- Brand
- EG4 Electronics
- Model
- SR-12|400-LL-00
- SKU / part number
- SR-12|400-LL-00 [1]
- Category
- Batteries
chargedreviews.com/batteries/eg4-electronics-sr-12-400-ll-00
Energy and chemistry
Charge and discharge
- Continuous charge current
- 200 A [1]
- Continuous discharge current
- 200 A [1]
- Maximum charge current
- 200 A [1]
- Maximum discharge current
- 200 A [2]
- Peak charge current
- ?
- Peak discharge current
- ?
- Continuous output power
- ?
- Peak output
- ?
- Maximum charge voltage
- 14 V [2]
- Charge cutoff voltage
- 15 V [2]
- Discharge cutoff voltage
- 9.6 V [2]
BMS and communication
Operating temperature
Mechanical and mounting
Installation (from the manual)
Torque
- Main terminal torque
- 7 N·m [2]
- Communication terminal torque
- ?
- Ground terminal torque
- ?
Conductors
- Cable size
- 2/0 AWG (min.) up to 10 ft; 4/0 AWG up to 18 ft; 600 V insulation [2]
Clearances and orientation
- Installation clearances
- ?
- Mounting orientation
- Never position the battery upside down or face down [2]
Grounding
- Grounding
- Grounding screw on the chassis; a grounding wire can run from the rack or cabinet to an equipment grounding conductor terminated at a grounding electrode. Do not ground the rack, cabinet or door to the negative or positive bus bars. [2]
Communication
- Communication ports
- CAN port (CAN bus communication); RS485 port (RS485 communication); Battery-Comm ports (parallel battery communication) [2]
- Address / DIP setting
- Set a DIP switch ID on each battery; the host battery (the one that connects to the inverter) is ID 1, the ID code range is 1 to 16, and all DIP switch settings must be different. [2]
Not in the manual: Protection
System limits
- Maximum parallel units
- 16 units [1]
- Series connection
- ?
- Maximum system energy
- ?