Printed as "Ensure that the grounding terminal is securely connected to the grounding bar." Setting 63 (PDF page 29) prints "N-PE bonding automatic switching function DIS default", an automatic N-PE switch that is off by default.
Converted: 118 lb x 0.45359237 kg/lb, rounded to 0.01 kg
Printed as "Weight 118 lbs" in the PowerCore_18K-48_All-in-One_Solar_Charge_Inverter_User_Manual.pdf; the maker prints pounds only, converted to kilograms. Revised on 30 September 2026: The maker prints this weight in pounds only; the stored kilograms were an unlabeled conversion, now labeled with the printed pounds kept (Project Manager, September 30, 2026).
Printed as "Max. Peak Power 2 times rated power, 10s" in the PowerCore 18K-48 user manual, next to "Rated Output Power 18000W". No figure in W is printed, so none is computed. Captured on September 25, 2026.
Printed as "Max. Peak Power 2 times rated power, 10s" in the PowerCore 18K-48 user manual, next to "Rated Output Power 18000W". No figure in W is printed, so none is computed. Captured on September 25, 2026.
Printed as "Provides three-phase pure sine wave output (156–242 V)" in the maker's document "PowerCore_18K-48_All-in-One_Solar_Charge_Inverter_User_Manual.pdf".
Printed as "Battery Types Li-ion / Lead-Acid / User Defined" (settable). Setting 33 (PDF page 28) lists the 485 and CAN BMS protocols, including "SGP=SUNGOLDPOWER".
Printed as "Ensure that the grounding terminal is securely connected to the grounding bar." Setting 63 (PDF page 29) prints "N-PE bonding automatic switching function DIS default", an automatic N-PE switch that is off by default.
Converted: 118 lb x 0.45359237 kg/lb, rounded to 0.01 kg
Printed as "Weight 118 lbs" in the PowerCore_18K-48_All-in-One_Solar_Charge_Inverter_User_Manual.pdf; the maker prints pounds only, converted to kilograms. Revised on 30 September 2026: The maker prints this weight in pounds only; the stored kilograms were an unlabeled conversion, now labeled with the printed pounds kept (Project Manager, September 30, 2026).
Printed as "PowerCore 18K-48 6mm²/ 10AWG 36A 2P-45A"; 2P-45A is the circuit breaker specification for a 36A maximum input current. The unit also has a PV switch (overview item 24).
Printed as "PowerCore 18K-48 Three-phase 35mm²/2 AWG (L1/L2/L3/N) 100A 4P-125A" in both the Grid and the Generator tables; 4P-125A is the circuit breaker specification for a 100A maximum input current.
Printed as "The grounding conductor shall have a minimum cross-sectional area of 4 mm²" and routed as close as possible to the grounding point. The PE terminal drawing on PDF page 15 labels its cable "6mm²/10AWG".
Printed as "PowerCore 18K-48 Three-phase 35mm²/2 AWG (L1/L2/L3/N) 100A 4P-125A" in the Load table; 4P-125A is the circuit breaker specification for a 100A maximum output current.
Printed as "Dedicated generator port, which can also serve as a secondary load output." The overview prints "Generator Input (L1+L2+L3+N)"; setting 74 says the maximum generator power setting of 36kW corresponds "to a maximum generator input of 18kW for charging and 18kW for load supply".
Read from rendered pages 14 and 15: the GRID, GEN and LOAD terminal drawings each mark "3.0-3.5N.m" next to the L1, L2, L3 and N terminals (Cable: 35mm²/2AWG).
Printed as "PowerCore 18K-48 Three-phase 35mm²/2 AWG (L1/L2/L3/N) 100A 4P-125A" in the Load table (three-phase output mode; 100A is the maximum output current).
