About brandOutBack Power's About page says the company has made battery-based power equipment since 2001, including off-grid inverter/chargers, grid-interactive inverter systems, MPPT charge controllers and energy storage. It says OutBack Power is now part of Energy Access Innovations (EAI). Its datasheets name OutBack Power Technologies, Inc. of Phoenix, Arizona.
conditions: Printed as "Models: GS8048A GS4048A" on OutBack's Radian A-Series datasheet #980-00076-01-001 REV C (03/2021), and the installation manual (900-0160-01-01 Rev C) says its instructions apply to models GS8048A and GS4048A only. OutBack publishes no separate stock keeping number; the model designation is recorded.
Printed as "delivers split-phase power (100/200 Vac to 120/240 Vac at 60 or 50 Hz)" in the Radian Series Inverter/Charger GS4048A GS8048A Installation Manual, 900-0160-01-01 Rev C, September 2022 (OutBack Power) (PDF page 6).
The unit must be connected to a permanent wiring system that is grounded according to the IEC 60364 TN standard.
Printed as "grounded according to the IEC 60364 TN standard" in the Radian Series Inverter/Charger GS4048A GS8048A Installation Manual, 900-0160-01-01 Rev C, September 2022 (OutBack Power) (PDF page 25).
Printed as "Weight (lb/kg): Unit: 125 / 56.7 | Shipping: 140 / 63.5" in the Weight (lb/kg) row of OutBack's Radian A-Series datasheet #980-00076-01-001 REV C (03/2021), the GS8048A column being the first value on each row. The unit weighs 125 lb / 56.7 kg; the shipping weight is 140 lb / 63.5 kg.
9000 VA for 30 min; 12000 VA for 5 s; 16970 VA for 100 ms
Printed as "Instantaneous Power (100ms)" 16970VA, "Surge Power (5 sec)" 12000VA and "Peak Power (30 min)" 9000VA in the GS8048A column of OutBack's Radian A-Series datasheet #980-00076-01-001 REV C (03/2021).
Where: Instantaneous Power, Surge Power and Peak Power rows, GS8048A column
Printed as "AC Output Voltage (Selectable): 120/240VAC (200 to 260VAC)" in the AC Output Voltage (Selectable) row of OutBack's Radian A-Series datasheet #980-00076-01-001 REV C (03/2021), the GS8048A column being the first value on each row.
Where: AC Output Voltage (Selectable) row, GS8048A column
Printed as "Continuous Battery Charge Output: 115ADC 57.5ADC" in the Continuous Battery Charge Output row of OutBack's Radian A-Series datasheet #980-00076-01-001 REV C (03/2021), the GS8048A column being the first value on each row. This is the inverter/charger's own battery charger output.
The minimum recommended clearance is 2 inches (5 cm) on all sides of the inverter.
Printed as "The minimum recommended clearance is 2 inches (5 cm) on all sides" in the Radian Series Inverter/Charger GS4048A GS8048A Installation Manual, 900-0160-01-01 Rev C, September 2022 (OutBack Power) (PDF page 17).
Where: PDF page 17, Location and Environmental Requirements
W 406 × H 711 × D 221 mm / W 16 × H 28 × D 8.7 in converted
Unit dimensions printed as "28 × 16 × 8.7 / 71.1 × 40.6 × 22.1" H × W × D in inches and centimeters in the GS8048A column of OutBack's Radian A-Series datasheet #980-00076-01-001 REV C (03/2021).
Where: Dimensions H × W × D (in/cm) row, GS8048A column
Printed as "Typical Efficiency: 93% 93%" in the Typical Efficiency row of OutBack's Radian A-Series datasheet #980-00076-01-001 REV C (03/2021), the GS8048A column being the first value on each row.
Printed as "AC Output Frequency (Selectable): 60Hz (50Hz)" in the AC Output Frequency (Selectable) row of OutBack's Radian A-Series datasheet #980-00076-01-001 REV C (03/2021), the GS8048A column being the first value on each row. 50 Hz is the selectable alternative.
Where: AC Output Frequency (Selectable) row, GS8048A column
It can provide backup power, sell power back to the utility grid, or provide complete stand-alone off-grid service
Printed as "sell power back to the utility grid, or provide complete stand-alone off-grid service" in the Radian Series Inverter/Charger GS4048A GS8048A Installation Manual, 900-0160-01-01 Rev C, September 2022 (OutBack Power) (PDF page 6).
Split-phase power (100/200 Vac to 120/240 Vac at 60 or 50 Hz)
Printed as "delivers split-phase power (100/200 Vac to 120/240 Vac at 60 or 50 Hz)" in the Radian Series Inverter/Charger GS4048A GS8048A Installation Manual, 900-0160-01-01 Rev C, September 2022 (OutBack Power) (PDF page 6).
