About brandOutBack Power's About page says the company has made battery-based power equipment since 2001, including off-grid inverter/chargers, grid-interactive inverter systems, MPPT charge controllers and energy storage. It says OutBack Power is now part of Energy Access Innovations (EAI). Its datasheets name OutBack Power Technologies, Inc. of Phoenix, Arizona.
SKU detail
locator: FLEXpower Radian Specifications table, first model row and Details header
conditions: OutBack's model number, printed on the FLEXpower Radian datasheet #980-00075-01-001 REV B with description "FLEXpower Radian AFCI", inverter GS4048A, load center GSLC-PV1-300VDC and charge controller FLEXmax 100 AFCI.
Assembled system weight printed as "199 / 91" lb/kg in the FPR-4048A-300AFCI column (first of five columns). Shipping weight is 218 lb / 98.6 kg. No battery is included.
The FPR-4048A-300AFCI row lists "(1) FLEXmax 100 AFCI" as its charge controller, and OutBack describes the FLEXmax 100 AFCI as an MPPT charge controller. The number of tracking inputs per controller is not printed; one controller is recorded as one MPPT.
4500 VA for 30 min; 6000 VA for 5 s; 8500 VA for 100 ms
Printed as "Instantaneous Power (100ms)" 8500VA, "Surge Power (5 sec)" 6000VA and "Peak Power (30 min)" 4500VA. Read from the GS4048A column (the second value on each row) of OutBack's Radian A-Series datasheet #980-00076-01-001 REV C (03/2021). The FLEXpower Radian datasheet names the GS4048A as the inverter/charger inside FPR-4048A-300AFCI; the figure is the inverter's, not a measurement of the assembled system.
Where: Instantaneous Power, Surge Power and Peak Power rows, GS4048A column
Printed as "AC Output Voltage (Selectable): 120/240VAC (200 to 260VAC)". Read from the GS4048A column (the second value on each row) of OutBack's Radian A-Series datasheet #980-00076-01-001 REV C (03/2021). The FLEXpower Radian datasheet names the GS4048A as the inverter/charger inside FPR-4048A-300AFCI; the figure is the inverter's, not a measurement of the assembled system.
The inverter/charger's own battery charger, printed as "Continuous Battery Charge Output" 57.5ADC. Solar charging through the included FLEXmax 100 AFCI is separate and is not added here. Read from the GS4048A column (the second value on each row) of OutBack's Radian A-Series datasheet #980-00076-01-001 REV C (03/2021). The FLEXpower Radian datasheet names the GS4048A as the inverter/charger inside FPR-4048A-300AFCI; the figure is the inverter's, not a measurement of the assembled system.
W 851 × H 1,194 × D 249 mm / W 33.5 × H 47.01 × D 9.8 in converted
Finished (assembled) dimensions printed as "47.0 × 33.5 × 9.84 / 119.4 × 85.1 × 24.9" H × W × D in inches and centimeters; the centimeter figures are recorded in millimeters. All five models print the same dimensions.
Printed as "Typical Efficiency: 93%". Read from the GS4048A column (the second value on each row) of OutBack's Radian A-Series datasheet #980-00076-01-001 REV C (03/2021). The FLEXpower Radian datasheet names the GS4048A as the inverter/charger inside FPR-4048A-300AFCI; the figure is the inverter's, not a measurement of the assembled system.
Maximum STC nameplate array for the one FLEXmax 100 AFCI on a 48 V battery, printed as "3500W / 5250W / 7000W" for 24, 36 and 48 V, with charging output limited to 100 A at battery voltage. This is a controller rating, not a system test.
Where: FLEXmax 100 AFCI Specifications, Maximum Array (STC Nameplate)
Printed for the FLEXmax 100 AFCI as "Maximum PV System Voltage 300VDC", with an operating input range of 30 to 290 VDC. The FPR-4048A-300AFCI row lists one FLEXmax 100 AFCI and the load center GSLC-PV1-300VDC.
Where: FLEXmax 100 AFCI Specifications, Maximum PV System Voltage
Printed as 4000VA at 25 °C. Read from the GS4048A column (the second value on each row) of OutBack's Radian A-Series datasheet #980-00076-01-001 REV C (03/2021). The FLEXpower Radian datasheet names the GS4048A as the inverter/charger inside FPR-4048A-300AFCI; the figure is the inverter's, not a measurement of the assembled system.
