Instructions, Lithium Storage System BOS-GL BOS-GH (Issue 02, 20250709; English edition) (page 15, 4.3 Technical Data, Charge/Discharge Current (A), Nominal row). The BOS-GL value is the second of the two columns (BOS-GH, BOS-GL); printed as the Nominal charge/discharge current. The manual notes the current is affected by temperature and SOC.
Printed as "Charge/Discharge Current (A)² Recommend 50 100 Nominal 100 100" in the Deye Installation and Operation Instructions, Lithium Storage System BOS-GL BOS-GH (Issue 02, 20250709; English edition) (page 15, 4.3 Technical Data, Charge/Discharge Current (A), Nominal row). The BOS-GL value is the second of the two columns (BOS-GH, BOS-GL); printed as the Nominal charge/discharge current. The manual notes the current is affected by temperature and SOC.
Printed as "125" in the "Peak Discharge ( 5S, 25℃ )" row of Deye's BOS-GL60 & BOS-GH60 series brochure for North America (20260707 v1.0), in a cell the table shares across the BOS-GL60, BOS-GH40 and BOS-GH60 columns: a five-second peak at 25°C.
The English edition manual prints a different value
Deye's BOS-GL60 & BOS-GH60 series brochure for North America prints the recorded operating voltage range (240 to 350.4 V); Deye's English (EN) edition of the BOS-GL and BOS-GH installation and operation instructions (Issue 02, 20250709) prints 268.8 to 350.4 V. Deye's product page also lists a separate UL edition of the user manual, which was not obtained.
Printed as "240 ~ 350.4" in the System Operating Voltage ( V ) row of Deye's BOS-GL60 & BOS-GH60 series brochure for North America (20260707 v1.0), read from the BOS-GL60 column of the rendered page 2 table.
268.8 to 350.4 V
Printed as "System Operating Voltage (V) 537.6~700.8 268.8~350.4" in Deye's Installation and Operation Instructions, Lithium Storage System BOS-GL BOS-GH (English edition, Issue 02, 20250709), 4.3 Technical Data, System Operating Voltage row. The row prints 537.6~700.8 for BOS-GH and 268.8~350.4 for BOS-GL (columns checked on rendered page 15). This record is the North American version. The English edition manual may describe different hardware, so the North American brochure's operating voltage range stays primary and the manual's range is kept here as an alternative.
Printed as "100" in the Recommend row of the Charge / Discharge Current ( A ) block of Deye's BOS-GL60 & BOS-GH60 series brochure for North America (20260707 v1.0), read from the BOS-GL60 column of the rendered page 2 table; footnote 2 reads "The current is affected by temperature and SOC."
Printed as "25±2°C, 0.5C / 0.5C, EOL70%≥6000" in the Cycle Life row of Deye's BOS-GL60 & BOS-GH60 series brochure for North America (20260707 v1.0), in a cell the table shares across the BOS-GL60, BOS-GH40 and BOS-GH60 columns: at least 6,000 cycles at 25±2°C, 0.5C charge and discharge, to 70% end-of-life capacity. Deye's product page prints "Rated for 6,000+ cycles". Revised on 1 October 2026: The value is unchanged; it is now cited first to Deye's North America brochure, which ranks above the product page.
Printed as "25±2°C, 0.5C / 0.5C, EOL70%≥6000" in the same maker document as the recorded cycle life; the cycle life ends at 70% of capacity as printed.
Location: Brochure page 2, Rack-Mounted Battery table, Cycle Life row
Documented
Lifetime production
Not published
Published claims and calculations are not independently tested lifetime output.
Battery weight
635 kg1,400 lb converted
The English edition manual prints a different value
Deye's BOS-GL60 & BOS-GH60 series brochure for North America prints the recorded weight (635 kg); Deye's English (EN) edition of the BOS-GL and BOS-GH installation and operation instructions (Issue 02, 20250709) prints 610 kg (approximate). Deye's product page also lists a separate UL edition of the user manual, which was not obtained.