Branch-rated circuit breakers of up to 50 Aac maximum size
Printed as "branch-rated circuit breakers of up to 50 Aac maximum size" in the Radian Series Inverter/Charger GS4048A GS8048A Installation Manual, 900-0160-01-01 Rev C, September 2022 (OutBack Power) (PDF page 29). Printed as "The AC input and output must be protected with branch-rated circuit breakers of up to 50 Aac maximum size".
Printed as "These inverters carry an Ingress Protection (IP) rating of 20" in the Radian Series Inverter/Charger GS4048A GS8048A Installation Manual, 900-0160-01-01 Rev C, September 2022 (OutBack Power) (PDF page 17).
Where: PDF page 17, Location and Environmental Requirements
Branch-rated circuit breakers of up to 50 Aac maximum size
Printed as "branch-rated circuit breakers of up to 50 Aac maximum size" in the Radian Series Inverter/Charger GS4048A GS8048A Installation Manual, 900-0160-01-01 Rev C, September 2022 (OutBack Power) (PDF page 29). Printed as "The AC input and output must be protected with branch-rated circuit breakers of up to 50 Aac maximum size".
Printed as "Continuous Power Rating (@ 25°C): 8000VA 4000VA" in the Continuous Power Rating (@ 25°C) row of OutBack's Radian A-Series datasheet #980-00076-01-001 REV C (03/2021), the GS8048A column being the first value on each row. The rating is at 25 °C.
Where: Continuous Power Rating (@ 25°C) row, GS8048A column
2/0 AWG (0.109 in²) or 70 mm² (minimum, per breaker)
Printed as "GS8048A 104 2/0 AWG (0.109 in²) or 70 mm² 175 Adc/AIC 10kA" in the Radian Series Inverter/Charger GS4048A GS8048A Installation Manual, 900-0160-01-01 Rev C, September 2022 (OutBack Power) (PDF page 27). The column is headed "Conductor Size (Minimum, per breaker)".
Where: PDF page 27, Table 4 DC Conductor Size and Torque Requirements, GS8048A row, Conductor Size column
Two sets of AC input terminals; two AC sources, such as a gas or diesel generator and the utility grid, can be connected
Printed as "The Radian inverter has two sets of AC input terminals" and "such as a gas or diesel generator and the utility grid, can be connected" in the Radian Series Inverter/Charger GS4048A GS8048A Installation Manual, 900-0160-01-01 Rev C, September 2022 (OutBack Power) (PDF page 9). The page adds that the inverter can only accept one source at a time.
Printed as "Nominal DC Input Voltage: 48VDC 48VDC" in the Nominal DC Input Voltage row of OutBack's Radian A-Series datasheet #980-00076-01-001 REV C (03/2021), the GS8048A column being the first value on each row.
Where: Nominal DC Input Voltage row, GS8048A column
#8 AWG (0.013 in2) or 10 mm2 (minimum recommended)
Printed as "The minimum recommended wire size is #8 AWG (0.013 in2) or 10 mm2" in the Radian Series Inverter/Charger GS4048A GS8048A Installation Manual, 900-0160-01-01 Rev C, September 2022 (OutBack Power) (PDF page 29). The same paragraph says the largest size that can be used with the terminals is #6 AWG (0.021 in2) or 16 mm2.
Printed as "GS8048A 104 2/0 AWG (0.109 in²) or 70 mm² 175 Adc/AIC 10kA" and "The modular construction of the GS8048A requires the use of two DC circuit breakers" in the Radian Series Inverter/Charger GS4048A GS8048A Installation Manual, 900-0160-01-01 Rev C, September 2022 (OutBack Power) (PDF page 27). PDF page 26 says to install a circuit breaker or overcurrent device on each DC positive (+) conductor.
Where: PDF page 27, Table 4 DC Conductor Size and Torque Requirements, GS8048A row, Breaker Size column
Printed as "Idle Power: Invert mode, no load: 34W | Search: 10W" in the Idle Power row of OutBack's Radian A-Series datasheet #980-00076-01-001 REV C (03/2021), the GS8048A column being the first value on each row. The invert-mode, no-load figure is recorded; search mode draws 10 W.
Printed as "up to ten units in parallel" in the feature list of OutBack's Radian A-Series datasheet #980-00076-01-001 REV C (03/2021), which covers the GS8048A and GS4048A.