Where: Continuous Power Rating row, GS4048A column
Nominal battery voltage, printed as "Nominal DC Input Voltage: 48VDC". Read from the GS4048A column (the second value on each row) of OutBack's Radian A-Series datasheet #980-00076-01-001 REV C (03/2021). The FLEXpower Radian datasheet names the GS4048A as the inverter/charger inside FPR-4048A-300AFCI; the figure is the inverter's, not a measurement of the assembled system.
Where: Nominal DC Input Voltage row, GS4048A column
#6 AWG THHN copper, or larger, rated to 75°C (minimum), unless local code requires otherwise
Printed as "OutBack recommends that conductors be #6 AWG THHN copper, or larger, rated to 75°C (minimum) unless local code requires otherwise." under the AC wire table of OutBack's FP Radian Quick Start Guide (900-0226-01-00 REV C); the same table covers the GRID IN, GEN IN and AC OUT bus bars. The guide prints this once for every FLEXpower Radian model; it is a general instruction, not a figure printed for FPR-4048A-300AFCI alone. Table layout checked on the rendered page.
Where: PDF page 2, Installation, note under the AC Wire Sizes and Torque Values table
Printed as "AWG In-lb #14 to #10 20 #8 25 #6 to #4 35 #3 35 #2 40 #1 50 1/0 50" with the newton meter column "Nm 2.3 2.8 4.0 4.0 4.5 5.6 5.6" in the AC Wire Sizes and Torque Values table of OutBack's FP Radian Quick Start Guide (900-0226-01-00 REV C); torque depends on the wire size used. The guide prints this once for every FLEXpower Radian model; it is a general instruction, not a figure printed for FPR-4048A-300AFCI alone. Table layout checked on the rendered page.
Where: PDF page 2, Installation, AC Wire Sizes and Torque Values table
Printed as "Invert mode, no load: 34W | Search: 10W"; the invert-mode figure is recorded, and search mode draws 10 W. Read from the GS4048A column (the second value on each row) of OutBack's Radian A-Series datasheet #980-00076-01-001 REV C (03/2021). The FLEXpower Radian datasheet names the GS4048A as the inverter/charger inside FPR-4048A-300AFCI; the figure is the inverter's, not a measurement of the assembled system.
#6 AWG THHN copper, or larger, rated to 75°C (minimum), unless local code requires otherwise
Printed as "OutBack recommends that conductors be #6 AWG THHN copper, or larger, rated to 75°C (minimum) unless local code requires otherwise." under the AC wire table of OutBack's FP Radian Quick Start Guide (900-0226-01-00 REV C); the same table covers the GRID IN, GEN IN and AC OUT bus bars. The guide prints this once for every FLEXpower Radian model; it is a general instruction, not a figure printed for FPR-4048A-300AFCI alone. Table layout checked on the rendered page.
Where: PDF page 2, Installation, note under the AC Wire Sizes and Torque Values table
GS4048A inverter/charger: ETL listed to UL 1741 SA, CE, CSA C22.2 No. 107.1, UL 778 Annex F, IEC 62109-1 ETL, RoHS compliant per directive 2011/65/EU, FCC Class B, IEEE 1574.1, EN61000-6-1, EN61000-6-3, EN61000-3-2, EN61000-3-3; FLEXmax 100 AFCI charge controller: UL 1741, CSA C22.2 No. 107.1, IEC 62109-1
Manufacturer claims recorded exactly as printed for two components of FPR-4048A-300AFCI. The FLEXpower Radian datasheet prints no listing for the assembled system; the product page says "Components carry all of the necessary UL certifications". No certificate or issuer record was read.
Printed as "Continuous Power Rating (@ 25°C)" 4000VA for the GS4048A. The datasheet states that OutBack rates power at unity power factor ("At 1.0PF (unity), all power is used. This is the industry standard used by OutBack Power"), so 4000 VA is recorded as 4 kW; the FLEXpower Radian datasheet calls this the 4kW system. Read from the GS4048A column (the second value on each row) of OutBack's Radian A-Series datasheet #980-00076-01-001 REV C (03/2021). The FLEXpower Radian datasheet names the GS4048A as the inverter/charger inside FPR-4048A-300AFCI; the figure is the inverter's, not a measurement of the assembled system.
Wall mounted: wall bracket secured with all 6 mounting screws, mounting holes centered on the wall studs; the mounting surface must handle 3 times the total weight of all components
Printed as "Ensure the mounting surface is strong enough to handle 3 times the total weight of all the components." and "Attach the wall bracket. Center the mounting holes on the wall studs. Use all 6 mounting screws to secure the bracket." in OutBack's FP Radian Quick Start Guide (900-0226-01-00 REV C). The guide prints this once for every FLEXpower Radian model; it is a general instruction, not a figure printed for FPR-4048A-300AFCI alone. Table layout checked on the rendered page.