Printed as "75+45 × 12+20=635kg" in the "Weight Approximate ( kg )" row of Deye's BOS-GL60 & BOS-GH60 series brochure for North America (20260707 v1.0), read from the BOS-GL60 column of the rendered page 2 table; an approximate figure, the brochure's own sum of cabinet, twelve modules and control box. Revised on 1 October 2026: The recorded 594 kg came from a seller listing that names no model; Deye prints an approximate 635 kg for the BOS-GL60.
610 kg / 1,344.82 lb
Printed as "Weight Approximate (kg) 610" in Deye's Installation and Operation Instructions, Lithium Storage System BOS-GL BOS-GH (English edition, Issue 02, 20250709), 4.3 Technical Data, Weight Approximate row. This record is the North American version. The English edition manual may describe different hardware, so the North American brochure's weight stays primary and the manual's weight is kept here as an alternative.
773.13 L*Calculated: Enclosure volume: W × H × D ÷ 1,000,000
The English edition manual prints a different value
Deye's BOS-GL60 & BOS-GH60 series brochure for North America prints the recorded dimensions (530 x 667 x 2187 mm (W x D x H)); Deye's English (EN) edition of the BOS-GL and BOS-GH installation and operation instructions (Issue 02, 20250709) prints 530*602*2219 mm (W/D/H) for the 13-floor rack. Deye's product page also lists a separate UL edition of the user manual, which was not obtained.
Printed as "530 × 667 × 2187" in the "Dimension ( W × D × H, mm )" row of Deye's BOS-GL60 & BOS-GH60 series brochure for North America (20260707 v1.0), read from the BOS-GL60 column of the rendered page 2 table; width 530 mm, depth 667 mm, height 2187 mm, as the row heading orders them. Revised on 1 October 2026: The recorded size came from a seller's unlabeled "530 × 602 × 2187 mm" with axes assigned by the catalog; Deye prints width, depth and height for the BOS-GL60 as 530 × 667 × 2187 mm.
602 D × 530 W × 2,219 H mm
Printed as "Dimensions (W/D/H,mm) 13th floor: 530*602*2219" in Deye's Installation and Operation Instructions, Lithium Storage System BOS-GL BOS-GH (English edition, Issue 02, 20250709), 4.3 Technical Data, Dimensions row. The order is width, depth and height; 13th floor is the rack with twelve battery modules and the HV control box. This record is the North American version. The English edition manual may describe different hardware, so the North American brochure's dimensions stay primary and the manual's dimensions are kept here as an alternative.
Printed as "IP20" in the IP Rating of Enclosure row of Deye's BOS-GL60 & BOS-GH60 series brochure for North America (20260707 v1.0), in a cell the table shares across the BOS-GL60, BOS-GH40 and BOS-GH60 columns. Deye's product page prints the same rating. Revised on 1 October 2026: The value is unchanged; it is now cited first to Deye's North America brochure, which ranks above the product page.
Printed as "CAN2.0 / RS485" in the Communication Port row of Deye's BOS-GL60 & BOS-GH60 series brochure for North America (20260707 v1.0), in a cell the table shares across the BOS-GL60, BOS-GH40 and BOS-GH60 columns. Deye's product page prints the same ports. Revised on 1 October 2026: The value is unchanged; it is now cited first to Deye's North America brochure, which ranks above the product page.
Printed as "Supports up to 16 battery clusters in parallel" beside the BOS-GL60 system diagram on page 3 of Deye's BOS-GL60 & BOS-GH60 series brochure for North America (20260707 v1.0) ("[30kW Inverter+Battery ( BOS-GL60 ) × 16] × 10" for the BOS-GL60, "[60kW Inverter+Battery ( BOS-GH60 ) × 16] × 10" for the BOS-GH60).
Printed as "0 ~ 35" in the Storage Temperature ( °C ) row of Deye's BOS-GL60 & BOS-GH60 series brochure for North America (20260707 v1.0), in a cell the table shares across the BOS-GL60, BOS-GH40 and BOS-GH60 columns.
Printed as "Charge : 0 ~ 55 / Discharge : -20 ~ 55" in the Working Temperature ( °C ) row of Deye's BOS-GL60 & BOS-GH60 series brochure for North America (20260707 v1.0), in a cell the table shares across the BOS-GL60, BOS-GH40 and BOS-GH60 columns.
