Printed as "Peak Apparent Power (5s, off-grid) 7,200VA 12,000VA" in the Sol-Ark 5K-1P-N datasheet PS-00032 Rev 3, captured on September 25, 2026; the datasheet has a 5K column (120 V single phase) and an 8K column, and 7,200 VA is the 5K value. Stated in VA, not W.
Printed as "Nominal AC Voltage 120V Single Phase" in Sol-Ark PS-00032 Rev3 5K-1P-N DataSheet EN 18June2025, Data sheet p.1, Output Data (AC), 5K column. Revised on 1 October 2026: The data sheet prints "Nominal AC Voltage 120V Single Phase" in the 5K column; 425V is the top of the PV "Nominal Voltage Range 150 - 425V".
Printed as "Max Efficiency 97.6%" in the Sol-Ark 5K-1P-N datasheet PS-00032 Rev 3, captured on September 25, 2026, once for both columns. Manufacturer rating; no test conditions are given.
Location: Datasheet, Output Data (AC), "Max Efficiency" row
Documented
8 specs not documented yet: output voltage distortion, communications, pv input limit, transfer time, emp test evidence, maximum grid charging, parallel units, continuous output 240v single phaseHelp fill in ›
Printed as "Peak Apparent Power (5s, off-grid) 7,200VA 12,000VA" in the Sol-Ark 5K-1P-N datasheet PS-00032 Rev 3, captured on September 25, 2026; the datasheet has a 5K column (120 V single phase) and an 8K column, and 7,200 VA is the 5K value. Stated in VA, not W.
Printed as "Nominal AC Voltage 120V Single Phase" in Sol-Ark PS-00032 Rev3 5K-1P-N DataSheet EN 18June2025, Data sheet p.1, Output Data (AC), 5K column. Revised on 1 October 2026: The data sheet prints "Nominal AC Voltage 120V Single Phase" in the 5K column; 425V is the top of the PV "Nominal Voltage Range 150 - 425V".
Printed as "Max Efficiency 97.6%" in the Sol-Ark 5K-1P-N datasheet PS-00032 Rev 3, captured on September 25, 2026, once for both columns. Manufacturer rating; no test conditions are given.
Printed as "Output power will vary depending on grid type selection: 4,800W @ 120V and 127V" in Sol-Ark 5k-1p-n Installation and user manual, Sol-Ark 5K-1P-N installation and user manual, grid type and output power description. Revised on 1 October 2026: The 5K-1P-N manual prints 4,800W output at 120V and 127V, the same figure as the datasheet "Real Power, max continuous" row, so the manual becomes the primary citation and the kW value is labeled as a conversion.
Not printed for this model. Sol-Ark PS-00032 Rev3 5K-1P-N DataSheet EN 18June2025 prints "Real Power, max continuous 2 4,800W 8,000W". Revised on 1 October 2026: The sheet covers 5K-120V and 8K-230V; 8,000W is the 8K column at 240V, while the 5K column prints 4,800W at 120V single phase, so no 240V output is printed for this model.
Printed as "Max. Allowed PV Power (STC) 10,400W" in Sol-Ark PS-00032 Rev3 5K-1P-N DataSheet EN 18June2025, Sol-Ark PS-00032 Rev3 5K-1P-N DataSheet EN 18June2025, PDF page None, "Max. Allowed PV Power (STC)" row. Revised on 1 October 2026: The Sol-Ark datasheet prints 10,400 W for "Max. Allowed PV Power (STC)"; the stored value is that figure converted.
Read from Sol-Ark's published document at https://sol-ark.com/wp-content/uploads/2024/06/PS-00032_Rev3_5K-1P-N_DataSheet_EN_18June2025.pdf, from a document that names 5K-1P-N and no other model in this catalog. Printed value: "97.6%". Conditions as stated on that sheet. No value was taken from another model or from a name.
Read from Sol-Ark's published document at https://sol-ark.com/wp-content/uploads/2024/06/PS-00032_Rev3_5K-1P-N_DataSheet_EN_18June2025.pdf, from a document that names 5K-1P-N and no other model in this catalog. Printed value: "125V". Conditions as stated on that sheet. No value was taken from another model or from a name.
