Fronius
Grid-tie inverter

Fronius Primo GEN24 5.0 208-240

Key specs

Weight16.13 kg / 35.56 lb converted Check note
Efficiency97.6 %
Max PV voltage600 V
Weighted efficiency97 %
Continuous output5 kW
PV start voltage80 V

All specifications

Identity

BrandFronius · Website
ModelPrimo GEN24 5.0 208-240
MarketUS
Manufacturer SKU4,210,141,800
About brandFronius makes solar inverters and works in welding technology and battery charging. Its US Primo datasheet says the company began in 1945 as a one-man operation and lists Fronius USA LLC in Portage, Indiana; its GEN24 datasheet lists Fronius International GmbH in Wels, Austria.
SKU detail
locator: Embedded product data, ArticleNumber
conditions: Fronius article number, carried as "ArticleNumber" 4,210,141,800 in the product data embedded in the Fronius technical data page for "Primo GEN24 5.0 208-240" captured on September 24, 2026 (the page labels the field "Article number"). Greentech Renewables lists the same article number.
Sources: [1]
FieldValueConditionsSource
PhaseSingle-phase
The datasheet prints the mains connection as "Single phase 208 V / 220 V / 240 V"; the technical data page calls the Primo GEN24 "Our single-phase inverter".
Where: Datasheet, Output data, Mains connection
[2]
Weight16.13 kg / 35.56 lb converted Check note
Weight differs between two Fronius documents. Fronius's Primo GEN24 operating instructions print 35.56 lbs. (16.13 kg) for the 5.0 model, while the Fronius Primo GEN24 208-240 data sheet prints a different weight.
Printed as "Weight 35.56 lbs. (16.13 kg)" in Fronius's Fronius Primo GEN24 3.8 - 6.0 kW / Plus / SC 208 - 240 Operating instructions (026-07092026), Appendix, Technical data, Fronius Primo GEN24 5.0 208 – 240 / 5.0 208 – 240 Plus table, Weight row. Revised on 1 October 2026: The operating instructions print 35.56 lbs. (16.13 kg) for this model; the recorded figure is from the data sheet.
Where: Appendix, Technical data, Fronius Primo GEN24 5.0 208 – 240 / 5.0 208 – 240 Plus table, Weight row
Sources
15.08 kg

Printed as "35.56 lbs. / 15.08 kg" in the Fronius Primo GEN24 208-240 datasheet for the 3.8/5.0/6.0 kW models. The technical data page prints "Weight 33,25 lb" for this model.

[2]
[3]
MPPT count2
Printed as "Number of MPP trackers 2" on the Fronius technical data page captured on September 24, 2026.
Where: Technical Data, Input Data
[1]
DimensionsW 474 × H 516 × D 165 mm / W 18.7 × H 20.3 × D 6.5 in converted Check note
Dimensions differ between two Fronius documents. Fronius's Primo GEN24 operating instructions print 516 × 474 × 165 mm for the 5.0 model, while the Fronius Primo GEN24 208-240 data sheet prints a different size.
Printed as "(516 × 474 × 165 mm)" in Fronius's Fronius Primo GEN24 3.8 - 6.0 kW / Plus / SC 208 - 240 Operating instructions (026-07092026), Appendix, Technical data, Fronius Primo GEN24 5.0 208 – 240 / 5.0 208 – 240 Plus table, Dimensions H × W × D row. Revised on 1 October 2026: The operating instructions print the unit dimensions as 516 × 474 × 165 mm (H x W x D) for this model; the recorded figure is from the data sheet.
Where: Appendix, Technical data, Fronius Primo GEN24 5.0 208 – 240 / 5.0 208 – 240 Plus table, Dimensions H × W × D row
Sources
W 474 × H 518 × D 164 mm

Printed in millimeters (height x width x depth) in the Fronius Primo GEN24 208-240 datasheet for the 3.8/5.0/6.0 kW models.

