Printed as a model on the SGS certificate NeoVolta serves ("Model(s): NV14, NV14-K, NV24") and as the first model column of the datasheet ("NV14 | NV24"). The datasheet heading prints NV14-US. NV14-K is a separate model and is not this record.
Read from the NV14 column of "14.4 | 9.6". Nominal, not usable; the datasheet prints no usable energy. The SGS certificate prints Energy Output 3*4800Wh for the NV14.
Printed as "Nominal AC output (W) 7,600" in the AC Output (On-Grid) table, with Max. AC Output 8,360 VA and Nominal AC Output 31.7 A. The datasheet calls it nominal, not continuous, and prints no separate backup continuous rating.
Printed as 500 Voc, with the note that it "shall be calculated at coldest operating temperature of installation locations". MPPT voltage range 150-425 V.
Read from the NV14 column of "14.4 | 9.6". Nominal, not usable; the datasheet prints no usable energy. The SGS certificate prints Energy Output 3*4800Wh for the NV14.
Printed as "Nominal AC output (W) 7,600" in the AC Output (On-Grid) table, with Max. AC Output 8,360 VA and Nominal AC Output 31.7 A. The datasheet calls it nominal, not continuous, and prints no separate backup continuous rating.
Printed as 500 Voc, with the note that it "shall be calculated at coldest operating temperature of installation locations". MPPT voltage range 150-425 V.
Printed as "NV14 575 / 260" (lbs / kg), the approximate weight with batteries. The manual gives 265 lbs (114 kg) for the cabinet without batteries and about 96.5 lbs (43.8 kg) per battery.
Location: AC Output Data (Back-Up), Nominal Output Voltage | Voltage Range (V)
Documented
Installation clearances (manual)
4 in (102 mm) on the right side, 4 in (102 mm) on the SW1 switch side and 36 in (914 mm) to the front; no vertical clearance requirement other than not using the top as a shelf
Printed as "clearance on right side, 4” (102mm) on SW1 switch side"; "and 36” (914mm) clearance to the front."; "There is no vertical clearance requirement other than not to use" in the NV14 Energy Storage System Installation Manual (w/NV24 Option), V1.02042026 (NeoVolta, captured September 24, 2026) (PDF page 14, section 5.1.2, clearance requirements).
Charged Reviews classified this product from the documents it is based on. It is our own grouping, not a manufacturer claim.
Printed as "The NV14 Energy Storage System must be installed using the wall mounting brackets and hardware provided." and "Floor Mount". Classified as Wall / floor from the maker's own words for this model (wall or floor mounting, the catalog's combined Wall / floor value).
Printed as "The position of the four (4) left-most dipswitch pins determine the Battery ID"; "Each battery must have a unique ID."; "Dipswitches 5 & 6 are not to be used" in the NV14 Energy Storage System Installation Manual (w/NV24 Option), V1.02042026 (NeoVolta, captured September 24, 2026) (PDF page 11, section 4.3.1, battery unique ID setting).
Printed as "Torque the battery terminal to 160 in-lbs. (18Nm)." in the NV14 Energy Storage System Installation Manual (w/NV24 Option), V1.02042026 (NeoVolta, captured September 24, 2026) (PDF page 26, section 6.3, battery wiring connections). Battery terminal torque for each battery in the NV14 and the NV24 cabinet.
Printed as "Connect the CAT5 ethernet cable to the battery RS485 port."; "There are two (2) RS485 ports." in the NV14 Energy Storage System Installation Manual (w/NV24 Option), V1.02042026 (NeoVolta, captured September 24, 2026) (PDF page 26, section 6.3, battery wiring connections).
Location: PDF page 26, section 6.3, battery wiring connections
Documented
Published claims and calculations, not independent test results.
Documents
2 on file
PDF
NV14 Datasheet V2.02102026, Inverter & Storage System NV14-US (NeoVolta, captured September 24, 2026)OfficialNeoVoltaOfficial datasheet
Certificate & compliance claims (9)
UL9540Manufacturer claim · equipment listingClaimedListed when checked
Listed by NeoVolta in the "Grid Regulations | Certifications" row of its NV14-US datasheet V2.02102026. Recorded exactly as printed. The datasheet names no issuer, report or edition; no issuer directory was read.