Printed as "BATTERY CABLES: 2/0 AWG THHN / Max Charge and Discharge limited to 120A" in the 5K-1P-N Installation Manual (MA-00015 Rev. 3), section 1.3, Wire Gauge Guide, captured on September 26, 2026.
Printed as "GRID Terminal 50A MAX, 50A passthrough, 8 AWG to 6 AWG conductor" in the 5K-1P-N Installation Manual (MA-00015 Rev. 3), section 1.3, captured on September 26, 2026.
Printed as "Battery Connection 40 in-lb 4.5 Nm" in the 5K-1P-N Installation Manual (MA-00015 Rev. 3), torque values application note, captured on September 26, 2026.
Printed as "LOAD Terminal 50A MAX, 50A passthrough, 8AWG to 6 AWG conductor" in the 5K-1P-N Installation Manual (MA-00015 Rev. 3), section 1.3, captured on September 26, 2026. 10 AWG is allowed for grid sell only.
Read from Sol-Ark's published document at https://sol-ark.com/wp-content/uploads/2024/06/PS-00032_Rev3_5K-1P-N_DataSheet_EN_18June2025.pdf, from a document that names 5K-1P-N and no other model in this catalog. Printed value: "-40~60°C, > 45°C Derating". Conditions as stated on that sheet. No value was taken from another model or from a name.
Archived copy of a document published by Sol-Ark. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email legal@chargedreviews.com.
Sol-Ark 5k-1p-n Installation and user manualOfficialSol-ArkOfficial instruction manual
Certificate & compliance claims (2)
UL 1741Manufacturer claim · equipment listingClaimedStatus unconfirmed
Sol-Ark prints "UL 1741" in a certification, standards or compliance row on PDF page 31 of https://sol-ark.com/wp-content/uploads/2024/06/MA-00015_Rev3_5K-1P-N_UserManual_v13_EN_16June2025.pdf, a document this catalog already attaches to 5K-1P-N; the value was located through a page that names 5K-1P-N and no other model in this catalog. This is a manufacturer statement only: no issuer listing, certificate number, edition, scope or validity was checked, and the printed row may cover further models in the same family.
Sol-Ark prints "IEEE 1547" in a certification, standards or compliance row on PDF page 31 of https://sol-ark.com/wp-content/uploads/2024/06/MA-00015_Rev3_5K-1P-N_UserManual_v13_EN_16June2025.pdf, a document this catalog already attaches to 5K-1P-N; the value was located through a page that names 5K-1P-N and no other model in this catalog. This is a manufacturer statement only: no issuer listing, certificate number, edition, scope or validity was checked, and the printed row may cover further models in the same family.
Archived copy of a document published by Sol-Ark. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email legal@chargedreviews.com.
Earlier revisions, archived captures and copies published by someone other than the manufacturer. Every one stays reachable.
Archived documents
Sol-Ark PS-00032 Rev3 5K-1P-N DataSheet EN 18June2025
Archived copy of a document published by Sol-Ark. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email legal@chargedreviews.com.
Archived copy of a document published by Sol-Ark. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email legal@chargedreviews.com.
The Evidence score uses the priorities you choose. It counts published documents, such as certificates and warranty terms, and it compares a documented figure with the best documented figure of the same kind. It does not count owner reviews, and it is not a verdict on product quality or on how many people have reviewed it. A low score can mean little is documented, or that a documented figure is below the best of its kind. Undisclosed data scores 0.
Missing for this product: Battery conversion efficiency needed.
Each input is scored against the best documented value for an inverter: warranty term and battery conversion efficiency against every published inverter, idle consumption (lower is better) against the inverters in the same output band, or against every published inverter when the output is not documented. A documented value always earns points; an undisclosed one earns 0 and is listed as missing. Researched products receive a score. Certificates earn points for the evidence itself. Size and weight do not affect scores.