[2]
[3]
Efficiency97.6 %
Maximum efficiency at 240 Vac, read from the second model (5.0) of the datasheet's 3.8/5.0/6.0 kW table, 240 Vac column.
Where: Datasheet, 3.8/5.0/6.0 kW table, Efficiency
[2]
MPPT voltage230 to 480 V
Printed as "MPP voltage range 230 – 480 V" in Fronius's Fronius Primo GEN24 3.8 - 6.0 kW / Plus / SC 208 - 240 Operating instructions (026-07092026), Appendix, Technical data, Fronius Primo GEN24 5.0 208 – 240 / 5.0 208 – 240 Plus table, MPP voltage range row. Re-cited on 1 October 2026 to the manufacturer's own document; previously cited to Fronius International GmbH (fronius.com), which stays listed as an additional source.
Where: Appendix, Technical data, Fronius Primo GEN24 5.0 208 – 240 / 5.0 208 – 240 Plus table, MPP voltage range row
[3] [1]
Solar array7 500 W at 208 V, 6 800 W at 220 V, 7 500 W at 240 V
Printed as "Max. PV array power at 208 V at 220 V at 240 V 7 500 W 6 800 W 7 500 W" in Fronius's Fronius Primo GEN24 3.8 - 6.0 kW / Plus / SC 208 - 240 Operating instructions (026-07092026), Appendix, Technical data, Fronius Primo GEN24 5.0 208 – 240 / 5.0 208 – 240 Plus table, Max. PV array power at 208 V, 220 V and 240 V row. The manual calls it the maximum PV array power; the figure differs by grid voltage, so it is kept as printed.
Where: Appendix, Technical data, Fronius Primo GEN24 5.0 208 – 240 / 5.0 208 – 240 Plus table, Max. PV array power at 208 V, 220 V and 240 V row
[3]
Solar input5.15 kW
Maximum PV input power, printed as "Maximum PV input power 5150 W" on the Fronius technical data page captured on September 24, 2026; expressed in kW. The datasheet calls the same figure "Max. usable DC power".
Where: Technical Data, Input Data
[1]
Enclosure ratingType 4X
Printed as "Protection class Type 4X" in Fronius's Fronius Primo GEN24 3.8 - 6.0 kW / Plus / SC 208 - 240 Operating instructions (026-07092026), Appendix, Technical data, Fronius Primo GEN24 5.0 208 – 240 / 5.0 208 – 240 Plus table, Protection class row. Re-cited on 1 October 2026 to the manufacturer's own document; previously cited to Fronius International GmbH (fronius.com), which stays listed as an additional source.
Where: Appendix, Technical data, Fronius Primo GEN24 5.0 208 – 240 / 5.0 208 – 240 Plus table, Protection class row
[3] [2]
Max PV currentPV 1: 22 A; PV 2: 12 A
Printed as "Max. input current PV 1 PV 2 22 A 12 A" in Fronius's Fronius Primo GEN24 3.8 - 6.0 kW / Plus / SC 208 - 240 Operating instructions (026-07092026), Appendix, Technical data, Fronius Primo GEN24 5.0 208 – 240 / 5.0 208 – 240 Plus table, Max. input current PV 1 / PV 2 row.
Where: Appendix, Technical data, Fronius Primo GEN24 5.0 208 – 240 / 5.0 208 – 240 Plus table, Max. input current PV 1 / PV 2 row
[3]
Max PV voltage600 V
Printed as "Max. input voltage at 1 000 W/m²/14 °F in an open circuit 600 V" in Fronius's Fronius Primo GEN24 3.8 - 6.0 kW / Plus / SC 208 - 240 Operating instructions (026-07092026), Appendix, Technical data, Fronius Primo GEN24 5.0 208 – 240 / 5.0 208 – 240 Plus table, Max. input voltage in an open circuit row.
Where: Appendix, Technical data, Fronius Primo GEN24 5.0 208 – 240 / 5.0 208 – 240 Plus table, Max. input voltage in an open circuit row
[3]
Apparent power5,000 VA
Apparent power at 240 Vac, read from the second model (5.0) of the datasheet's 3.8/5.0/6.0 kW table, 240 Vac column: 5,000 VA.
Where: Datasheet, 3.8/5.0/6.0 kW table, Output data, Apparent power
[2]
Idle consumption10 W
Less than 10 W
Printed as "Night consumption W < 10" in the Fronius Primo GEN24 208-240 datasheet; an upper bound ("less than 10 W"), not a measured value.
Where: Datasheet, General data
[2]
PV start voltage80 V
Printed as "Start-up input voltage 80 V" in Fronius's Fronius Primo GEN24 3.8 - 6.0 kW / Plus / SC 208 - 240 Operating instructions (026-07092026), Appendix, Technical data, Fronius Primo GEN24 5.0 208 – 240 / 5.0 208 – 240 Plus table, Start-up input voltage row. Re-cited on 1 October 2026 to the manufacturer's own document; previously cited to Fronius International GmbH (fronius.com), which stays listed as an additional source.
Where: Appendix, Technical data, Fronius Primo GEN24 5.0 208 – 240 / 5.0 208 – 240 Plus table, Start-up input voltage row
[3] [1]
Night consumption8.2 W at 208 V, 8.2 W at 220 V, 8.3 W at 240 V
Printed as "Night tare loss at 208 V at 220 V at 240 V 8.2 W 8.2 W 8.3 W" in Fronius's Fronius Primo GEN24 3.8 - 6.0 kW / Plus / SC 208 - 240 Operating instructions (026-07092026), Appendix, Technical data, Fronius Primo GEN24 5.0 208 – 240 / 5.0 208 – 240 Plus table, Night tare loss at 208 V, 220 V and 240 V row.
Where: Appendix, Technical data, Fronius Primo GEN24 5.0 208 – 240 / 5.0 208 – 240 Plus table, Night tare loss at 208 V, 220 V and 240 V row
[3]
Continuous output5 kW
Printed as "Max. output power at 208 V at 220 V at 240 V 5 000 W 5 000 W 5 000 W" in Fronius's Fronius Primo GEN24 3.8 - 6.0 kW / Plus / SC 208 - 240 Operating instructions (026-07092026), Appendix, Technical data, Fronius Primo GEN24 5.0 208 – 240 / 5.0 208 – 240 Plus table, Max. output power at 208 V, 220 V and 240 V row. The same figure is printed at all three grid voltages. Re-cited on 1 October 2026 to the manufacturer's own document; previously cited to Fronius International GmbH (fronius.com), which stays listed as an additional source.
Where: Appendix, Technical data, Fronius Primo GEN24 5.0 208 – 240 / 5.0 208 – 240 Plus table, Max. output power at 208 V, 220 V and 240 V row
[3] [2]
Max PV short circuitPV 1: 36 A; PV 2: 19 A; total 55 A
Printed as "PV 1 PV 2 36 A 19 A" and "(I SC PV1 + I SC PV2 = I SC max ) 55 A" in Fronius's Fronius Primo GEN24 3.8 - 6.0 kW / Plus / SC 208 - 240 Operating instructions (026-07092026), Appendix, Technical data, Fronius Primo GEN24 5.0 208 – 240 / 5.0 208 – 240 Plus table, Max. short circuit current for module array (I SC PV) PV 1 / PV 2 and Max. total short circuit current row.
Where: Appendix, Technical data, Fronius Primo GEN24 5.0 208 – 240 / 5.0 208 – 240 Plus table, Max. short circuit current for module array (I SC PV) PV 1 / PV 2 and Max. total short circuit current row
[3]
Operating temperature-40 to 60 °C / -40 to 140 °F converted
Printed as "Permitted ambient temperature -40 °F – +140 °F (-40 °C – +60 °C)" in Fronius's Fronius Primo GEN24 3.8 - 6.0 kW / Plus / SC 208 - 240 Operating instructions (026-07092026), Appendix, Technical data, Fronius Primo GEN24 5.0 208 – 240 / 5.0 208 – 240 Plus table, Permitted ambient temperature row. Re-cited on 1 October 2026 to the manufacturer's own document; previously cited to Fronius International GmbH (fronius.com), which stays listed as an additional source.
Where: Appendix, Technical data, Fronius Primo GEN24 5.0 208 – 240 / 5.0 208 – 240 Plus table, Permitted ambient temperature row
[3] [2]
Weighted efficiency97 %
Printed as "CEC efficiency at 208 V at 220 V at 240 V 97 % 97 % 97 %" in Fronius's Fronius Primo GEN24 3.8 - 6.0 kW / Plus / SC 208 - 240 Operating instructions (026-07092026), Appendix, Technical data, Fronius Primo GEN24 5.0 208 – 240 / 5.0 208 – 240 Plus table, CEC efficiency at 208 V, 220 V and 240 V row. The same figure is printed at all three grid voltages. Re-cited on 1 October 2026 to the manufacturer's own document; previously cited to Fronius International GmbH (fronius.com), which stays listed as an additional source.
Where: Appendix, Technical data, Fronius Primo GEN24 5.0 208 – 240 / 5.0 208 – 240 Plus table, CEC efficiency at 208 V, 220 V and 240 V row
[3] [2]
AC voltage configurationSingle phase 208 V / 220 V / 240 V (-12 / +10%) V
Literal mains connection printed in the Fronius Primo GEN24 208-240 datasheet, one value across the models of the table.
Where: Datasheet, Output data, Mains connection
[2]