Printed as "Charge : 0 ~ 55 / Discharge : -20 ~ 55" in the Working Temperature ( °C ) row of Deye's BOS-GL60 & BOS-GH60 series brochure for North America (20260707 v1.0), in a cell the table shares across the BOS-GL60, BOS-GH40 and BOS-GH60 columns.
Printed as "hole reserved for grounding on the HV control box using an M4 screw"; "holes reserved for grounding on the battery rack using an M6 screw" in the Deye Installation and Operation Instructions, Lithium Storage System BOS-GL BOS-GH (Issue 02, 20250709; English edition) (page 33, 4.10.2 Grounding description). Applies to both BOS-GH and BOS-GL.
Location: PDF page 33, 4.10.2 Grounding description
Documented
Installation clearances (manual)
The minimum distance away from surrounding barriers is 100mm.
From the English edition manual; the North American edition may differ
The value comes from Deye's English (EN) edition of the BOS-GL and BOS-GH installation and operation instructions (Issue 02, 20250709). Deye's product page also lists a separate UL edition of the user manual, which was not obtained, so the North American edition may print a different value.
Printed as "The minimum distance away from surrounding barriers is 100mm." in Deye's Installation and Operation Instructions, Lithium Storage System BOS-GL BOS-GH (English edition, Issue 02, 20250709), 1.6 Installation Environment, Minimum product installation distance.
From the English edition manual; the North American edition may differ
The value comes from Deye's English (EN) edition of the BOS-GL and BOS-GH installation and operation instructions (Issue 02, 20250709). Deye's product page also lists a separate UL edition of the user manual, which was not obtained, so the North American edition may print a different value.
Charged Reviews classified this product from the documents it is based on. It is our own grouping, not a manufacturer claim.
Printed as "Rack-Mounted Battery" and "Standard 19inch rack can install 12 / 8 pcs batteries". Classified as Server rack from the maker's own words for this model.
Printed as "307.2" in the System Nominal Voltage ( V ) row of Deye's BOS-GL60 & BOS-GH60 series brochure for North America (20260707 v1.0), read from the BOS-GL60 column of the rendered page 2 table. Revised on 1 October 2026: The recorded 614.4 V came from a seller listing and is the BOS-GH60 figure; Deye prints 307.2 V for the BOS-GL60, which this record now covers.
Location: Brochure page 2, Rack-Mounted Battery table, System Nominal Voltage ( V ) row
Documented
Battery cable size (manual)
Positive PCS power cord (6AWG 2000mm); Negative PCS power cord (6AWG 2000mm)
From the English edition manual; the North American edition may differ
The value comes from Deye's English (EN) edition of the BOS-GL and BOS-GH installation and operation instructions (Issue 02, 20250709). Deye's product page also lists a separate UL edition of the user manual, which was not obtained, so the North American edition may print a different value.
Printed as "Positive PCS power cord (6AWG 2000mm) Standard 2" and "Negative PCS power cord (6AWG 2000mm) Standard 2" in Deye's Installation and Operation Instructions, Lithium Storage System BOS-GL BOS-GH (English edition, Issue 02, 20250709), 4.8 Cable List, items 11 and 12. The supplied cables from the battery system to the inverter (PCS), two of each.
Printed as "Module Energy ( kWh ) 5.12" in Deye's BOS-GL60 & BOS-GH60 series brochure for North America (20260707 v1.0), in a cell the table shares across the BOS-GL60, BOS-GH40 and BOS-GH60 columns. Deye's product page prints "Module Energy 5.12 kWh". Revised on 1 October 2026: The value is unchanged; it is now cited first to Deye's North America brochure, which ranks above the product page.
Printed as "61.44" in the System Energy ( kWh ) row of Deye's BOS-GL60 & BOS-GH60 series brochure for North America (20260707 v1.0), read from the BOS-GL60 column of the rendered page 2 table. Revised on 1 October 2026: The value is unchanged; the record now covers the BOS-GL60 only and cites Deye's brochure column for it instead of a seller listing.
Location: Brochure page 2, Rack-Mounted Battery table, System Energy ( kWh ) row
Documented
Communication ports (manual)
PCS COM battery communication terminal: (RJ45 port) follow the CAN protocol (default baud rate: 500bps) and RS485 protocol (default baud rate:9.6bps), used to output battery information to the inverter.