Printed as "16.7AAC" at 25 °C; the voltage is printed only in the GS8048A column ("@ 240VAC"). Read from the GS4048A column (the second value on each row) of OutBack's Radian A-Series datasheet #980-00076-01-001 REV C (03/2021). The FLEXpower Radian datasheet names the GS4048A as the inverter/charger inside FPR-4048A-300AFCI; the figure is the inverter's, not a measurement of the assembled system.
Where: Continuous AC Output Current row, GS4048A column
Printed as "DC Input Voltage Range: 40 to 64VDC". Read from the GS4048A column (the second value on each row) of OutBack's Radian A-Series datasheet #980-00076-01-001 REV C (03/2021). The FLEXpower Radian datasheet names the GS4048A as the inverter/charger inside FPR-4048A-300AFCI; the figure is the inverter's, not a measurement of the assembled system.
Printed as "Rated: –20 to 50°C | Maximum: –40 to 60°C"; the rated range is recorded. Read from the GS4048A column (the second value on each row) of OutBack's Radian A-Series datasheet #980-00076-01-001 REV C (03/2021). The FLEXpower Radian datasheet names the GS4048A as the inverter/charger inside FPR-4048A-300AFCI; the figure is the inverter's, not a measurement of the assembled system.
Printed as "CEC Weighted Efficiency: 92.5%". Read from the GS4048A column (the second value on each row) of OutBack's Radian A-Series datasheet #980-00076-01-001 REV C (03/2021). The FLEXpower Radian datasheet names the GS4048A as the inverter/charger inside FPR-4048A-300AFCI; the figure is the inverter's, not a measurement of the assembled system.
253.01 L* (Calculated from published dimensions)W: 851 × H: 1,194 × D: 249 mm / W: 33.5 × H: 47.01 × D: 9.8 inWeight91 kg / 200 lb
Evidence score
6/100Missing details40% documented
The Evidence score uses the priorities you choose. It counts published documents, such as certificates and warranty terms, and it compares a documented figure with the best documented figure of the same kind. It does not count owner reviews, and it is not a verdict on product quality or on how many people have reviewed it. A low score can mean little is documented, or that a documented figure is below the best of its kind. Undisclosed data scores 0.
Missing details. This number counts only the evidence recorded so far. The source review for this product is not finished, or the maker has not disclosed enough, so the number can only go up.
Missing for this product: Certificate evidence needed; Battery conversion efficiency needed.
Each input is scored against the best documented value for an inverter: warranty term and battery conversion efficiency against every published inverter, idle consumption (lower is better) against the inverters in the same output band, or against every published inverter when the output is not documented. A documented value always earns points; an undisclosed one earns 0 and is listed as missing. Researched products receive a score. Certificates earn points for the evidence itself. Size and weight do not affect scores.
Warranty term5 years6.0 / 30.0
5 of 25 years, the best documented for an inverter (printed by the maker): APsystems DS3
Five-year limited warranty against defects in materials and workmanship and two-year limited warranty against fan failure. The statement lists "USA factory pre-wired FLEXpower systems incorporating the above inverters" among the covered products. The term starts at commissioning or first activation, or 6 months after factory shipment, whichever is earlier. The Radian datasheet prints "Standard 5 year, extended 10 year available" for the GS4048A; the terms of the extension were not read.
34 against 1 W, the lowest documented for an inverter in the 3.5 to 7 kW output band (printed by the maker): Fronius Primo 3.8-1 208-240. The bar is a printed bound: less than 1 W, as printed.
Printed as "Invert mode, no load: 34W | Search: 10W"; the invert-mode figure is recorded, and search mode draws 10 W. Read from the GS4048A column (the second value on each row) of OutBack's Radian A-Series datasheet #980-00076-01-001 REV C (03/2021). The FLEXpower Radian datasheet names the GS4048A as the inverter/charger inside FPR-4048A-300AFCI; the figure is the inverter's, not a measurement of the assembled system.
Research pending, 0 points: Certificates, Battery conversion efficiency.
Warranty term and battery conversion efficiency are compared with every published inverter; idle consumption with the inverters in the same 3.5 to 7 kW output band. · Method version 0.5
What this shows: what each record says and how far it reaches. It does not mean the product is approved.