Owner reviews

No owner reviews yet
Write a review

Sellers

No listed sellers in this data.

Price history

No seller price history.

Quick reference sheet

Continuous output
5 kW
Battery voltage
Not stated
Solar input
7 500 W at 208 V, 6 800 W at 220 V, 7 500 W at 240 VMPPT trackers 2MPPT range 230 to 480 V
AC output
Not stated
Warranty
Not stated
Size
40.36 L* (Calculated from published dimensions)W: 474 × H: 516 × D: 165 mm / W: 18.7 × H: 20.3 × D: 6.5 inWeight 16.13 kg / 35.56 lb

Evidence score

15/100Missing details55% documented

The Evidence score uses the priorities you choose. It counts published documents, such as certificates and warranty terms, and it compares a documented figure with the best documented figure of the same kind. It does not count owner reviews, and it is not a verdict on product quality or on how many people have reviewed it. A low score can mean little is documented, or that a documented figure is below the best of its kind. Undisclosed data scores 0.

Missing details. This number counts only the evidence recorded so far. The source review for this product is not finished, or the maker has not disclosed enough, so the number can only go up.

Missing for this product: Warranty term needed; Battery conversion efficiency needed.

Each input is scored against the best documented value for an inverter: warranty term and battery conversion efficiency against every published inverter, idle consumption (lower is better) against the inverters in the same output band, or against every published inverter when the output is not documented. A documented value always earns points; an undisclosed one earns 0 and is listed as missing. Researched products receive a score. Certificates earn points for the evidence itself. Size and weight do not affect scores.

CertificatesUL 1741 SB +15Claimed14.2 / 45.0

Manufacturer claim; issuer verification pending. Applies to the exact inverter.

[4]

Idle consumption10 W1.0 / 10.0

10 against 1 W, the lowest documented for an inverter in the 3.5 to 7 kW output band (printed by the maker): Fronius Primo 3.8-1 208-240. The bar is a printed bound: less than 1 W, as printed.

Printed as "Night consumption W < 10" in the Fronius Primo GEN24 208-240 datasheet; an upper bound ("less than 10 W"), not a measured value. Printed as a bound: less than 10 W, as printed.

[2]

Research pending, 0 points: Warranty term, Battery conversion efficiency.

Warranty term and battery conversion efficiency are compared with every published inverter; idle consumption with the inverters in the same 3.5 to 7 kW output band. · Method version 0.5