From the English edition manual; the North American edition may differ
The value comes from Deye's English (EN) edition of the BOS-GL and BOS-GH installation and operation instructions (Issue 02, 20250709). Deye's product page also lists a separate UL edition of the user manual, which was not obtained, so the North American edition may print a different value.
Printed as "PCS COM battery communication terminal: (RJ45 port) follow the CAN protocol (default baud rate: 500bps) and RS485 protocol (default baud rate:9.6bps), used to output battery information to the inverter." in Deye's Installation and Operation Instructions, Lithium Storage System BOS-GL BOS-GH (English edition, Issue 02, 20250709), 4.7 Description of HVB, item 15. The baud rates are quoted as printed.
Printed as "UL1973 / UL9540A / UN38.3 / UL9540" in the Certification row of Deye's BOS-GL60 & BOS-GH60 series brochure for North America (20260707 v1.0), in a cell the table shares across the BOS-GL60, BOS-GH40 and BOS-GH60 columns. Manufacturer claims; no issuer record was checked. Revised on 1 October 2026: The value is unchanged; it is now cited first to Deye's North America brochure, which ranks above the product page.
From the English edition manual; the North American edition may differ
The value comes from Deye's English (EN) edition of the BOS-GL and BOS-GH installation and operation instructions (Issue 02, 20250709). Deye's product page also lists a separate UL edition of the user manual, which was not obtained, so the North American edition may print a different value.
Printed as "HV control box grounding 1.2N.m" in Deye's Installation and Operation Instructions, Lithium Storage System BOS-GL BOS-GH (English edition, Issue 02, 20250709), 8.1 Maintenance, tightening torque table, HV control box grounding row. The manual prints the unit as N.m.
Printed as "A DC isolation switch is added into between the HV Box and the PCS" in the Deye Installation and Operation Instructions, Lithium Storage System BOS-GL BOS-GH (Issue 02, 20250709; English edition) (page 32, 4.10.1 Wiring, BOS-GL, Attach to the PCS step (4)). Printed in the BOS-GL wiring steps.
Printed as "(RJ45 port) follow the CAN protocol (default baud rate: 500bps) and RS485 protocol"; "used to output battery information to the inverter" in the Deye Installation and Operation Instructions, Lithium Storage System BOS-GL BOS-GH (Issue 02, 20250709; English edition) (page 19, 4.7 Description of HVB, PCS COM row). The PCS COM port on the HV control box, which applies to both BOS-GH and BOS-GL.
Printed as "100" in the Recommend row of the Charge / Discharge Current ( A ) block of Deye's BOS-GL60 & BOS-GH60 series brochure for North America (20260707 v1.0), read from the BOS-GL60 column of the rendered page 2 table; the row covers both charge and discharge.
Location: Brochure page 2, Rack-Mounted Battery table, Charge / Discharge Current ( A ), Recommend row
Documented
Published claims and calculations, not independent test results.
Documents
2 on file
PDF
Deye Installation and Operation Instructions, Lithium Storage System BOS-GL BOS-GH (Issue 02, 20250709; English edition)OfficialDeyeOfficial installation manualJuly 2025
Source details
Revision
Issue: 02
Revision date
July 2025
English edition linked from Deye's product page through a hosted flipbook; obtained by Alternative Research on 2 October 2026.
Location: PDF page 1 (cover, issue and date) and PDF pages 4 and 5 (1.2 System Description, models covered)
Retrieved
Deye's own installation and operation instructions for its BOS-GL and BOS-GH lithium storage systems; the cover prints "Issue: 02" and the date 20250709. Section 1.2 lists BOS-GH15 to BOS-GH60 and BOS-GL 20 to BOS-GL 60, and the technical data table (PDF page 15) has one column for BOS-GH and one for BOS-GL. Deye's BOS-GL & BOS-GH product page, as the Internet Archive captured it on 14 November 2025, links this file through a hosted flipbook as the "Deye BOS-GL & BOS-GH User Manual EN" and lists a separate "User Manual UL (JA)", which was not obtained, so this is labeled the English edition and the North American edition may differ. The file was obtained by Alternative Research on 2 October 2026 from the flipbook host, because Deye's own site refuses our research agent. Manufacturer instructions, not independent tests.