StandardEvidenceStatusSource
CSA C22.2 No. 107.1manufacturer claimpresent at observation[2]
Scope
equipment listing
Covered models
FLEXmax 100 AFCI
Limitations
Listed by OutBack Power for the FLEXmax 100 AFCI charge controller, one of which is included in FPR-4048A-300AFCI, on the FLEXmax 100 AFCI datasheet #980-00078-01-00 REV A (08/2019), Certifications row. It is a claim for that component, not a listing of the assembled pre-wired system. No certificate number, certification body or issuer record was read. Recorded exactly as printed.
IEC 62109-1manufacturer claimpresent at observation[2]
Scope
equipment listing
Covered models
FLEXmax 100 AFCI
Limitations
Listed by OutBack Power for the FLEXmax 100 AFCI charge controller, one of which is included in FPR-4048A-300AFCI, on the FLEXmax 100 AFCI datasheet #980-00078-01-00 REV A (08/2019), Certifications row. It is a claim for that component, not a listing of the assembled pre-wired system. No certificate number, certification body or issuer record was read. Recorded exactly as printed.
UL 1741manufacturer claimpresent at observation[2]
Scope
equipment listing
Covered models
FLEXmax 100 AFCI
Limitations
Listed by OutBack Power for the FLEXmax 100 AFCI charge controller, one of which is included in FPR-4048A-300AFCI, on the FLEXmax 100 AFCI datasheet #980-00078-01-00 REV A (08/2019), Certifications row. It is a claim for that component, not a listing of the assembled pre-wired system. No certificate number, certification body or issuer record was read. Recorded exactly as printed.
CSA C22.2 No. 107.1manufacturer claimpresent at observation[3]
Scope
equipment listing
Covered models
GS4048A
Limitations
Listed by OutBack Power for the Radian GS4048A inverter/charger, the inverter inside FPR-4048A-300AFCI, on the Radian A-Series datasheet #980-00076-01-001 REV C (03/2021), Listings/Certifications row. It is a claim for that component, not a listing of the assembled pre-wired system. No certificate number, file number or issuer record was read. Recorded exactly as printed.
EN61000-3-2manufacturer claimpresent at observation[3]
Scope
equipment listing
Covered models
GS4048A
Limitations
Listed by OutBack Power for the Radian GS4048A inverter/charger, the inverter inside FPR-4048A-300AFCI, on the Radian A-Series datasheet #980-00076-01-001 REV C (03/2021), Listings/Certifications row. It is a claim for that component, not a listing of the assembled pre-wired system. No certificate number, file number or issuer record was read. Recorded exactly as printed.
EN61000-3-3manufacturer claimpresent at observation[3]
Scope
equipment listing
Covered models
GS4048A
Limitations
Listed by OutBack Power for the Radian GS4048A inverter/charger, the inverter inside FPR-4048A-300AFCI, on the Radian A-Series datasheet #980-00076-01-001 REV C (03/2021), Listings/Certifications row. It is a claim for that component, not a listing of the assembled pre-wired system. No certificate number, file number or issuer record was read. Recorded exactly as printed.
EN61000-6-1manufacturer claimpresent at observation[3]
Scope
equipment listing
Covered models
GS4048A
Limitations
Listed by OutBack Power for the Radian GS4048A inverter/charger, the inverter inside FPR-4048A-300AFCI, on the Radian A-Series datasheet #980-00076-01-001 REV C (03/2021), Listings/Certifications row. It is a claim for that component, not a listing of the assembled pre-wired system. No certificate number, file number or issuer record was read. Recorded exactly as printed.
EN61000-6-3manufacturer claimpresent at observation[3]
Scope
equipment listing
Covered models
GS4048A
Limitations
Listed by OutBack Power for the Radian GS4048A inverter/charger, the inverter inside FPR-4048A-300AFCI, on the Radian A-Series datasheet #980-00076-01-001 REV C (03/2021), Listings/Certifications row. It is a claim for that component, not a listing of the assembled pre-wired system. No certificate number, file number or issuer record was read. Recorded exactly as printed.
FCC Class Bmanufacturer claimpresent at observation[3]
Scope
equipment listing
Covered models
GS4048A
Limitations
Listed by OutBack Power for the Radian GS4048A inverter/charger, the inverter inside FPR-4048A-300AFCI, on the Radian A-Series datasheet #980-00076-01-001 REV C (03/2021), Listings/Certifications row. It is a claim for that component, not a listing of the assembled pre-wired system. No certificate number, file number or issuer record was read. Recorded exactly as printed.
IEC 62109-1manufacturer claimpresent at observation[3]
Scope
equipment listing
Covered models
GS4048A
Limitations
Listed by OutBack Power for the Radian GS4048A inverter/charger, the inverter inside FPR-4048A-300AFCI, on the Radian A-Series datasheet #980-00076-01-001 REV C (03/2021), Listings/Certifications row, printed as "IEC 62109-1 ETL". It is a claim for that component, not a listing of the assembled pre-wired system. No certificate number, file number or issuer record was read. Recorded exactly as printed.