How it works

Certificates

What this shows: what each record says and how far it reaches. It does not mean the product is approved.
UL 1741 Third Edition (incl. UL1741 Supplement SA and SB)manufacturer claimpresent at observation[2]
Scope
equipment listing
Covered models
Primo GEN24 5.0 208-240
Limitations
The Fronius Primo GEN24 208-240 datasheet (EN V09 Aug 2025), in a table shared by the GEN24 and GEN24 Plus, lists "UL 1741 Third Edition (incl. UL1741 Supplement SA and SB)" under its certificates and compliance with standards for Primo GEN24 5.0 208-240. This is recorded as the manufacturer's claim exactly as printed. No certificate number, certification body, file number or issuer directory record was read, so the listing, its scope and its current status are not independently established.
Record detail
Issued: Not stated
Valid from: Not stated
Expiry: Not stated
Not checked
Source
[2]
UL CRD - Non-Isolated EPS Interactive PV Inverters Rated Less Than 30kVAmanufacturer claimpresent at observation[2]
Scope
equipment listing
Covered models
Primo GEN24 5.0 208-240
Limitations
The Fronius Primo GEN24 208-240 datasheet (EN V09 Aug 2025), in a table shared by the GEN24 and GEN24 Plus, lists "UL CRD - Non-Isolated EPS Interactive PV Inverters Rated Less Than 30kVA" under its certificates and compliance with standards for Primo GEN24 5.0 208-240. This is recorded as the manufacturer's claim exactly as printed. No certificate number, certification body, file number or issuer directory record was read, so the listing, its scope and its current status are not independently established.
Record detail
Issued: Not stated
Valid from: Not stated
Expiry: Not stated
Not checked
Source
[2]
UL1998 (for functions: AFCI, RCMU, PVRSE and isolation monitoring)manufacturer claimpresent at observation[2]
Scope
equipment listing
Covered models
Primo GEN24 5.0 208-240
Limitations
The Fronius Primo GEN24 208-240 datasheet (EN V09 Aug 2025), in a table shared by the GEN24 and GEN24 Plus, lists "UL1998 (for functions: AFCI, RCMU, PVRSE and isolation monitoring)" under its certificates and compliance with standards for Primo GEN24 5.0 208-240. This is recorded as the manufacturer's claim exactly as printed. No certificate number, certification body, file number or issuer directory record was read, so the listing, its scope and its current status are not independently established.
Record detail
Issued: Not stated
Valid from: Not stated
Expiry: Not stated
Not checked
Source
[2]
IEEE 1547:2018 incl. IEEE 1547a:2020manufacturer claimpresent at observation[2]
Scope
equipment listing
Covered models
Primo GEN24 5.0 208-240
Limitations
The Fronius Primo GEN24 208-240 datasheet (EN V09 Aug 2025), in a table shared by the GEN24 and GEN24 Plus, lists "IEEE 1547:2018 incl. IEEE 1547a:2020" under its certificates and compliance with standards for Primo GEN24 5.0 208-240. This is recorded as the manufacturer's claim exactly as printed. No certificate number, certification body, file number or issuer directory record was read, so the listing, its scope and its current status are not independently established.
Record detail
Issued: Not stated
Valid from: Not stated
Expiry: Not stated
Not checked
Source
[2]
IEEE 1547.1:2020manufacturer claimpresent at observation[2]
Scope
equipment listing
Covered models
Primo GEN24 5.0 208-240
Limitations
The Fronius Primo GEN24 208-240 datasheet (EN V09 Aug 2025), in a table shared by the GEN24 and GEN24 Plus, lists "IEEE 1547.1:2020" under its certificates and compliance with standards for Primo GEN24 5.0 208-240. This is recorded as the manufacturer's claim exactly as printed. No certificate number, certification body, file number or issuer directory record was read, so the listing, its scope and its current status are not independently established.
Record detail
Issued: Not stated
Valid from: Not stated
Expiry: Not stated
Not checked
Source
[2]
IEEE 1547:2003 incl. IEEE 1547.1:2005manufacturer claimpresent at observation[2]
Scope
equipment listing
Covered models
Primo GEN24 5.0 208-240
Limitations
The Fronius Primo GEN24 208-240 datasheet (EN V09 Aug 2025), in a table shared by the GEN24 and GEN24 Plus, lists "IEEE 1547:2003 incl. IEEE 1547.1:2005" under its certificates and compliance with standards for Primo GEN24 5.0 208-240. This is recorded as the manufacturer's claim exactly as printed. No certificate number, certification body, file number or issuer directory record was read, so the listing, its scope and its current status are not independently established.
Record detail
Issued: Not stated
Valid from: Not stated
Expiry: Not stated
Not checked
Source
[2]
ANSI/IEEE C62.41manufacturer claimpresent at observation[2]
Scope
equipment listing
Covered models
Primo GEN24 5.0 208-240
Limitations
The Fronius Primo GEN24 208-240 datasheet (EN V09 Aug 2025), in a table shared by the GEN24 and GEN24 Plus, lists "ANSI/IEEE C62.41" under its certificates and compliance with standards for Primo GEN24 5.0 208-240. This is recorded as the manufacturer's claim exactly as printed. No certificate number, certification body, file number or issuer directory record was read, so the listing, its scope and its current status are not independently established.
Record detail
Issued: Not stated
Valid from: Not stated
Expiry: Not stated
Not checked
Source
[2]
FCC Part 15 A & Bmanufacturer claimpresent at observation[2]
Scope
equipment listing
Covered models
Primo GEN24 5.0 208-240
Limitations
The Fronius Primo GEN24 208-240 datasheet (EN V09 Aug 2025), in a table shared by the GEN24 and GEN24 Plus, lists "FCC Part 15 A & B" under its certificates and compliance with standards for Primo GEN24 5.0 208-240. This is recorded as the manufacturer's claim exactly as printed. No certificate number, certification body, file number or issuer directory record was read, so the listing, its scope and its current status are not independently established.
Record detail
Issued: Not stated
Valid from: Not stated
Expiry: Not stated
Not checked