UL9540AManufacturer claim · equipment listingClaimedListed when checked
Listed by NeoVolta in the "Grid Regulations | Certifications" row of its NV14-US datasheet V2.02102026. Recorded exactly as printed. UL 9540A is a test method; the datasheet names no report, issuer or unit level, and none was read.
IEEE1547.1 SRD V2.0Manufacturer claim · equipment listingClaimedListed when checked
Listed by NeoVolta in the "Grid Regulations | Certifications" row of its NV14-US datasheet V2.02102026. Recorded exactly as printed. The datasheet names no issuer or report; none was read.
UL1741 CRDManufacturer claim · equipment listingClaimedListed when checked
Listed by NeoVolta in the "Grid Regulations | Certifications" row of its NV14-US datasheet V2.02102026. Recorded exactly as printed. The datasheet names no issuer or report; none was read.
UL1741 SBManufacturer claim · equipment listingClaimedListed when checked
Listed by NeoVolta in the "Grid Regulations | Certifications" row of its NV14-US datasheet V2.02102026. Recorded exactly as printed. The datasheet names no issuer or report; none was read.
UL1699BManufacturer claim · equipment listingClaimedListed when checked
Listed by NeoVolta in the "Grid Regulations | Certifications" row of its NV14-US datasheet V2.02102026. Recorded exactly as printed. The datasheet's General table lists the arc fault circuit interrupter as optional. No issuer or report is named; none was read.
CSA C22.2 NO 107.1-16Manufacturer claim · equipment listingClaimedListed when checked
Listed by NeoVolta in the "Grid Regulations | Certifications" row of its NV14-US datasheet V2.02102026. Recorded exactly as printed. The datasheet names no issuer or report; none was read.
CA Rule No. 21 CECManufacturer claim · equipment listingClaimedListed when checked
Listed by NeoVolta in the "Grid Regulations | Certifications" row of its NV14-US datasheet V2.02102026, printed as "CA Rule No. 21 CEC" with no separator, so it may name two entries (California Rule 21 and a CEC listing). Recorded exactly as printed. The CEC equipment list was not read in this pass.
HECOManufacturer claim · equipment listingClaimedListed when checked
Listed by NeoVolta in the "Grid Regulations | Certifications" row of its NV14-US datasheet V2.02102026. Recorded exactly as printed. Hawaiian Electric's qualified equipment list was not read in this pass.
NeoVolta's two-page datasheet for the NV14-US inverter and storage system with the optional NV24 cabinet, listed as "NV14 Datasheet V2.02102026" on NeoVolta's documentation page and captured on September 24, 2026. Where a row prints two values separated by "|" under the heading "NV14 | NV24", the first is the NV14 and the second the NV24. NeoVolta's disclaimer says all weights and measures are best approximations. The certification row is a manufacturer claim; no issuer directory was read.
Archived copies
Archived copy of a document published by NeoVolta. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email legal@chargedreviews.com.
NV14 Energy Storage System Installation Manual (w/NV24 Option), V1.02042026 (NeoVolta, captured September 24, 2026)OfficialNeoVoltaOfficial installation manual
Source details
Revision
V1.02042026
Revision date
Not stated
Location: Sections 5.1 and 5.2
Retrieved
NeoVolta's 41-page installation manual for the NV14 with the optional NV24 battery cabinet, listed as "NV14 wNV24 Installation Manual V1.02052026" on NeoVolta's documentation page (the cover prints V1.02042026), captured on September 24, 2026. Read here for the NV24 cabinet's enclosure rating and installed weight.
Archived copies
Archived copy of a document published by NeoVolta. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email legal@chargedreviews.com.
Earlier revisions, archived captures and copies published by someone other than the manufacturer. Every one stays reachable.
Archived documents
NV14 Datasheet V2.02102026, Inverter & Storage System NV14-US (NeoVolta, captured September 24, 2026)
Archived copy of a document published by NeoVolta. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email legal@chargedreviews.com.
NV14 Energy Storage System Installation Manual (w/NV24 Option), V1.02042026 (NeoVolta, captured September 24, 2026)
Archived copy of a document published by NeoVolta. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email legal@chargedreviews.com.
SGS Certificate of Compliance SGSNA/22/GZ/00203, Energy Storage System NV14, NV14-K, NV24 (as served by NeoVolta, captured September 24, 2026)
Archived copy of a document published by NeoVolta. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email legal@chargedreviews.com.