#8 AWG (0.013 in2) or 10 mm2 (minimum recommended)
Printed as "The minimum recommended wire size is #8 AWG (0.013 in2) or 10 mm2" in the Radian Series Inverter/Charger GS4048A GS8048A Installation Manual, 900-0160-01-01 Rev C, September 2022 (OutBack Power) (PDF page 29). The statement covers the whole nine-position AC terminal block; the largest size that can be used is #6 AWG (0.021 in2) or 16 mm2.
ETL listed to UL 1741 SA; CE; CSA C22.2 No. 107.1; UL 778 Annex F; IEC 62109-1 ETL; RoHS compliant per directive 2011/65/EU; FCC Class B; IEEE 1574.1; EN61000-6-1; EN61000-6-3; EN61000-3-2; EN61000-3-3
Printed in the Listings/Certifications row of OutBack's Radian A-Series datasheet #980-00076-01-001 REV C (03/2021) (GS8048A column). Manufacturer claims; no issuer record was checked.
Printed as "8.0kVA 8.0kW" in the GS8048A power factor chart of OutBack's Radian A-Series datasheet #980-00076-01-001 REV C (03/2021), the industry standard unity power factor case; the Continuous Power Rating row prints 8000VA at 25 °C.
The Radian inverter must be wall-mounted in an upright position
Printed as "The Radian inverter must be wall-mounted in an upright position" in the Radian Series Inverter/Charger GS4048A GS8048A Installation Manual, 900-0160-01-01 Rev C, September 2022 (OutBack Power) (PDF page 17). The page adds that the inverter is not approved for mounting in any other position or orientation.
Where: PDF page 17, Location and Environmental Requirements
Printed as "Advanced Battery Charging: Flooded, gel, AGM, lithium-ion and flow chemistry" in the Advanced Battery Charging row of OutBack's Radian A-Series datasheet #980-00076-01-001 REV C (03/2021), the GS8048A column being the first value on each row.
Printed as "Continuous AC Output Current (@ 25°C): 33.3AAC @ 240VAC" in the Continuous AC Output Current (@ 25°C) row of OutBack's Radian A-Series datasheet #980-00076-01-001 REV C (03/2021), the GS8048A column being the first value on each row. The current is at 240 VAC and 25 °C.
Where: Continuous AC Output Current (@ 25°C) row, GS8048A column
Printed as "Inverter DC Terminals 60 in-lb (6.9 Nm)" in the Radian Series Inverter/Charger GS4048A GS8048A Installation Manual, 900-0160-01-01 Rev C, September 2022 (OutBack Power) (PDF page 27). For battery terminals the table says to see the battery manufacturer’s recommendations.
Where: PDF page 27, Table 4, Inverter DC Terminals row
Printed as "DC Input Voltage Range: 40 to 64VDC 40 to 64VDC" in the DC Input Voltage Range row of OutBack's Radian A-Series datasheet #980-00076-01-001 REV C (03/2021), the GS8048A column being the first value on each row.
Printed as "Temperature Range: Rated: –20 to 50°C | Maximum: –40 to 60°C" in the Temperature Range row of OutBack's Radian A-Series datasheet #980-00076-01-001 REV C (03/2021), the GS8048A column being the first value on each row. The rated range is recorded; the maximum range is -40 to 60 °C.
Printed as "CEC Weighted Efficiency: 92.5% 92.5%" in the CEC Weighted Efficiency row of OutBack's Radian A-Series datasheet #980-00076-01-001 REV C (03/2021), the GS8048A column being the first value on each row.
OutBack Power does not bond these conductors (neutral and ground) within the inverter. Make sure that no more than one bond is present in the AC system at any time.
Printed as "OutBack Power does not bond these conductors within the inverter" and "Make sure that no more than one bond is present in the AC system" in the Radian Series Inverter/Charger GS4048A GS8048A Installation Manual, 900-0160-01-01 Rev C, September 2022 (OutBack Power) (PDF page 25).
Split-phase power (100/200 Vac to 120/240 Vac at 60 or 50 Hz)
Warranty
5 years
Size
63.8 L* (Calculated from published dimensions)W: 406 × H: 711 × D: 221 mm / W: 16 × H: 28 × D: 8.7 inWeight56.7 kg / 125 lb
Evidence score
19/100Missing details85% documented
The Evidence score uses the priorities you choose. It counts published documents, such as certificates and warranty terms, and it compares a documented figure with the best documented figure of the same kind. It does not count owner reviews, and it is not a verdict on product quality or on how many people have reviewed it. A low score can mean little is documented, or that a documented figure is below the best of its kind. Undisclosed data scores 0.
Missing details. This number counts only the evidence recorded so far. The source review for this product is not finished, or the maker has not disclosed enough, so the number can only go up.
Missing for this product: Battery conversion efficiency needed.