Parallel Port (PAR-B); Parallel Port (PAR-A); CAN Port; DRM Port; CT Port; USB-2 Port; USB-1 Port; WiFi Port; Meter Port; RS485/CAN Port; Dry Contact Port
Printed as "4 Parallel Port (PAR-B) 5 Parallel Port (PAR-A) 6 CAN Port 7 DRM Port 8 CT Port 9 USB-2 Port 10 USB-1 Port 11 WiFi Port 12 Meter Port 13 RS485/CAN Port 14 Dry Contact Prot" (the manual spells the last one "Prot"). The product overview (PDF page 6) also lists a second WiFi port.
Printed as "Select a solid wall to mount the inverter." and "Install the inverter at eye level for easy access and monitoring." Section 3.2.2 (PDF page 10) hangs the unit on a wall-mounting bracket.
Printed as "between 14 °F and 131 °F (–10 °C to 55 °C)" for optimal performance; the datasheet (PDF page 50) prints "Operating Temperature 14 ~ 131 °F, >113 °F Derated".
Linked from https://sungoldpower.com/products/18kw-48v-all-in-one-solar-charge-inverter-powercore-18k-48 with link text "none".
Location: PowerCore_18K-48_Data_Sheet.pdf
Retrieved
Original manufacturer-hosted PDF preserved byte for byte, linked from the manufacturer's own product page for SKU PowerCore 18K-48. The revision is whatever was published at this URL on the access date; no later revision was checked and no separate variant coverage is claimed beyond the page that linked it.
Archived copy of a document published by SunGoldPower. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email legal@chargedreviews.com.
IEC62109-1Manufacturer claim · equipment listingClaimedListed when checked
SunGoldPower's own statement, recorded exactly as printed: "Safety IEC62109-1, IEC62109-2 EMC EN61000-6-1, EN61000-6-3, FCC 15 class B" (PowerCore_18K-48_All-in-One_Solar_Charge_Inverter_User_Manual.pdf). A manufacturer statement names no certificate number or issuer and is not evidence of a listing; certificate documents SunGoldPower serves are recorded separately.
IEC62109-2Manufacturer claim · equipment listingClaimedListed when checked
SunGoldPower's own statement, recorded exactly as printed: "Safety IEC62109-1, IEC62109-2 EMC EN61000-6-1, EN61000-6-3, FCC 15 class B" (PowerCore_18K-48_All-in-One_Solar_Charge_Inverter_User_Manual.pdf). A manufacturer statement names no certificate number or issuer and is not evidence of a listing; certificate documents SunGoldPower serves are recorded separately.
EN61000-6-1Manufacturer claim · equipment listingClaimedListed when checked
SunGoldPower's own statement, recorded exactly as printed: "Safety IEC62109-1, IEC62109-2 EMC EN61000-6-1, EN61000-6-3, FCC 15 class B" (PowerCore_18K-48_All-in-One_Solar_Charge_Inverter_User_Manual.pdf). A manufacturer statement names no certificate number or issuer and is not evidence of a listing; certificate documents SunGoldPower serves are recorded separately.
EN61000-6-3Manufacturer claim · equipment listingClaimedListed when checked
SunGoldPower's own statement, recorded exactly as printed: "Safety IEC62109-1, IEC62109-2 EMC EN61000-6-1, EN61000-6-3, FCC 15 class B" (PowerCore_18K-48_All-in-One_Solar_Charge_Inverter_User_Manual.pdf). A manufacturer statement names no certificate number or issuer and is not evidence of a listing; certificate documents SunGoldPower serves are recorded separately.
FCC 15 class BManufacturer claim · equipment listingClaimedListed when checked
SunGoldPower's own statement, recorded exactly as printed: "Safety IEC62109-1, IEC62109-2 EMC EN61000-6-1, EN61000-6-3, FCC 15 class B" (PowerCore_18K-48_All-in-One_Solar_Charge_Inverter_User_Manual.pdf). A manufacturer statement names no certificate number or issuer and is not evidence of a listing; certificate documents SunGoldPower serves are recorded separately.
