Printed as "The IQ Battery C80 operates at 277/480 VAC (WYE) or 120/208 VAC (WYE) three-phase, four wire with TN-S grounding connection." in Enphase's IQ Battery C80 installation guide (PDF page 5). The manual applies to this model: IQ Battery C80 installation guide ING-00068-1.0 (North America): key specifications (p10) list the "277Y/480 V variant: IQ‑BT‑C80‑V5‑R3". Source: Enphase's preliminary installation guide ING-00068-1.0 (the guide says it is a preliminary version); the value is replaced when a final guide is published.
≥10 ft (3.0 m) from property lines, buildings and combustible structures (reducible to 3 ft (0.9 m) with a 1-hour fire-rated barrier); ≥3 ft (0.9 m) between ESS cabinets (outdoor, same group)
Printed as "Property lines, buildings, combustible structures ≥10 ft (3.0 m) Reducible to 3 ft (0.9 m) with a 1-hour fire-rated barrier between the ESS and the exposure" in Enphase's IQ Battery C80 installation guide (PDF page 28). The manual applies to this model: IQ Battery C80 installation guide ING-00068-1.0 (North America): key specifications (p10) list the "277Y/480 V variant: IQ‑BT‑C80‑V5‑R3". It also prints "Between ESS cabinets (outdoor, same group) ≥3 ft (0.9 m)" in the same table. Source: Enphase's preliminary installation guide ING-00068-1.0 (the guide says it is a preliminary version); the value is replaced when a final guide is published.
Charged Reviews classified this product from the documents it is based on. It is our own grouping, not a manufacturer claim.
Printed as "Compact, outdoor-ready NEMA 3R enclosure optimized for tight commercial spaces". Classified as Industrial cabinet from the maker's own words for this model (PM decision, October 13, 2026: a commercial or industrial battery cabinet is Industrial cabinet).
minimum OCPD rating 60 A (277Y/480 V, single cabinet)
Printed as "Minimum OCPD rating 60 A" in Enphase's IQ Battery C80 installation guide (PDF page 65). The manual applies to this model: IQ Battery C80 installation guide ING-00068-1.0 (North America): key specifications (p10) list the "277Y/480 V variant: IQ‑BT‑C80‑V5‑R3". Source: Enphase's preliminary installation guide ING-00068-1.0 (the guide says it is a preliminary version); the value is replaced when a final guide is published.
Where: PDF page 65
Sources
60 A min OCPD (1 cabinet)
Printed as "1 48 A 60 A Cu—6 AWG Al—4 AWG 60 A Cu—10 AWG Al—8 AWG" in the same manual (PDF page 74); differs from the value above.
Printed as "AC phase conductors (L1, L2, L3, N, PE) AC terminal block with studs for compression lug termination 7–13 N m" in Enphase's IQ Battery C80 installation guide (PDF page 66). The manual applies to this model: IQ Battery C80 installation guide ING-00068-1.0 (North America): key specifications (p10) list the "277Y/480 V variant: IQ‑BT‑C80‑V5‑R3". Source: Enphase's preliminary installation guide ING-00068-1.0 (the guide says it is a preliminary version); the value is replaced when a final guide is published.
Where: PDF page 66
Sources
7 to 13 N·m
Printed as "AC phase conductors (L1, L2, L3, N, PE) Cabinet AC terminal 7–13 N m" in the same manual (PDF page 73); differs from the value above.
Printed as "Ethernet (RJ45) Ethernet port" in Enphase's IQ Battery C80 installation guide (PDF page 73). The manual applies to this model: IQ Battery C80 installation guide ING-00068-1.0 (North America): key specifications (p10) list the "277Y/480 V variant: IQ‑BT‑C80‑V5‑R3". Source: Enphase's preliminary installation guide ING-00068-1.0 (the guide says it is a preliminary version); the value is replaced when a final guide is published.
outdoor ground-mount (pad); must remain upright at all times
Printed as "The IQ Battery C80 is designed for outdoor, ground-mount (pad) installation as the primary deployment context." in Enphase's IQ Battery C80 installation guide (PDF page 25). The manual applies to this model: IQ Battery C80 installation guide ING-00068-1.0 (North America): key specifications (p10) list the "277Y/480 V variant: IQ‑BT‑C80‑V5‑R3". It also prints "The IQ Battery C80 must remain upright at all times." in the same guide. Source: Enphase's preliminary installation guide ING-00068-1.0 (the guide says it is a preliminary version); the value is replaced when a final guide is published.
Printed as "AC phase conductors (L1, L2, L3, N, PE) AC terminal block with studs for compression lug termination 7–13 N m" in Enphase's IQ Battery C80 installation guide (PDF page 66). The manual applies to this model: IQ Battery C80 installation guide ING-00068-1.0 (North America): key specifications (p10) list the "277Y/480 V variant: IQ‑BT‑C80‑V5‑R3". Source: Enphase's preliminary installation guide ING-00068-1.0 (the guide says it is a preliminary version); the value is replaced when a final guide is published.
Printed only in Fahrenheit, as a low-end heater rating and a high-end ambient rating, not as a single stated range: "The built-in heater ensures reliable operation in temperatures as low as -22°F" and "ambient temperatures up to 131°F". Recorded as printed text rather than converted to Celsius, since the source states no formula.