Each input is scored against the best documented value for an inverter: warranty term and battery conversion efficiency against every published inverter, idle consumption (lower is better) against the inverters in the same output band, or against every published inverter when the output is not documented. A documented value always earns points; an undisclosed one earns 0 and is listed as missing. Researched products receive a score. Certificates earn points for the evidence itself. Size and weight do not affect scores.
CertificatesUL 1741 SA · CECClaimed12.6 / 45.0
Manufacturer claim; issuer verification pending. Applies to the exact inverter.
5 of 25 years, the best documented for an inverter (printed by the maker): APsystems DS3
Printed as "Standard 5 year, extended 10 year available" in the Warranty row of OutBack's Radian A-Series datasheet #980-00076-01-001 REV C (03/2021). The warranty statement itself was not read for this record.
34 against 1 W, the lowest documented for an inverter in the 7 to 15 kW output band (printed by the maker): Fronius Primo 11.4-1 208-240. The bar is a printed bound: less than 1 W, as printed.
Printed as "Idle Power: Invert mode, no load: 34W | Search: 10W" in the Idle Power row of OutBack's Radian A-Series datasheet #980-00076-01-001 REV C (03/2021), the GS8048A column being the first value on each row. The invert-mode, no-load figure is recorded; search mode draws 10 W.
Research pending, 0 points: Battery conversion efficiency.
Warranty term and battery conversion efficiency are compared with every published inverter; idle consumption with the inverters in the same 7 to 15 kW output band. · Method version 0.5
What this shows: what each record says and how far it reaches. It does not mean the product is approved.
StandardEvidenceStatusSource
UL 1741 SAauthority listing reportedlisted as of snapshot[5]
Scope
equipment listing
Covered models
GS8048A
Limitations
Listed on the California Energy Commission Grid Support Battery Inverter List (data unchanged since October 1, 2026; downloaded October 11, 2026) as OutBack Power "GS8048A {240V}": UL 1741 SA, certifying entity Intertek, certificate date 2017-11-07, CEC listing date 2017-12-15. A state equipment list entry, not the certification body's own record.
CECauthority listing reportedlisted as of snapshot[5]
Scope
equipment listing
Covered models
GS8048A
Limitations
Model GS8048A listed on the California Energy Commission Grid Support Battery Inverter List (data unchanged since October 1, 2026; downloaded October 11, 2026) under OutBack Power, as "GS8048A {240V}", CEC listing date 2017-12-15. This is an equipment listing, not UL certification or complete-system approval.
Printed as "Standard 5 year, extended 10 year available" in the Warranty row of OutBack's Radian A-Series datasheet #980-00076-01-001 REV C (03/2021). The warranty statement itself was not read for this record.
OutBack Power's installation manual for the Radian GS8048A and GS4048A, served from OutBack's own document archive (old.outbackpower.com) and linked as the installation manual from Signature Solar's Radian listing. It names the models it applies to; it prints no electrical specification table, so the figures on this record come from the Radian A-Series datasheet. Manufacturer claims, not independent tests.
Archived copies
Archived copy of a document published by OutBack Power. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email [email protected].
OutBack Power's datasheet for the Radian GS8048A and GS4048A inverter/chargers, dated 03/2021, linked from the Radian Series product page. The GS4048A is the inverter/charger inside FPR-4048A-300AFCI; its figures are read from the GS4048A column and describe the inverter, not the assembled pre-wired system.
Archived copies
Archived copy of a document published by OutBack Power Technologies, Inc.. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email [email protected].
Archived copy of a document published by OutBack Power Technologies, Inc.. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email [email protected].
Radian Series Inverter/Charger GS4048A GS8048A Installation Manual, 900-0160-01-01 Rev C, September 2022 (OutBack Power)
Archived copy of a document published by OutBack Power. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email [email protected].
No sourced accessories or replacement parts listed yet.
Model history
Model identity
Model
GS8048A
Manufacturer SKU GS8048A · US market
Observed Oct 11, 2026
UL 1741 SA: claimed
Product / system scope unresolved. Listed on the California Energy Commission Grid Support Battery Inverter List (data unchanged since October 1, 2026; downloaded October 11, 2026) as OutBack Power "GS8048A {240V}": UL 1741 SA, certifying entity Intertek, certificate date 2017-11-07, CEC listing date 2017-12-15. A state equipment list entry, not the certification body's own record.
Product / system scope unresolved. Model GS8048A listed on the California Energy Commission Grid Support Battery Inverter List (data unchanged since October 1, 2026; downloaded October 11, 2026) under OutBack Power, as "GS8048A {240V}", CEC listing date 2017-12-15. This is an equipment listing, not UL certification or complete-system approval.