Archived copies
Archived copy of a document published by Deye. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email legal@chargedreviews.com.
Location: Technical Specifications; description; feature list "Certification:" line
Retrieved
Deye's own product page for the BOS-GL and BOS-GH (NA) rack-mounted battery systems, captured on September 25, 2026. It establishes the Technical Specifications block, the feature list with its "Certification:" line and the names of the certificate files the page offers for download. The certification line is a manufacturer statement.
Earlier revisions, archived captures and copies published by someone other than the manufacturer. Every one stays reachable.
PDF
Deye BOS-GL60 & BOS-GH60 series brochure, North America, 2026-07-07 v1.0OfficialNingbo Deye TechnologyOfficial document
Source details
Revision
Not stated
Revision date
Not stated
Numeric columns did not yield extractable text; no fact cites this file.
Location: Rack-mounted battery model table: BOS-GL60 / BOS-GH40 / BOS-GH60
Retrieved
North American brochure PDF for the BOS-GL60 and BOS-GH60, archived 20 September 2026. Row labels extract but the numeric columns are set in embedded fonts that did not extract reliably, so no numeric value here is read from it; it establishes only that the North American names of this family are BOS-GL60, BOS-GH40 and BOS-GH60.
Archived copies
Archived copy of a document published by Ningbo Deye Technology. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email legal@chargedreviews.com.
Location: Technical Specifications table, feature list and voltage-architecture section
Retrieved
Deye's own North American product page for the BOS-GL and BOS-GH rack battery systems, read on 20 September 2026. It establishes the shared 5.12 kWh / 51.2 V / 100 Ah module, the series counts and the resulting system voltages and energies, the enclosure rating, the cycle rating and the warranty term. It does not establish which configuration any reseller ships, nor the mass or footprint of an assembled rack.
Best Solar Bundle: Deye Bos GL/H 60kwh SystemBest Solar BundleDistributor product page
Source details
Revision
Not stated
Revision date
Not stated
Location: Overview "Bundle Contents" block, variant selector and the "Tech Specs" tables
Retrieved
Best Solar Bundle product page read on 20 September 2026. It establishes what this affiliate distributor lists, at what price, under which variant stock keeping units, plus the contents list and the per-component specification tables the seller prints. It is a seller statement throughout: it is not a manufacturer datasheet and it establishes no manufacturer part number, test condition or certification.
Deye BOS-GL60 & BOS-GH60 series brochure, North America, 2026-07-07 v1.0
Archived copy of a document published by Ningbo Deye Technology. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email legal@chargedreviews.com.
Deye Installation and Operation Instructions, Lithium Storage System BOS-GL BOS-GH (Issue 02, 20250709; English edition)
Archived copy of a document published by Deye. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email legal@chargedreviews.com.
Printed as "10 years" in the Warranty row of Deye's BOS-GL60 & BOS-GH60 series brochure for North America (20260707 v1.0), in a cell shared by all three columns; footnote 3 reads "The warranty is due whichever reached first of warranty period or life cycle power." The warranty terms document was not read. Revised on 1 October 2026: The value is unchanged; it is now cited first to Deye's North America brochure, which ranks above the product page.
The Evidence score uses the priorities you choose. It counts published documents, such as certificates and warranty terms, and it compares a documented figure with the best documented figure of the same kind. It does not count owner reviews, and it is not a verdict on product quality or on how many people have reviewed it. A low score can mean little is documented, or that a documented figure is below the best of its kind. Undisclosed data scores 0.
Missing details. This number counts only the evidence recorded so far. The source review for this product is not finished, or the maker has not disclosed enough, so the number can only go up.
Missing for this product: Warranty energy disclosure evidence needed; Cell model disclosure evidence needed.
High voltage · Server rack · Rated capacity
The warranty term and the lifetime energy are each scored against the best documented value for a home storage battery: a value earns its share of that best, times the weight. A documented value always earns points; an undisclosed one earns 0.