IEEE 1574.1manufacturer claimpresent at observation[3]
Scope
equipment listing
Covered models
GS4048A
Limitations
Listed by OutBack Power for the Radian GS4048A inverter/charger, the inverter inside FPR-4048A-300AFCI, on the Radian A-Series datasheet #980-00076-01-001 REV C (03/2021), Listings/Certifications row. It is a claim for that component, not a listing of the assembled pre-wired system. No certificate number, file number or issuer record was read. Recorded exactly as printed.
UL 1741 SAmanufacturer claimpresent at observation[3]
Scope
equipment listing
Covered models
GS4048A
Limitations
Listed by OutBack Power for the Radian GS4048A inverter/charger, the inverter inside FPR-4048A-300AFCI, on the Radian A-Series datasheet #980-00076-01-001 REV C (03/2021), Listings/Certifications row, printed as "ETL listed to UL 1741 SA". It is a claim for that component, not a listing of the assembled pre-wired system. No certificate number, file number or issuer record was read. Recorded exactly as printed.
UL 778 Annex Fmanufacturer claimpresent at observation[3]
Scope
equipment listing
Covered models
GS4048A
Limitations
Listed by OutBack Power for the Radian GS4048A inverter/charger, the inverter inside FPR-4048A-300AFCI, on the Radian A-Series datasheet #980-00076-01-001 REV C (03/2021), Listings/Certifications row. It is a claim for that component, not a listing of the assembled pre-wired system. No certificate number, file number or issuer record was read. Recorded exactly as printed.
Five-year limited warranty against defects in materials and workmanship and two-year limited warranty against fan failure. The statement lists "USA factory pre-wired FLEXpower systems incorporating the above inverters" among the covered products. The term starts at commissioning or first activation, or 6 months after factory shipment, whichever is earlier. The Radian datasheet prints "Standard 5 year, extended 10 year available" for the GS4048A; the terms of the extension were not read.
Where: Limited Warranty, first section; Radian A-Series datasheet, Warranty row
Location: PDF page 1 (Quick Start Guide, FP Radian, 900-0226-01-00 REV C); PDF page 2 (Installation)
Retrieved Oct 1, 2026
OutBack Power's own quick start guide for the FLEXpower Radian (FP Radian), linked from OutBack's FLEXpower Radian product page as the Quick Start Guide for FPR-8048A-300VDC, FPR-8048A-01, FPR-4048A-300VDC and FPR-4048A-01, captured 1 October 2026; revision 900-0226-01-00 REV C (2018) as printed. A 4-page quick start guide, not the full installation manual, which it refers to; it prints general installation instructions for every FP Radian model. Manufacturer instructions, not independent tests.
Archived copies
Archived copy of a document published by OutBack Power. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email [email protected].
UL 1741 SAManufacturer claim · equipment listingClaimedListed when checked
Listed by OutBack Power for the Radian GS4048A inverter/charger, the inverter inside FPR-4048A-300AFCI, on the Radian A-Series datasheet #980-00076-01-001 REV C (03/2021), Listings/Certifications row, printed as "ETL listed to UL 1741 SA". It is a claim for that component, not a listing of the assembled pre-wired system. No certificate number, file number or issuer record was read. Recorded exactly as printed.
CSA C22.2 No. 107.1Manufacturer claim · equipment listingClaimedListed when checked
Listed by OutBack Power for the Radian GS4048A inverter/charger, the inverter inside FPR-4048A-300AFCI, on the Radian A-Series datasheet #980-00076-01-001 REV C (03/2021), Listings/Certifications row. It is a claim for that component, not a listing of the assembled pre-wired system. No certificate number, file number or issuer record was read. Recorded exactly as printed.
UL 778 Annex FManufacturer claim · equipment listingClaimedListed when checked
Listed by OutBack Power for the Radian GS4048A inverter/charger, the inverter inside FPR-4048A-300AFCI, on the Radian A-Series datasheet #980-00076-01-001 REV C (03/2021), Listings/Certifications row. It is a claim for that component, not a listing of the assembled pre-wired system. No certificate number, file number or issuer record was read. Recorded exactly as printed.