The Evidence score uses the priorities you choose. It counts published documents, such as certificates and warranty terms, and it compares a documented figure with the best documented figure of the same kind. It does not count owner reviews, and it is not a verdict on product quality or on how many people have reviewed it. A low score can mean little is documented, or that a documented figure is below the best of its kind. Undisclosed data scores 0.
Missing details. This number counts only the evidence recorded so far. The source review for this product is not finished, or the maker has not disclosed enough, so the number can only go up.
Missing for this product: Warranty energy disclosure evidence needed; Cell model disclosure evidence needed.
AC-coupled · Wall / floor · Usable capacity
The warranty term and the lifetime energy are each scored against the best documented value for a home storage battery: a value earns its share of that best, times the weight. A documented value always earns points; an undisclosed one earns 0.
CertificatesCEC +9CEC listed45 / 45
100 evidence points · 45% weight
CEC listing: full credit for the certificate criterion. Exact model found in the dated CEC equipment list. This is not a safety certification or system approval. Applies: CEC; UL 9540; UL 1973.
Printed as "Warranty 15 years" in the datasheet's General table. The warranty document's coverage, throughput limits, exclusions and claim procedure were not read in this pass.
Research pending, 0 points: Warranty energy disclosure, Cell model disclosure.
Computed from public specifications and evidence records. Warranty duration is not service quality; certificate evidence points are not a safety rating. Compatibility and installation limits still apply.
UL 9540, 2nd Edition, dated February 27, 2020Product / system scope unresolvedClaimedListed when checked
SGS North America certificate of compliance SGSNA/22/GZ/00203, effective April 29, 2026, certified product "Energy Storage System", models NV14, NV14-K and NV24. The standard is recorded exactly as the certificate prints it. Read from the certificate as NeoVolta serves it on its documentation page, captured September 24, 2026; the SGS directory the certificate names was not checked, so this remains a manufacturer-hosted certificate.
Models: NV14, NV14-K, NV24
Standard as printed
UL 9540, 2nd Edition, dated February 27, 2020
Edition as printed
Not printed
What it covers
Product / system scope unresolved
Type
A listing to the energy storage system standard
For a permit
Permit offices commonly ask for this listing; local rules vary.
UL9540Product / system scope unresolvedClaimedListed when checked
Listed by NeoVolta in the "Grid Regulations | Certifications" row of its NV14-US datasheet V2.02102026. Recorded exactly as printed. The datasheet names no issuer, report or edition; no issuer directory was read.
Models: NV14-US
Standard as printed
UL9540
Edition as printed
Not printed
What it covers
Product / system scope unresolved
Type
A listing to the energy storage system standard
For a permit
Permit offices commonly ask for this listing; local rules vary.
UL9540AProduct / system scope unresolvedClaimedListed when checked
Listed by NeoVolta in the "Grid Regulations | Certifications" row of its NV14-US datasheet V2.02102026. Recorded exactly as printed. UL 9540A is a test method; the datasheet names no report, issuer or unit level, and none was read.
Models: NV14-US
Standard as printed
UL9540A
Edition as printed
Not printed
What it covers
Product / system scope unresolved
Type
A fire-test report (UL 9540A is a test method, not a listing)
For a permit
A fire test. Useful supporting evidence, but it does not replace UL 9540.
IEEE1547.1 SRD V2.0Product / system scope unresolvedClaimedListed when checked
Listed by NeoVolta in the "Grid Regulations | Certifications" row of its NV14-US datasheet V2.02102026. Recorded exactly as printed. The datasheet names no issuer or report; none was read.
UL1741 CRDProduct / system scope unresolvedClaimedListed when checked
Listed by NeoVolta in the "Grid Regulations | Certifications" row of its NV14-US datasheet V2.02102026. Recorded exactly as printed. The datasheet names no issuer or report; none was read.
UL1741 SBProduct / system scope unresolvedClaimedListed when checked
Listed by NeoVolta in the "Grid Regulations | Certifications" row of its NV14-US datasheet V2.02102026. Recorded exactly as printed. The datasheet names no issuer or report; none was read.
UL1699BProduct / system scope unresolvedClaimedListed when checked
Listed by NeoVolta in the "Grid Regulations | Certifications" row of its NV14-US datasheet V2.02102026. Recorded exactly as printed. The datasheet's General table lists the arc fault circuit interrupter as optional. No issuer or report is named; none was read.