Source
[2]
CSA C22. 2 No. 107.1-16 (reaffirmed 2021)manufacturer claimpresent at observation[2]
Scope
equipment listing
Covered models
Primo GEN24 5.0 208-240
Limitations
The Fronius Primo GEN24 208-240 datasheet (EN V09 Aug 2025), in a table shared by the GEN24 and GEN24 Plus, lists "CSA C22. 2 No. 107.1-16 (reaffirmed 2021)" under its certificates and compliance with standards for Primo GEN24 5.0 208-240. This is recorded as the manufacturer's claim exactly as printed. No certificate number, certification body, file number or issuer directory record was read, so the listing, its scope and its current status are not independently established.
Record detail
Issued: Not stated
Valid from: Not stated
Expiry: Not stated
Not checked
Source
[2]
CSA C22.2 No.290-19manufacturer claimpresent at observation[2]
Scope
equipment listing
Covered models
Primo GEN24 5.0 208-240
Limitations
The Fronius Primo GEN24 208-240 datasheet (EN V09 Aug 2025), in a table shared by the GEN24 and GEN24 Plus, lists "CSA C22.2 No.290-19" under its certificates and compliance with standards for Primo GEN24 5.0 208-240. This is recorded as the manufacturer's claim exactly as printed. No certificate number, certification body, file number or issuer directory record was read, so the listing, its scope and its current status are not independently established.
Record detail
Issued: Not stated
Valid from: Not stated
Expiry: Not stated
Not checked
Source
[2]
CSA C22.2 No.330-23manufacturer claimpresent at observation[2]
Scope
equipment listing
Covered models
Primo GEN24 5.0 208-240
Limitations
The Fronius Primo GEN24 208-240 datasheet (EN V09 Aug 2025), in a table shared by the GEN24 and GEN24 Plus, lists "CSA C22.2 No.330-23" under its certificates and compliance with standards for Primo GEN24 5.0 208-240. This is recorded as the manufacturer's claim exactly as printed. No certificate number, certification body, file number or issuer directory record was read, so the listing, its scope and its current status are not independently established.
Record detail
Issued: Not stated
Valid from: Not stated
Expiry: Not stated
Not checked
Source
[2]
CSA C22.3 No.9:20manufacturer claimpresent at observation[2]
Scope
equipment listing
Covered models
Primo GEN24 5.0 208-240
Limitations
The Fronius Primo GEN24 208-240 datasheet (EN V09 Aug 2025), in a table shared by the GEN24 and GEN24 Plus, lists "CSA C22.3 No.9:20" under its certificates and compliance with standards for Primo GEN24 5.0 208-240. This is recorded as the manufacturer's claim exactly as printed. No certificate number, certification body, file number or issuer directory record was read, so the listing, its scope and its current status are not independently established.
Record detail
Issued: Not stated
Valid from: Not stated
Expiry: Not stated
Not checked
Source
[2]
UL1699B:2021manufacturer claimpresent at observation[2]
Scope
equipment listing
Covered models
Primo GEN24 5.0 208-240
Limitations
The Fronius Primo GEN24 208-240 datasheet (EN V09 Aug 2025), in a table shared by the GEN24 and GEN24 Plus, lists "UL1699B:2021" under its certificates and compliance with standards for Primo GEN24 5.0 208-240. This is recorded as the manufacturer's claim exactly as printed. No certificate number, certification body, file number or issuer directory record was read, so the listing, its scope and its current status are not independently established.
Record detail
Issued: Not stated
Valid from: Not stated
Expiry: Not stated
Not checked
Source
[2]
UL 1741 SAauthority listing reportedlisted as of snapshot[4]
Scope
equipment listing
Covered models
Primo GEN24 5.0 208-240
Limitations
Listed on the California Energy Commission Grid Support Solar Inverter List (data unchanged since October 1, 2026; downloaded October 11, 2026) as Fronius International GmbH "Primo GEN24 5.0 208-240 {208V}": UL 1741 SA, certifying entity CSA Group, CEC listing date 2021-11-12. A state equipment list entry, not the certification body's own record.
Record detail
Issued: Not stated
Valid from: Nov 12, 2021
Expiry: Not stated
Issuer checked: Oct 11, 2026
Source
[4]
UL 1741 SBauthority listing reportedlisted as of snapshot[4]
Scope
equipment listing
Covered models
Primo GEN24 5.0 208-240
Limitations
Listed on the California Energy Commission Grid Support Solar Inverter List (data unchanged since October 1, 2026; downloaded October 11, 2026) as Fronius International GmbH "Primo GEN24 5.0 208-240 {208V}": UL 1741 SB, certifying entity CSA Group, certificate date 2025-04-09, CEC listing date 2021-11-12. A state equipment list entry, not the certification body's own record.
Record detail
Issued: Not stated
Valid from: Apr 9, 2025
Expiry: Not stated
Issuer checked: Oct 11, 2026
Source
[4]
CECauthority listing reportedlisted as of snapshot[4]
Scope
equipment listing
Covered models
Primo GEN24 5.0 208-240
Limitations
Model Primo GEN24 5.0 208-240 listed on the California Energy Commission Grid Support Battery Inverter List (data unchanged since October 1, 2026; downloaded October 11, 2026) under Fronius International GmbH, as "Primo GEN24 5.0 208-240 {208V}"; "Primo GEN24 5.0 208-240 {240V}", CEC listing date 2021-11-12. This is an equipment listing, not UL certification or complete-system approval.
Record detail
Issued: Not stated
Valid from: Nov 12, 2021
Expiry: Not stated
Issuer checked: Oct 11, 2026
Source
[4]
CECauthority listing reportedlisted as of snapshot[4]
Scope
equipment listing
Covered models
Primo GEN24 5.0 208-240
Limitations
Model Primo GEN24 5.0 208-240 listed on the California Energy Commission Grid Support Solar Inverter List (data unchanged since October 1, 2026; downloaded October 11, 2026) under Fronius International GmbH, as "Primo GEN24 5.0 208-240 {208V}"; "Primo GEN24 5.0 208-240 {240V}", CEC listing date 2021-11-12. This is an equipment listing, not UL certification or complete-system approval.
Record detail
Issued: Not stated
Valid from: Nov 12, 2021
Expiry: Not stated
Issuer checked: Oct 11, 2026
Source
[4]