CertificatesCEC · UL 1973 +3CEC listed45 / 45
100 evidence points · 45% weight
CEC listing: full credit for the certificate criterion. Exact model found in the dated CEC equipment list. This is not a safety certification or system approval. Applies: CEC; UL 9540; UL 1973.
Printed as "10 years" in the Warranty row of Deye's BOS-GL60 & BOS-GH60 series brochure for North America (20260707 v1.0), in a cell shared by all three columns; footnote 3 reads "The warranty is due whichever reached first of warranty period or life cycle power." The warranty terms document was not read. Revised on 1 October 2026: The value is unchanged; it is now cited first to Deye's North America brochure, which ranks above the product page.
Research pending, 0 points: Warranty energy disclosure, Cell model disclosure.
Computed from public specifications and evidence records. Warranty duration is not service quality; certificate evidence points are not a safety rating. Compatibility and installation limits still apply.
UL 1973Battery pack claim; verification pendingClaimedListed when checked
Listed as "UL1973" in the "Certification:" line of Deye's own product page, captured on September 25, 2026. A manufacturer claim: the page names no certificate number beside the line and no issuer directory record was read; the page does not say whether it covers the cell, the module or the system.
UL 9540AProduct / system scope unresolvedClaimedListed when checked
Listed as "UL9540A" in the "Certification:" line of Deye's own product page, captured on September 25, 2026. A manufacturer claim: the page names no certificate number beside the line and no issuer directory record was read; the page does not say whether it covers the cell, the module or the system.
Models: BOS-GL60, BOS-GH60
Standard as printed
UL 9540A
Edition as printed
Not printed
What it covers
Product / system scope unresolved
Type
A fire-test report (UL 9540A is a test method, not a listing)
For a permit
A fire test. Useful supporting evidence, but it does not replace UL 9540.
UN 38.3Battery pack claim; verification pendingClaimedListed when checked
Listed as "UN38.3" in the "Certification:" line of Deye's own product page, captured on September 25, 2026. A manufacturer claim: the page names no certificate number beside the line and no issuer directory record was read; the page does not say whether it covers the cell, the module or the system.
UL 9540Product / system scope unresolvedClaimedListed when checked
Listed as "UL9540" in the "Certification:" line of Deye's own product page, captured on September 25, 2026. A manufacturer claim: the page names no certificate number beside the line and no issuer directory record was read; the page does not say whether it covers the cell, the module or the system.
Models: BOS-GL60, BOS-GH60
Standard as printed
UL 9540
Edition as printed
Not printed
What it covers
Product / system scope unresolved
Type
A listing to the energy storage system standard
For a permit
Permit offices commonly ask for this listing; local rules vary.
UL 1973Product / system scope unresolvedClaimedListed when checked
Listed on the California Energy Commission Battery List (data unchanged since October 1, 2026; downloaded October 11, 2026) as NINGBO DEYE ESS TECHNOLOGY CO., LTD "BOS-GL60": UL 1973, certifying entity SGS, certificate date 2024-04-19, Ed. 2 : 2018, CEC listing date 2024-07-22. A state equipment list entry, not the certification body's own record.
CECProduct / system scope unresolvedClaimedListed when checked
Model BOS-GL60 listed on the California Energy Commission Battery List (data unchanged since October 1, 2026; downloaded October 11, 2026) under NINGBO DEYE ESS TECHNOLOGY CO., LTD, as "BOS-GL60", CEC listing date 2024-07-22. This is an equipment listing, not UL certification or complete-system approval.
Product / system scope unresolved. Listed on the California Energy Commission Battery List (data unchanged since October 1, 2026; downloaded October 11, 2026) as NINGBO DEYE ESS TECHNOLOGY CO., LTD "BOS-GL60": UL 1973, certifying entity SGS, certificate date 2024-04-19, Ed. 2 : 2018, CEC listing date 2024-07-22. A state equipment list entry, not the certification body's own record.
Product / system scope unresolved. Model BOS-GL60 listed on the California Energy Commission Battery List (data unchanged since October 1, 2026; downloaded October 11, 2026) under NINGBO DEYE ESS TECHNOLOGY CO., LTD, as "BOS-GL60", CEC listing date 2024-07-22. This is an equipment listing, not UL certification or complete-system approval.