IEC 62109-1Manufacturer claim · equipment listingClaimedListed when checked
Listed by OutBack Power for the Radian GS4048A inverter/charger, the inverter inside FPR-4048A-300AFCI, on the Radian A-Series datasheet #980-00076-01-001 REV C (03/2021), Listings/Certifications row, printed as "IEC 62109-1 ETL". It is a claim for that component, not a listing of the assembled pre-wired system. No certificate number, file number or issuer record was read. Recorded exactly as printed.
FCC Class BManufacturer claim · equipment listingClaimedListed when checked
Listed by OutBack Power for the Radian GS4048A inverter/charger, the inverter inside FPR-4048A-300AFCI, on the Radian A-Series datasheet #980-00076-01-001 REV C (03/2021), Listings/Certifications row. It is a claim for that component, not a listing of the assembled pre-wired system. No certificate number, file number or issuer record was read. Recorded exactly as printed.
IEEE 1574.1Manufacturer claim · equipment listingClaimedListed when checked
Listed by OutBack Power for the Radian GS4048A inverter/charger, the inverter inside FPR-4048A-300AFCI, on the Radian A-Series datasheet #980-00076-01-001 REV C (03/2021), Listings/Certifications row. It is a claim for that component, not a listing of the assembled pre-wired system. No certificate number, file number or issuer record was read. Recorded exactly as printed.
EN61000-6-1Manufacturer claim · equipment listingClaimedListed when checked
Listed by OutBack Power for the Radian GS4048A inverter/charger, the inverter inside FPR-4048A-300AFCI, on the Radian A-Series datasheet #980-00076-01-001 REV C (03/2021), Listings/Certifications row. It is a claim for that component, not a listing of the assembled pre-wired system. No certificate number, file number or issuer record was read. Recorded exactly as printed.
EN61000-6-3Manufacturer claim · equipment listingClaimedListed when checked
Listed by OutBack Power for the Radian GS4048A inverter/charger, the inverter inside FPR-4048A-300AFCI, on the Radian A-Series datasheet #980-00076-01-001 REV C (03/2021), Listings/Certifications row. It is a claim for that component, not a listing of the assembled pre-wired system. No certificate number, file number or issuer record was read. Recorded exactly as printed.
EN61000-3-2Manufacturer claim · equipment listingClaimedListed when checked
Listed by OutBack Power for the Radian GS4048A inverter/charger, the inverter inside FPR-4048A-300AFCI, on the Radian A-Series datasheet #980-00076-01-001 REV C (03/2021), Listings/Certifications row. It is a claim for that component, not a listing of the assembled pre-wired system. No certificate number, file number or issuer record was read. Recorded exactly as printed.
EN61000-3-3Manufacturer claim · equipment listingClaimedListed when checked
Listed by OutBack Power for the Radian GS4048A inverter/charger, the inverter inside FPR-4048A-300AFCI, on the Radian A-Series datasheet #980-00076-01-001 REV C (03/2021), Listings/Certifications row. It is a claim for that component, not a listing of the assembled pre-wired system. No certificate number, file number or issuer record was read. Recorded exactly as printed.
OutBack Power's datasheet for the Radian GS8048A and GS4048A inverter/chargers, dated 03/2021, linked from the Radian Series product page. The GS4048A is the inverter/charger inside FPR-4048A-300AFCI; its figures are read from the GS4048A column and describe the inverter, not the assembled pre-wired system.
Archived copies
Archived copy of a document published by OutBack Power Technologies, Inc.. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email [email protected].
Captured by scripts/prepare-brand-sweep-sep21.mjs on 2026-09-24.
Location: Limited Warranty, first section
Retrieved Sep 23, 2026
OutBack Power's limited warranty statement, linked as "Warranty Information - English / Spanish" from the FLEXpower Radian product page. It covers GS series inverter/chargers with model numbers ending in A or E, FM60, FM80 and FM100 charge controllers and USA factory pre-wired FLEXpower systems incorporating those inverters. It prints no issue date.
Archived copies
Archived copy of a document published by OutBack Power Technologies, Inc.. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email [email protected].
Captured by scripts/prepare-brand-sweep-sep21.mjs on 2026-09-24.
Location: Heading, Product Highlights and Description sections
Retrieved Sep 23, 2026
OutBack Power's product page for the FLEXpower Radian family, captured on September 24, 2026. It calls the family a fully pre-wired 4 kW or 8 kW inverter system and links the FLEXpower Radian datasheet. Its model line names FPR-8048A-300VDC and FPR-8048A-01 and its description names FPR-4048A-300VDC; it does not print FPR-4048A-300AFCI, which is printed on the linked datasheet. It prints no per-model figures.