Warranty

Unknown: no warranty facts recorded.

Recalls / legal notices

No recalls on file. All notices · Report a notice

This register is incomplete. A missing notice does not establish that a product has no recalls.

Documents

  • Manuals

  • Fronius Fronius Primo GEN24 3.8 - 6.0 kW / Plus / SC 208 - 240 Operating instructions (026-07092026)Official · Fronius · Official user manual · September 2026 · Web page
    Source details
    Revision
    026-07092026
    Revision date
    September 2026

    Archived copy captured on 2026-10-01.

    Location: Appendix, Technical data, tables headed Fronius Primo GEN24 3.8, 5.0 and 6.0 208 – 240 / 208 – 240 Plus

    Retrieved Oct 1, 2026

    Fronius's own operating instructions for the Fronius Primo GEN24 3.8 - 6.0 kW 208 - 240, Plus and SC models, captured 1 October 2026 from manuals.fronius.com; revision printed as 026-07092026. The technical data appendix has tables for the Primo GEN24 3.8, 5.0 and 6.0 208 - 240 (and Plus). Manufacturer instructions, not independent tests.

    Open
  • Datasheets

  • Fronius datasheet: Fronius Primo GEN24 208-240 and GEN24 208-240 Plus (EN V09 Aug 2025)Official · Fronius International GmbH · Official datasheet · PDF
    Certificate & compliance claims (13)
    UL 1741 Third Edition (incl. UL1741 Supplement SA and SB)Manufacturer claim · equipment listingClaimedListed when checked

    The Fronius Primo GEN24 208-240 datasheet (EN V09 Aug 2025), in a table shared by the GEN24 and GEN24 Plus, lists "UL 1741 Third Edition (incl. UL1741 Supplement SA and SB)" under its certificates and compliance with standards for Primo GEN24 5.0 208-240. This is recorded as the manufacturer's claim exactly as printed. No certificate number, certification body, file number or issuer directory record was read, so the listing, its scope and its current status are not independently established.

    Manufacturer document

    Official datasheet: Fronius datasheet: Fronius Primo GEN24 208-240 and GEN24 208-240 Plus (EN V09 Aug 2025)
    UL CRD - Non-Isolated EPS Interactive PV Inverters Rated Less Than 30kVAManufacturer claim · equipment listingClaimedListed when checked

    The Fronius Primo GEN24 208-240 datasheet (EN V09 Aug 2025), in a table shared by the GEN24 and GEN24 Plus, lists "UL CRD - Non-Isolated EPS Interactive PV Inverters Rated Less Than 30kVA" under its certificates and compliance with standards for Primo GEN24 5.0 208-240. This is recorded as the manufacturer's claim exactly as printed. No certificate number, certification body, file number or issuer directory record was read, so the listing, its scope and its current status are not independently established.

    Manufacturer document

    Official datasheet: Fronius datasheet: Fronius Primo GEN24 208-240 and GEN24 208-240 Plus (EN V09 Aug 2025)
    UL1998 (for functions: AFCI, RCMU, PVRSE and isolation monitoring)Manufacturer claim · equipment listingClaimedListed when checked

    The Fronius Primo GEN24 208-240 datasheet (EN V09 Aug 2025), in a table shared by the GEN24 and GEN24 Plus, lists "UL1998 (for functions: AFCI, RCMU, PVRSE and isolation monitoring)" under its certificates and compliance with standards for Primo GEN24 5.0 208-240. This is recorded as the manufacturer's claim exactly as printed. No certificate number, certification body, file number or issuer directory record was read, so the listing, its scope and its current status are not independently established.

    Manufacturer document

    Official datasheet: Fronius datasheet: Fronius Primo GEN24 208-240 and GEN24 208-240 Plus (EN V09 Aug 2025)
    IEEE 1547:2018 incl. IEEE 1547a:2020Manufacturer claim · equipment listingClaimedListed when checked

    The Fronius Primo GEN24 208-240 datasheet (EN V09 Aug 2025), in a table shared by the GEN24 and GEN24 Plus, lists "IEEE 1547:2018 incl. IEEE 1547a:2020" under its certificates and compliance with standards for Primo GEN24 5.0 208-240. This is recorded as the manufacturer's claim exactly as printed. No certificate number, certification body, file number or issuer directory record was read, so the listing, its scope and its current status are not independently established.

    Manufacturer document

    Official datasheet: Fronius datasheet: Fronius Primo GEN24 208-240 and GEN24 208-240 Plus (EN V09 Aug 2025)
    IEEE 1547.1:2020Manufacturer claim · equipment listingClaimedListed when checked

    The Fronius Primo GEN24 208-240 datasheet (EN V09 Aug 2025), in a table shared by the GEN24 and GEN24 Plus, lists "IEEE 1547.1:2020" under its certificates and compliance with standards for Primo GEN24 5.0 208-240. This is recorded as the manufacturer's claim exactly as printed. No certificate number, certification body, file number or issuer directory record was read, so the listing, its scope and its current status are not independently established.

    Manufacturer document

    Official datasheet: Fronius datasheet: Fronius Primo GEN24 208-240 and GEN24 208-240 Plus (EN V09 Aug 2025)
    IEEE 1547:2003 incl. IEEE 1547.1:2005Manufacturer claim · equipment listingClaimedListed when checked

    The Fronius Primo GEN24 208-240 datasheet (EN V09 Aug 2025), in a table shared by the GEN24 and GEN24 Plus, lists "IEEE 1547:2003 incl. IEEE 1547.1:2005" under its certificates and compliance with standards for Primo GEN24 5.0 208-240. This is recorded as the manufacturer's claim exactly as printed. No certificate number, certification body, file number or issuer directory record was read, so the listing, its scope and its current status are not independently established.

    Manufacturer document

    Official datasheet: Fronius datasheet: Fronius Primo GEN24 208-240 and GEN24 208-240 Plus (EN V09 Aug 2025)
    ANSI/IEEE C62.41Manufacturer claim · equipment listingClaimedListed when checked

    The Fronius Primo GEN24 208-240 datasheet (EN V09 Aug 2025), in a table shared by the GEN24 and GEN24 Plus, lists "ANSI/IEEE C62.41" under its certificates and compliance with standards for Primo GEN24 5.0 208-240. This is recorded as the manufacturer's claim exactly as printed. No certificate number, certification body, file number or issuer directory record was read, so the listing, its scope and its current status are not independently established.

    Manufacturer document

    Official datasheet: Fronius datasheet: Fronius Primo GEN24 208-240 and GEN24 208-240 Plus (EN V09 Aug 2025)
    FCC Part 15 A & BManufacturer claim · equipment listingClaimedListed when checked

    The Fronius Primo GEN24 208-240 datasheet (EN V09 Aug 2025), in a table shared by the GEN24 and GEN24 Plus, lists "FCC Part 15 A & B" under its certificates and compliance with standards for Primo GEN24 5.0 208-240. This is recorded as the manufacturer's claim exactly as printed. No certificate number, certification body, file number or issuer directory record was read, so the listing, its scope and its current status are not independently established.