Where: Built for harsh weather and Designed to stay cool sections
1,470.65 L* (Calculated enclosure volume: W × H × D in mm ÷ 1,000,000)W: 919.5 × H: 1,999 × D: 800.1 mm / W: 36.2 × H: 78.7 × D: 31.5 in1,050.07 kg / 2,315 lb0.05 kWh/L* (Rated or usable capacity shown on this card ÷ enclosure volume)
Evidence score
20/100Missing details20% documented
The Evidence score uses the priorities you choose. It counts published documents, such as certificates and warranty terms, and it compares a documented figure with the best documented figure of the same kind. It does not count owner reviews, and it is not a verdict on product quality or on how many people have reviewed it. A low score can mean little is documented, or that a documented figure is below the best of its kind. Undisclosed data scores 0.
Missing details. This number counts only the evidence recorded so far. The source review for this product is not finished, or the maker has not disclosed enough, so the number can only go up.
Missing for this product: Certificates evidence needed; Warranty energy disclosure evidence needed; Lifetime / capacity evidence needed; Cell model disclosure evidence needed.
Industrial/Commercial ESS · Voltage unconfirmed · 30 to 100 kWh · Rated capacity
The warranty term and the lifetime energy are each scored against the best documented value for a home storage battery: a value earns its share of that best, times the weight. A documented value always earns points; an undisclosed one earns 0.
Warranty term15 years20 / 20
15 years · 20% weight
This is the best documented for a home storage battery, printed by the maker. 29 home storage batteries share this value.
Printed as "covered by a 15-year warranty up to 7,000 cycles".
Research pending, 0 points: Certificates, Warranty energy disclosure, Lifetime / capacity, Cell model disclosure.
Computed from public specifications and evidence records. Warranty duration is not service quality; certificate evidence points are not a safety rating. Compatibility and installation limits still apply.
What this shows: what each record says and how far it reaches. It does not mean the product is approved.
StandardEvidenceStatusSource
UL 9540Amanufacturer claimpresent at observation[1]
Scope
unresolved document set
Covered models
IQ Battery C80 (277Y/480 V)
Limitations
Printed on the product's own store page as "UL 9540A-tested thermal-runaway mitigation", a claim of testing to the standard rather than a named certificate or listing number. No certificate document is published yet and no issuer record was checked.
Printed as "up to 7,000 cycles", alongside the 15-year term; the two are printed as alternative limits (whichever is reached first is not stated explicitly).
Enphase's own IQ Battery C80 installation guide ING-00068-1.0 (August 2026), captured October 15, 2026 with the paced research fetcher (robots.txt read first). The guide says it is a preliminary version that will be updated before product launch. Manufacturer instructions, not independent tests.
Archived copies
Archived copy of a document published by Enphase. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email [email protected].
Captured by scripts/prepare-brand-sweep-sep21.mjs on 2026-09-28.
Location: Technical specifications and Warranty accordions
Retrieved Sep 27, 2026
Enphase's own US store page for the 277Y/480 V IQ Battery C80, captured September 28, 2026. The product is listed "Available in Q1 2027" and orderable for pre-order; the page prints the SKU, technical specification list and warranty term. The page is script-rendered (Magento); the text below is what the markup itself serves.
Captured by scripts/prepare-brand-sweep-sep21.mjs on 2026-09-28.
Location: Electrical specifications, Built for harsh weather, Designed to stay cool and Industry-leading warranty sections
Retrieved Sep 27, 2026
Enphase's own installer-facing overview page for the IQ Battery C80, captured September 28, 2026, titled "IQ Battery C80 | Commercial Battery Energy Storage | Enphase". It states both voltage variants' electrical ratings side by side and describes the product's enclosure, temperature range and warranty in prose rather than a table.
Captured by scripts/prepare-brand-sweep-sep21.mjs on 2026-09-28.
Location: Featured products SKU list
Retrieved Sep 27, 2026
Enphase's own US store storage-category listing page, captured September 28, 2026, which lists every storage product's printed SKU next to its model name. Used only to corroborate the SKUs each C80 variant's own product page prints; no specification figure is read from it.
Archived copy of a document published by Enphase. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email [email protected].
No sourced accessories or replacement parts listed yet.
Model history
Model identity
Model
IQ Battery C80 (277Y/480 V)
Manufacturer SKU IQ-BT-C80-V5-R3 · US market
No historical observations recorded yet.
Other recorded fields
Field
Value
Conditions
Source
Evidence breakdown
method version: 0.21-personal
documented pct: 20
basis: nominal
missing:
Certificates evidence needed
Warranty energy disclosure evidence needed
Lifetime / capacity evidence needed
Cell model disclosure evidence needed
criteria:
key: certificateEvidence
label: Certificates
value: 0
unit: evidence points
shown: UL 9540A
shown detail: Research pending
state: pending
points: 0
ceiling: 45
weight: 45
share: 0
covered: no
missing: yes
folded: yes
reason: Unknown
reason text: Unknown
note: No qualifying applicable evidence recorded. This is not proof that certification is absent. Applies: UL 9540; UL 1973; CEC not assessed for commercial and industrial equipment in this catalog. UL 9540A is recorded but not scored: a thermal-runaway test method, recorded as a documented report and never scored as a listing.
Product prices and availability are accurate as of the date/time indicated and are subject to change. Any price and availability information displayed on Amazon.com at the time of purchase will apply to the purchase of this product. CERTAIN CONTENT THAT APPEARS ON THIS SITE COMES FROM AMAZON. THIS CONTENT IS PROVIDED ‘AS IS’ AND IS SUBJECT TO CHANGE OR REMOVAL AT ANY TIME.