OutBack Power's FLEXpower Radian datasheet, linked from the current product page and served from old.outbackpower.com, dated 07/2020. Its specification table lists five pre-wired models, including FPR-4048A-300AFCI, with the inverter, load center, charge controller, dimensions and weight of each. Its power and efficiency charts are for the GS8048A only. Figures for FPR-4048A-300AFCI are read from its own row and column.
Archived copies
Archived copy of a document published by OutBack Power Technologies, Inc.. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email [email protected].
UL 1741Manufacturer claim · equipment listingClaimedListed when checked
Listed by OutBack Power for the FLEXmax 100 AFCI charge controller, one of which is included in FPR-4048A-300AFCI, on the FLEXmax 100 AFCI datasheet #980-00078-01-00 REV A (08/2019), Certifications row. It is a claim for that component, not a listing of the assembled pre-wired system. No certificate number, certification body or issuer record was read. Recorded exactly as printed.
CSA C22.2 No. 107.1Manufacturer claim · equipment listingClaimedListed when checked
Listed by OutBack Power for the FLEXmax 100 AFCI charge controller, one of which is included in FPR-4048A-300AFCI, on the FLEXmax 100 AFCI datasheet #980-00078-01-00 REV A (08/2019), Certifications row. It is a claim for that component, not a listing of the assembled pre-wired system. No certificate number, certification body or issuer record was read. Recorded exactly as printed.
IEC 62109-1Manufacturer claim · equipment listingClaimedListed when checked
Listed by OutBack Power for the FLEXmax 100 AFCI charge controller, one of which is included in FPR-4048A-300AFCI, on the FLEXmax 100 AFCI datasheet #980-00078-01-00 REV A (08/2019), Certifications row. It is a claim for that component, not a listing of the assembled pre-wired system. No certificate number, certification body or issuer record was read. Recorded exactly as printed.
Captured by scripts/prepare-brand-sweep-sep21.mjs on 2026-09-24.
Location: Page 2, FLEXmax 100 AFCI Specifications
Retrieved Sep 23, 2026
OutBack Power's datasheet for the FLEXmax 100 AFCI charge controller, dated 08/2019, linked from the FLEXpower Radian product page. FPR-4048A-300AFCI includes one FLEXmax 100 AFCI; its figures describe that controller, not the assembled system.
Archived copies
Archived copy of a document published by OutBack Power Technologies, Inc.. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email [email protected].
Archived copy of a document published by OutBack Power Technologies, Inc.. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email [email protected].
Archived copy of a document published by OutBack Power Technologies, Inc.. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email [email protected].
Archived copy of a document published by OutBack Power Technologies, Inc.. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email [email protected].
OutBack Power Limited Warranty, 900-0216-10-00 Rev C (English and Spanish)
Archived copy of a document published by OutBack Power Technologies, Inc.. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email [email protected].
OutBack Power FP Radian Quick Start Guide, Setup and Programming (900-0226-01-00 REV C)
Archived copy of a document published by OutBack Power. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email [email protected].
No sourced accessories or replacement parts listed yet.
Model history
Model identity
Model
FPR-4048A-300AFCI
Manufacturer SKU FPR-4048A-300AFCI · US market
Observed Sep 24, 2026
UL 1741 SA: claimed
Product / system scope unresolved. Listed by OutBack Power for the Radian GS4048A inverter/charger, the inverter inside FPR-4048A-300AFCI, on the Radian A-Series datasheet #980-00076-01-001 REV C (03/2021), Listings/Certifications row, printed as "ETL listed to UL 1741 SA". It is a claim for that component, not a listing of the assembled pre-wired system. No certificate number, file number or issuer record was read. Recorded exactly as printed.
Product / system scope unresolved. Listed by OutBack Power for the Radian GS4048A inverter/charger, the inverter inside FPR-4048A-300AFCI, on the Radian A-Series datasheet #980-00076-01-001 REV C (03/2021), Listings/Certifications row. It is a claim for that component, not a listing of the assembled pre-wired system. No certificate number, file number or issuer record was read. Recorded exactly as printed.
Product / system scope unresolved. Listed by OutBack Power for the Radian GS4048A inverter/charger, the inverter inside FPR-4048A-300AFCI, on the Radian A-Series datasheet #980-00076-01-001 REV C (03/2021), Listings/Certifications row. It is a claim for that component, not a listing of the assembled pre-wired system. No certificate number, file number or issuer record was read. Recorded exactly as printed.