Original manufacturer-hosted PDF preserved byte for byte, linked from the manufacturer's own product page for SKU PowerCore 18K-48. The revision is whatever was published at this URL on the access date; no later revision was checked and no separate variant coverage is claimed beyond the page that linked it.
Archived copy of a document published by SunGoldPower. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email legal@chargedreviews.com.
Location: Product heading; Highlight list; Specification and User Manual tabs (manual-download-button links)
Retrieved
SunGoldPower's own product page, captured byte for byte on September 23, 2026. It establishes what SunGoldPower published for PowerCore 18K-48 on that date: the page heading, the Highlight text, the variant selector (SKUs PowerCore 18K-48) and the 2 document link(s) under its User Manual tab. Prices and stock on the page are the state of a promotional storefront and are not recorded from it. A specification quoted from the page is SunGoldPower's own published figure, not a test result.
Earlier revisions, archived captures and copies published by someone other than the manufacturer. Every one stays reachable.
Archived documents
PowerCore_18K-48_Data_Sheet.pdf
Archived copy of a document published by SunGoldPower. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email legal@chargedreviews.com.
Archived copy of a document published by SunGoldPower. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email legal@chargedreviews.com.
$3,816.94Price as of Nov 13, 2026, 3:41 PM PST, may change
Visit sellerPaid link. As an Amazon Associate we earn from qualifying purchases.
Evidence
Price from the Amazon Creators API for the New-condition featured offer. Price checked .
Product prices and availability are accurate as of the date/time indicated and are subject to change. Any price and availability information displayed on Amazon.com at the time of purchase will apply to the purchase of this product.
Product prices and availability are accurate as of the date/time indicated and are subject to change. Any price and availability information displayed on Amazon.com at the time of purchase will apply to the purchase of this product.
CERTAIN CONTENT THAT APPEARS ON THIS SITE COMES FROM AMAZON. THIS CONTENT IS PROVIDED ‘AS IS’ AND IS SUBJECT TO CHANGE OR REMOVAL AT ANY TIME.
The Evidence score uses the priorities you choose. It counts published documents, such as certificates and warranty terms, and it compares a documented figure with the best documented figure of the same kind. It does not count owner reviews, and it is not a verdict on product quality or on how many people have reviewed it. A low score can mean little is documented, or that a documented figure is below the best of its kind. Undisclosed data scores 0.
Missing for this product: Certificate evidence needed; Warranty term needed; Battery conversion efficiency needed; Idle consumption needed.
Each input is scored against the best documented value for an inverter: warranty term and battery conversion efficiency against every published inverter, idle consumption (lower is better) against the inverters in the same output band, or against every published inverter when the output is not documented. A documented value always earns points; an undisclosed one earns 0 and is listed as missing. Researched products receive a score. Certificates earn points for the evidence itself. Size and weight do not affect scores.
Warranty term and battery conversion efficiency are compared with every published inverter; idle consumption with the inverters in the same 15 to 50 kW output band. · Method version 0.5
IEC62109-1Product / system scope unresolvedClaimedListed when checked
SunGoldPower's own statement, recorded exactly as printed: "Safety IEC62109-1, IEC62109-2 EMC EN61000-6-1, EN61000-6-3, FCC 15 class B" (PowerCore_18K-48_All-in-One_Solar_Charge_Inverter_User_Manual.pdf). A manufacturer statement names no certificate number or issuer and is not evidence of a listing; certificate documents SunGoldPower serves are recorded separately.
IEC62109-2Product / system scope unresolvedClaimedListed when checked
SunGoldPower's own statement, recorded exactly as printed: "Safety IEC62109-1, IEC62109-2 EMC EN61000-6-1, EN61000-6-3, FCC 15 class B" (PowerCore_18K-48_All-in-One_Solar_Charge_Inverter_User_Manual.pdf). A manufacturer statement names no certificate number or issuer and is not evidence of a listing; certificate documents SunGoldPower serves are recorded separately.