    Manufacturer document

    Official datasheet: Fronius datasheet: Fronius Primo GEN24 208-240 and GEN24 208-240 Plus (EN V09 Aug 2025)
    CSA C22. 2 No. 107.1-16 (reaffirmed 2021)Manufacturer claim · equipment listingClaimedListed when checked

    The Fronius Primo GEN24 208-240 datasheet (EN V09 Aug 2025), in a table shared by the GEN24 and GEN24 Plus, lists "CSA C22. 2 No. 107.1-16 (reaffirmed 2021)" under its certificates and compliance with standards for Primo GEN24 5.0 208-240. This is recorded as the manufacturer's claim exactly as printed. No certificate number, certification body, file number or issuer directory record was read, so the listing, its scope and its current status are not independently established.

    Manufacturer document

    Official datasheet: Fronius datasheet: Fronius Primo GEN24 208-240 and GEN24 208-240 Plus (EN V09 Aug 2025)
    CSA C22.2 No.290-19Manufacturer claim · equipment listingClaimedListed when checked

    The Fronius Primo GEN24 208-240 datasheet (EN V09 Aug 2025), in a table shared by the GEN24 and GEN24 Plus, lists "CSA C22.2 No.290-19" under its certificates and compliance with standards for Primo GEN24 5.0 208-240. This is recorded as the manufacturer's claim exactly as printed. No certificate number, certification body, file number or issuer directory record was read, so the listing, its scope and its current status are not independently established.

    Manufacturer document

    Official datasheet: Fronius datasheet: Fronius Primo GEN24 208-240 and GEN24 208-240 Plus (EN V09 Aug 2025)
    CSA C22.2 No.330-23Manufacturer claim · equipment listingClaimedListed when checked

    The Fronius Primo GEN24 208-240 datasheet (EN V09 Aug 2025), in a table shared by the GEN24 and GEN24 Plus, lists "CSA C22.2 No.330-23" under its certificates and compliance with standards for Primo GEN24 5.0 208-240. This is recorded as the manufacturer's claim exactly as printed. No certificate number, certification body, file number or issuer directory record was read, so the listing, its scope and its current status are not independently established.

    Manufacturer document

    Official datasheet: Fronius datasheet: Fronius Primo GEN24 208-240 and GEN24 208-240 Plus (EN V09 Aug 2025)
    CSA C22.3 No.9:20Manufacturer claim · equipment listingClaimedListed when checked

    The Fronius Primo GEN24 208-240 datasheet (EN V09 Aug 2025), in a table shared by the GEN24 and GEN24 Plus, lists "CSA C22.3 No.9:20" under its certificates and compliance with standards for Primo GEN24 5.0 208-240. This is recorded as the manufacturer's claim exactly as printed. No certificate number, certification body, file number or issuer directory record was read, so the listing, its scope and its current status are not independently established.

    Manufacturer document

    Official datasheet: Fronius datasheet: Fronius Primo GEN24 208-240 and GEN24 208-240 Plus (EN V09 Aug 2025)
    UL1699B:2021Manufacturer claim · equipment listingClaimedListed when checked

    The Fronius Primo GEN24 208-240 datasheet (EN V09 Aug 2025), in a table shared by the GEN24 and GEN24 Plus, lists "UL1699B:2021" under its certificates and compliance with standards for Primo GEN24 5.0 208-240. This is recorded as the manufacturer's claim exactly as printed. No certificate number, certification body, file number or issuer directory record was read, so the listing, its scope and its current status are not independently established.

    Manufacturer document

    Official datasheet: Fronius datasheet: Fronius Primo GEN24 208-240 and GEN24 208-240 Plus (EN V09 Aug 2025)
    Source details
    Revision
    EN V09 Aug 2025
    Revision date
    Not stated

    Captured by scripts/prepare-brand-sweep-sep21.mjs on 2026-09-24.

    Location: Technical data 3.8/5.0/6.0 kW and 7.7/10.0 kW tables

    Retrieved Sep 23, 2026

    US datasheet for the Primo GEN24 208-240 and GEN24 208-240 Plus, 3.8 to 10.0 kW, fetched from www.fronius.com and archived on September 24, 2026. Each table covers several models with three AC voltage columns each (208, 220 and 240 Vac), so every figure is read from the named model and voltage columns and the whole row is quoted. The same tables describe the GEN24 and the GEN24 Plus; battery and Full Backup data apply only after the UP.storage software upgrade that the datasheet says turns a GEN24 into a GEN24 Plus. It names models, not article numbers. Its standards list is a manufacturer claim that no issuer record was read against.

    Archived copies

    Archived copy of a document published by Fronius International GmbH. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email [email protected].

    Archived backupEN V09 Aug 2025 · 2.12 MB

    Archived copy, unaltered, kept as a record of what Fronius International GmbH published. Original address: https://www.fronius.com/en/~/downloads/Solar%20Energy/Datasheets/SE_DS_Fronius_GEN24_Plus_208_240_EN_US.pdf. Copyright and takedown

    Source first found
    This copy captured
    Archived
    File detailsOriginal source
    Embedded creation date
    Embedded modification date
    Pages
    8

    Embedded dates are file metadata, not independent proof of publication.

    SHA-256: b147ed4ce8d91627887af52e94aa2fd281e7c26939545ea1bf4e839b3e89b164

    Open
  • Other documents

  • Primo GEN24 5.0 208-240 | Fronius USA technical data page (September 24, 2026 capture)Official · Fronius International GmbH · Official product page · Web page
    Source details
    Revision
    Not stated
    Revision date
    Not stated

    Captured by scripts/prepare-brand-sweep-sep21.mjs on 2026-09-24.

    Location: Technical Data table; embedded product data "ArticleNumber"

    Retrieved Sep 23, 2026

    Fronius USA technical data page on www.fronius.com, captured byte for byte on September 24, 2026. The visible page prints the Fronius Primo GEN24 family text and a technical data table for this one model. The article number 4,210,141,800 is carried in the product data the page embeds (field "ArticleNumber") and is checked against that markup (expect_html), not against visible text. Where the page and the Fronius datasheet disagree, the disagreement is written into the product identity note. The page is a technical data page, not a signed specification.

    Open

Archive and older revisions

Archive and older revisions0

Earlier revisions, archived captures and copies published by someone other than the manufacturer. Every one stays reachable.