Product / system scope unresolved. Listed by OutBack Power for the Radian GS4048A inverter/charger, the inverter inside FPR-4048A-300AFCI, on the Radian A-Series datasheet #980-00076-01-001 REV C (03/2021), Listings/Certifications row, printed as "IEC 62109-1 ETL". It is a claim for that component, not a listing of the assembled pre-wired system. No certificate number, file number or issuer record was read. Recorded exactly as printed.
Product / system scope unresolved. Listed by OutBack Power for the Radian GS4048A inverter/charger, the inverter inside FPR-4048A-300AFCI, on the Radian A-Series datasheet #980-00076-01-001 REV C (03/2021), Listings/Certifications row. It is a claim for that component, not a listing of the assembled pre-wired system. No certificate number, file number or issuer record was read. Recorded exactly as printed.
Product / system scope unresolved. Listed by OutBack Power for the Radian GS4048A inverter/charger, the inverter inside FPR-4048A-300AFCI, on the Radian A-Series datasheet #980-00076-01-001 REV C (03/2021), Listings/Certifications row. It is a claim for that component, not a listing of the assembled pre-wired system. No certificate number, file number or issuer record was read. Recorded exactly as printed.
Product / system scope unresolved. Listed by OutBack Power for the Radian GS4048A inverter/charger, the inverter inside FPR-4048A-300AFCI, on the Radian A-Series datasheet #980-00076-01-001 REV C (03/2021), Listings/Certifications row. It is a claim for that component, not a listing of the assembled pre-wired system. No certificate number, file number or issuer record was read. Recorded exactly as printed.
Product / system scope unresolved. Listed by OutBack Power for the Radian GS4048A inverter/charger, the inverter inside FPR-4048A-300AFCI, on the Radian A-Series datasheet #980-00076-01-001 REV C (03/2021), Listings/Certifications row. It is a claim for that component, not a listing of the assembled pre-wired system. No certificate number, file number or issuer record was read. Recorded exactly as printed.
Product / system scope unresolved. Listed by OutBack Power for the Radian GS4048A inverter/charger, the inverter inside FPR-4048A-300AFCI, on the Radian A-Series datasheet #980-00076-01-001 REV C (03/2021), Listings/Certifications row. It is a claim for that component, not a listing of the assembled pre-wired system. No certificate number, file number or issuer record was read. Recorded exactly as printed.
Product / system scope unresolved. Listed by OutBack Power for the Radian GS4048A inverter/charger, the inverter inside FPR-4048A-300AFCI, on the Radian A-Series datasheet #980-00076-01-001 REV C (03/2021), Listings/Certifications row. It is a claim for that component, not a listing of the assembled pre-wired system. No certificate number, file number or issuer record was read. Recorded exactly as printed.
Product / system scope unresolved. Listed by OutBack Power for the FLEXmax 100 AFCI charge controller, one of which is included in FPR-4048A-300AFCI, on the FLEXmax 100 AFCI datasheet #980-00078-01-00 REV A (08/2019), Certifications row. It is a claim for that component, not a listing of the assembled pre-wired system. No certificate number, certification body or issuer record was read. Recorded exactly as printed.
Product / system scope unresolved. Listed by OutBack Power for the FLEXmax 100 AFCI charge controller, one of which is included in FPR-4048A-300AFCI, on the FLEXmax 100 AFCI datasheet #980-00078-01-00 REV A (08/2019), Certifications row. It is a claim for that component, not a listing of the assembled pre-wired system. No certificate number, certification body or issuer record was read. Recorded exactly as printed.
Product / system scope unresolved. Listed by OutBack Power for the FLEXmax 100 AFCI charge controller, one of which is included in FPR-4048A-300AFCI, on the FLEXmax 100 AFCI datasheet #980-00078-01-00 REV A (08/2019), Certifications row. It is a claim for that component, not a listing of the assembled pre-wired system. No certificate number, certification body or issuer record was read. Recorded exactly as printed.
Product prices and availability are accurate as of the date/time indicated and are subject to change. Any price and availability information displayed on Amazon.com at the time of purchase will apply to the purchase of this product. CERTAIN CONTENT THAT APPEARS ON THIS SITE COMES FROM AMAZON. THIS CONTENT IS PROVIDED ‘AS IS’ AND IS SUBJECT TO CHANGE OR REMOVAL AT ANY TIME.
* Missing details
Product prices and availability are accurate as of the date/time indicated and are subject to change. Any price and availability information displayed on Amazon.com at the time of purchase will apply to the purchase of this product. CERTAIN CONTENT THAT APPEARS ON THIS SITE COMES FROM AMAZON. THIS CONTENT IS PROVIDED ‘AS IS’ AND IS SUBJECT TO CHANGE OR REMOVAL AT ANY TIME.