CertificatesUL 1741 · IEEE 1547Claimed10.2 / 45.0
Manufacturer claim; issuer verification pending. Applies to the exact inverter.
60 against 1 W, the lowest documented for an inverter in the 3.5 to 7 kW output band (printed by the maker): Fronius Primo 3.8-1 208-240. The bar is a printed bound: less than 1 W, as printed.
Exact model and stated mode; no independent performance test implied.
Not documented, 0 points: Battery conversion efficiency.
Warranty term and battery conversion efficiency are compared with every published inverter; idle consumption with the inverters in the same 3.5 to 7 kW output band. · Method version 0.5
UL 1741Product / system scope unresolvedClaimedStatus unconfirmed
Sol-Ark prints "UL 1741" in a certification, standards or compliance row on PDF page 31 of https://sol-ark.com/wp-content/uploads/2024/06/MA-00015_Rev3_5K-1P-N_UserManual_v13_EN_16June2025.pdf, a document this catalog already attaches to 5K-1P-N; the value was located through a page that names 5K-1P-N and no other model in this catalog. This is a manufacturer statement only: no issuer listing, certificate number, edition, scope or validity was checked, and the printed row may cover further models in the same family.
IEEE 1547Product / system scope unresolvedClaimedStatus unconfirmed
Sol-Ark prints "IEEE 1547" in a certification, standards or compliance row on PDF page 31 of https://sol-ark.com/wp-content/uploads/2024/06/MA-00015_Rev3_5K-1P-N_UserManual_v13_EN_16June2025.pdf, a document this catalog already attaches to 5K-1P-N; the value was located through a page that names 5K-1P-N and no other model in this catalog. This is a manufacturer statement only: no issuer listing, certificate number, edition, scope or validity was checked, and the printed row may cover further models in the same family.
UL 1741Manufacturer claim · equipment listingClaimedStatus unconfirmed
Sol-Ark prints "UL 1741" in a certification, standards or compliance row on PDF page 31 of https://sol-ark.com/wp-content/uploads/2024/06/MA-00015_Rev3_5K-1P-N_UserManual_v13_EN_16June2025.pdf, a document this catalog already attaches to 5K-1P-N; the value was located through a page that names 5K-1P-N and no other model in this catalog. This is a manufacturer statement only: no issuer listing, certificate number, edition, scope or validity was checked, and the printed row may cover further models in the same family.
Sol-Ark prints "IEEE 1547" in a certification, standards or compliance row on PDF page 31 of https://sol-ark.com/wp-content/uploads/2024/06/MA-00015_Rev3_5K-1P-N_UserManual_v13_EN_16June2025.pdf, a document this catalog already attaches to 5K-1P-N; the value was located through a page that names 5K-1P-N and no other model in this catalog. This is a manufacturer statement only: no issuer listing, certificate number, edition, scope or validity was checked, and the printed row may cover further models in the same family.
No sourced accessories or replacement parts listed yet.
Model history
Model identity
Model
5K-1P-N
Manufacturer SKU unknown · US market
Observed
UL 1741: claimed
Product / system scope unresolved. Sol-Ark prints "UL 1741" in a certification, standards or compliance row on PDF page 31 of https://sol-ark.com/wp-content/uploads/2024/06/MA-00015_Rev3_5K-1P-N_UserManual_v13_EN_16June2025.pdf, a document this catalog already attaches to 5K-1P-N; the value was located through a page that names 5K-1P-N and no other model in this catalog. This is a manufacturer statement only: no issuer listing, certificate number, edition, scope or validity was checked, and the printed row may cover further models in the same family.
Product / system scope unresolved. Sol-Ark prints "IEEE 1547" in a certification, standards or compliance row on PDF page 31 of https://sol-ark.com/wp-content/uploads/2024/06/MA-00015_Rev3_5K-1P-N_UserManual_v13_EN_16June2025.pdf, a document this catalog already attaches to 5K-1P-N; the value was located through a page that names 5K-1P-N and no other model in this catalog. This is a manufacturer statement only: no issuer listing, certificate number, edition, scope or validity was checked, and the printed row may cover further models in the same family.