CSA C22.2 NO 107.1-16Product / system scope unresolvedClaimedListed when checked
Listed by NeoVolta in the "Grid Regulations | Certifications" row of its NV14-US datasheet V2.02102026. Recorded exactly as printed. The datasheet names no issuer or report; none was read.
CA Rule No. 21 CECProduct / system scope unresolvedClaimedListed when checked
Listed by NeoVolta in the "Grid Regulations | Certifications" row of its NV14-US datasheet V2.02102026, printed as "CA Rule No. 21 CEC" with no separator, so it may name two entries (California Rule 21 and a CEC listing). Recorded exactly as printed.
UL 1741 SBProduct / system scope unresolvedClaimedListed when checked
Listed on the California Energy Commission Energy Storage System List (data unchanged since October 1, 2026; downloaded October 11, 2026) as NeoVolta Inc. "NV14 {208V, 14.4kWh}": UL 1741 SB, certifying entity SGS, certificate date 2022-07-14, CEC listing date 2019-11-01. A state equipment list entry, not the certification body's own record.
UL 9540Product / system scope unresolvedClaimedListed when checked
Listed on the California Energy Commission Energy Storage System List (data unchanged since October 1, 2026; downloaded October 11, 2026) as NeoVolta Inc. "NV14 {208V, 14.4kWh}": UL 9540, certifying entity SGS, certificate date 2022-09-15, Ed. 2 : 2020, CEC listing date 2019-11-01. A state equipment list entry, not the certification body's own record.
Models: NV14
Standard as printed
UL 9540
Edition as printed
Not printed
What it covers
Product / system scope unresolved
Type
A listing to the energy storage system standard
For a permit
Permit offices commonly ask for this listing; local rules vary.
CECProduct / system scope unresolvedClaimedListed when checked
Model NV14 listed on the California Energy Commission Energy Storage System List (data unchanged since October 1, 2026; downloaded October 11, 2026) under NeoVolta Inc., as "NV14 {208V, 14.4kWh}"; "NV14 {208V, 24kWh}"; "NV14 {240V, 14.4kWh}"; "NV14 {240V, 24kWh}", CEC listing date 2019-11-01. This is an equipment listing, not UL certification or complete-system approval.
UL9540Manufacturer claim · equipment listingClaimedListed when checked
Listed by NeoVolta in the "Grid Regulations | Certifications" row of its NV14-US datasheet V2.02102026. Recorded exactly as printed. The datasheet names no issuer, report or edition; no issuer directory was read.
UL9540AManufacturer claim · equipment listingClaimedListed when checked
Listed by NeoVolta in the "Grid Regulations | Certifications" row of its NV14-US datasheet V2.02102026. Recorded exactly as printed. UL 9540A is a test method; the datasheet names no report, issuer or unit level, and none was read.
IEEE1547.1 SRD V2.0Manufacturer claim · equipment listingClaimedListed when checked
Listed by NeoVolta in the "Grid Regulations | Certifications" row of its NV14-US datasheet V2.02102026. Recorded exactly as printed. The datasheet names no issuer or report; none was read.
UL1741 CRDManufacturer claim · equipment listingClaimedListed when checked
Listed by NeoVolta in the "Grid Regulations | Certifications" row of its NV14-US datasheet V2.02102026. Recorded exactly as printed. The datasheet names no issuer or report; none was read.
UL1741 SBManufacturer claim · equipment listingClaimedListed when checked
Listed by NeoVolta in the "Grid Regulations | Certifications" row of its NV14-US datasheet V2.02102026. Recorded exactly as printed. The datasheet names no issuer or report; none was read.
UL1699BManufacturer claim · equipment listingClaimedListed when checked
Listed by NeoVolta in the "Grid Regulations | Certifications" row of its NV14-US datasheet V2.02102026. Recorded exactly as printed. The datasheet's General table lists the arc fault circuit interrupter as optional. No issuer or report is named; none was read.
CSA C22.2 NO 107.1-16Manufacturer claim · equipment listingClaimedListed when checked
Listed by NeoVolta in the "Grid Regulations | Certifications" row of its NV14-US datasheet V2.02102026. Recorded exactly as printed. The datasheet names no issuer or report; none was read.
CA Rule No. 21 CECManufacturer claim · equipment listingClaimedListed when checked
Listed by NeoVolta in the "Grid Regulations | Certifications" row of its NV14-US datasheet V2.02102026, printed as "CA Rule No. 21 CEC" with no separator, so it may name two entries (California Rule 21 and a CEC listing). Recorded exactly as printed. The CEC equipment list was not read in this pass.