EN61000-6-1Product / system scope unresolvedClaimedListed when checked
SunGoldPower's own statement, recorded exactly as printed: "Safety IEC62109-1, IEC62109-2 EMC EN61000-6-1, EN61000-6-3, FCC 15 class B" (PowerCore_18K-48_All-in-One_Solar_Charge_Inverter_User_Manual.pdf). A manufacturer statement names no certificate number or issuer and is not evidence of a listing; certificate documents SunGoldPower serves are recorded separately.
EN61000-6-3Product / system scope unresolvedClaimedListed when checked
SunGoldPower's own statement, recorded exactly as printed: "Safety IEC62109-1, IEC62109-2 EMC EN61000-6-1, EN61000-6-3, FCC 15 class B" (PowerCore_18K-48_All-in-One_Solar_Charge_Inverter_User_Manual.pdf). A manufacturer statement names no certificate number or issuer and is not evidence of a listing; certificate documents SunGoldPower serves are recorded separately.
FCC 15 class BProduct / system scope unresolvedClaimedListed when checked
SunGoldPower's own statement, recorded exactly as printed: "Safety IEC62109-1, IEC62109-2 EMC EN61000-6-1, EN61000-6-3, FCC 15 class B" (PowerCore_18K-48_All-in-One_Solar_Charge_Inverter_User_Manual.pdf). A manufacturer statement names no certificate number or issuer and is not evidence of a listing; certificate documents SunGoldPower serves are recorded separately.
IEC62109-1Manufacturer claim · equipment listingClaimedListed when checked
SunGoldPower's own statement, recorded exactly as printed: "Safety IEC62109-1, IEC62109-2 EMC EN61000-6-1, EN61000-6-3, FCC 15 class B" (PowerCore_18K-48_All-in-One_Solar_Charge_Inverter_User_Manual.pdf). A manufacturer statement names no certificate number or issuer and is not evidence of a listing; certificate documents SunGoldPower serves are recorded separately.
IEC62109-2Manufacturer claim · equipment listingClaimedListed when checked
SunGoldPower's own statement, recorded exactly as printed: "Safety IEC62109-1, IEC62109-2 EMC EN61000-6-1, EN61000-6-3, FCC 15 class B" (PowerCore_18K-48_All-in-One_Solar_Charge_Inverter_User_Manual.pdf). A manufacturer statement names no certificate number or issuer and is not evidence of a listing; certificate documents SunGoldPower serves are recorded separately.
EN61000-6-1Manufacturer claim · equipment listingClaimedListed when checked
SunGoldPower's own statement, recorded exactly as printed: "Safety IEC62109-1, IEC62109-2 EMC EN61000-6-1, EN61000-6-3, FCC 15 class B" (PowerCore_18K-48_All-in-One_Solar_Charge_Inverter_User_Manual.pdf). A manufacturer statement names no certificate number or issuer and is not evidence of a listing; certificate documents SunGoldPower serves are recorded separately.
EN61000-6-3Manufacturer claim · equipment listingClaimedListed when checked
SunGoldPower's own statement, recorded exactly as printed: "Safety IEC62109-1, IEC62109-2 EMC EN61000-6-1, EN61000-6-3, FCC 15 class B" (PowerCore_18K-48_All-in-One_Solar_Charge_Inverter_User_Manual.pdf). A manufacturer statement names no certificate number or issuer and is not evidence of a listing; certificate documents SunGoldPower serves are recorded separately.
FCC 15 class BManufacturer claim · equipment listingClaimedListed when checked
SunGoldPower's own statement, recorded exactly as printed: "Safety IEC62109-1, IEC62109-2 EMC EN61000-6-1, EN61000-6-3, FCC 15 class B" (PowerCore_18K-48_All-in-One_Solar_Charge_Inverter_User_Manual.pdf). A manufacturer statement names no certificate number or issuer and is not evidence of a listing; certificate documents SunGoldPower serves are recorded separately.