Archived documents

Fronius datasheet: Fronius Primo GEN24 208-240 and GEN24 208-240 Plus (EN V09 Aug 2025)

Archived copy of a document published by Fronius International GmbH. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email [email protected].

Archived backupEN V09 Aug 2025 · 2.12 MB

Archived copy, unaltered, kept as a record of what Fronius International GmbH published. Original address: https://www.fronius.com/en/~/downloads/Solar%20Energy/Datasheets/SE_DS_Fronius_GEN24_Plus_208_240_EN_US.pdf. Copyright and takedown

Source first found
This copy captured
Archived
File detailsOriginal source
Embedded creation date
Embedded modification date
Pages
8

Embedded dates are file metadata, not independent proof of publication.

SHA-256: b147ed4ce8d91627887af52e94aa2fd281e7c26939545ea1bf4e839b3e89b164

Submit a document

Parts and accessories

No sourced accessories or replacement parts listed yet.

Model history

Model identity

Model
Primo GEN24 5.0 208-240

Manufacturer SKU 4,210,141,800 · US market

  1. Observed Oct 11, 2026

    UL 1741 SA: claimed

    Product / system scope unresolved. Listed on the California Energy Commission Grid Support Solar Inverter List (data unchanged since October 1, 2026; downloaded October 11, 2026) as Fronius International GmbH "Primo GEN24 5.0 208-240 {208V}": UL 1741 SA, certifying entity CSA Group, CEC listing date 2021-11-12. A state equipment list entry, not the certification body's own record.

    [4]

  2. Observed Oct 11, 2026

    UL 1741 SB: claimed

    Product / system scope unresolved. Listed on the California Energy Commission Grid Support Solar Inverter List (data unchanged since October 1, 2026; downloaded October 11, 2026) as Fronius International GmbH "Primo GEN24 5.0 208-240 {208V}": UL 1741 SB, certifying entity CSA Group, certificate date 2025-04-09, CEC listing date 2021-11-12. A state equipment list entry, not the certification body's own record.

    [4]

  3. Observed Oct 11, 2026

    CEC: claimed

    Product / system scope unresolved. Model Primo GEN24 5.0 208-240 listed on the California Energy Commission Grid Support Battery Inverter List (data unchanged since October 1, 2026; downloaded October 11, 2026) under Fronius International GmbH, as "Primo GEN24 5.0 208-240 {208V}"; "Primo GEN24 5.0 208-240 {240V}", CEC listing date 2021-11-12. This is an equipment listing, not UL certification or complete-system approval.

    [4]

  4. Observed Oct 11, 2026

    CEC: claimed

    Product / system scope unresolved. Model Primo GEN24 5.0 208-240 listed on the California Energy Commission Grid Support Solar Inverter List (data unchanged since October 1, 2026; downloaded October 11, 2026) under Fronius International GmbH, as "Primo GEN24 5.0 208-240 {208V}"; "Primo GEN24 5.0 208-240 {240V}", CEC listing date 2021-11-12. This is an equipment listing, not UL certification or complete-system approval.

    [4]

Other recorded fields

FieldValueConditionsSource
Evidence breakdown
method version: inverters-0.5-personal
documented pct: 55
basis: Unknown
missing:
Warranty term needed
Battery conversion efficiency needed
criteria:
key: certificates
label: Certificates
value: 31.5
unit: Unknown
shown: UL 1741 SB +15
shown detail: Claimed
state: claimed
points: 14.2
ceiling: 45
weight: 45
share: 31.5
covered: yes
missing: no
folded: no
reason: Unknown
reason text: Unknown
note: Manufacturer claim; issuer verification pending. Applies to the exact inverter.
display note: Unknown
Sources: [4]
key: warranty
label: Warranty term
value: Unknown
unit: Unknown
shown: Research pending
shown detail: Unknown
state: pending
points: 0
ceiling: 30
weight: 30
share: Unknown
covered: no
missing: yes
folded: yes
reason: undocumented
reason text: Not documented. Undisclosed data scores 0.
note: Not documented.
display note: Unknown
Sources: No source on record
key: efficiency
label: Battery conversion efficiency
value: Unknown
unit: Unknown
shown: Research pending
shown detail: Unknown
state: pending
points: 0
ceiling: 15
weight: 15
share: Unknown
covered: no
missing: yes
folded: yes
reason: undocumented
reason text: Not documented. Undisclosed data scores 0.
note: Not documented.
display note: Unknown
Sources: No source on record
key: idle
label: Idle consumption
value: 10
unit: Unknown
shown: 10 W
shown detail: Unknown
state: documented
points: 1
ceiling: 10
weight: 10
share: 10
covered: yes
missing: no
folded: no
reason: Unknown
reason text: Unknown
note: Printed as a bound: less than 10 W, as printed.
display note: Unknown
Sources: [2]

Community discussions

No discussions linked yet. Search DIY Solar Forum

Sources

  1. Primo GEN24 5.0 208-240 | Fronius USA technical data page (September 24, 2026 capture) (Fronius International GmbH · manufacturer · observed Sep 23, 2026)
  2. Fronius datasheet: Fronius Primo GEN24 208-240 and GEN24 208-240 Plus (EN V09 Aug 2025) (Fronius International GmbH · manufacturer · EN V09 Aug 2025 · observed Sep 23, 2026)
  3. Fronius Fronius Primo GEN24 3.8 - 6.0 kW / Plus / SC 208 - 240 Operating instructions (026-07092026) (Fronius · manufacturer · 026-07092026 · observed Oct 1, 2026)
  4. CEC Grid Support Inverter Lists (solar and battery inverters), official spreadsheet (data unchanged since October 1, 2026; downloaded October 11, 2026) (California Energy Commission · government equipment registry · Data unchanged since October 1, 2026 · observed Oct 10, 2026 · effective Oct 1, 2026)

Sign in to report an error on this page