HECOManufacturer claim · equipment listingClaimedListed when checked
Listed by NeoVolta in the "Grid Regulations | Certifications" row of its NV14-US datasheet V2.02102026. Recorded exactly as printed. Hawaiian Electric's qualified equipment list was not read in this pass.
Product / system scope unresolved. Listed on the California Energy Commission Energy Storage System List (data unchanged since October 1, 2026; downloaded October 11, 2026) as NeoVolta Inc. "NV14 {208V, 14.4kWh}": UL 1741 SB, certifying entity SGS, certificate date 2022-07-14, CEC listing date 2019-11-01. A state equipment list entry, not the certification body's own record.
Product / system scope unresolved. Listed on the California Energy Commission Energy Storage System List (data unchanged since October 1, 2026; downloaded October 11, 2026) as NeoVolta Inc. "NV14 {208V, 14.4kWh}": UL 9540, certifying entity SGS, certificate date 2022-09-15, Ed. 2 : 2020, CEC listing date 2019-11-01. A state equipment list entry, not the certification body's own record.
Product / system scope unresolved. Model NV14 listed on the California Energy Commission Energy Storage System List (data unchanged since October 1, 2026; downloaded October 11, 2026) under NeoVolta Inc., as "NV14 {208V, 14.4kWh}"; "NV14 {208V, 24kWh}"; "NV14 {240V, 14.4kWh}"; "NV14 {240V, 24kWh}", CEC listing date 2019-11-01. This is an equipment listing, not UL certification or complete-system approval.
UL 9540, 2nd Edition, dated February 27, 2020: claimed
Product / system scope unresolved. SGS North America certificate of compliance SGSNA/22/GZ/00203, effective April 29, 2026, certified product "Energy Storage System", models NV14, NV14-K and NV24. The standard is recorded exactly as the certificate prints it. Read from the certificate as NeoVolta serves it on its documentation page, captured September 24, 2026; the SGS directory the certificate names was not checked, so this remains a manufacturer-hosted certificate.
Product / system scope unresolved. Listed by NeoVolta in the "Grid Regulations | Certifications" row of its NV14-US datasheet V2.02102026. Recorded exactly as printed. The datasheet names no issuer, report or edition; no issuer directory was read.
Product / system scope unresolved. Listed by NeoVolta in the "Grid Regulations | Certifications" row of its NV14-US datasheet V2.02102026. Recorded exactly as printed. UL 9540A is a test method; the datasheet names no report, issuer or unit level, and none was read.
Product / system scope unresolved. Listed by NeoVolta in the "Grid Regulations | Certifications" row of its NV14-US datasheet V2.02102026. Recorded exactly as printed. The datasheet names no issuer or report; none was read.
Product / system scope unresolved. Listed by NeoVolta in the "Grid Regulations | Certifications" row of its NV14-US datasheet V2.02102026. Recorded exactly as printed. The datasheet names no issuer or report; none was read.
Product / system scope unresolved. Listed by NeoVolta in the "Grid Regulations | Certifications" row of its NV14-US datasheet V2.02102026. Recorded exactly as printed. The datasheet names no issuer or report; none was read.
Product / system scope unresolved. Listed by NeoVolta in the "Grid Regulations | Certifications" row of its NV14-US datasheet V2.02102026. Recorded exactly as printed. The datasheet's General table lists the arc fault circuit interrupter as optional. No issuer or report is named; none was read.
Product / system scope unresolved. Listed by NeoVolta in the "Grid Regulations | Certifications" row of its NV14-US datasheet V2.02102026. Recorded exactly as printed. The datasheet names no issuer or report; none was read.
Product / system scope unresolved. Listed by NeoVolta in the "Grid Regulations | Certifications" row of its NV14-US datasheet V2.02102026, printed as "CA Rule No. 21 CEC" with no separator, so it may name two entries (California Rule 21 and a CEC listing). Recorded exactly as printed. The CEC equipment list was not read in this pass.
Product / system scope unresolved. Listed by NeoVolta in the "Grid Regulations | Certifications" row of its NV14-US datasheet V2.02102026. Recorded exactly as printed. Hawaiian Electric's qualified equipment list was not read in this pass.