Charged Reviews
Quick reference
Fox ESS FOX HUB G2 Smart Energy Management System (200 A)
Model: FOX HUB G2 · SKU: Not documented
Prepared Nov 12, 2026

Common specifications
| Maximum current | 200 ASource [1] |
|---|---|
| Service voltage | 120/240 Vac nominal output, 240 Vac nominal input, 60 HzSource [1] |
| Poles | Not documented |
| Transfer time | Not documented |
| Generator input | Optional generator input: 48 kW maximum rated AC power, 211 to 264 Vac, 200 A maximum continuous input current, 2-wire start switchSource [1] |
| PV and storage ports | Solar terminal 80 A; FOX inverter 80 A; Smart Circuit 1 (240 V) 80 A; Smart Circuits 2 and 3 (120 V) 80 A; up to 4 invertersSource [1] |
| Enclosure | Type 3RSource [1] |
| Safety listing | UL67, UL869A, UL916, UL1741, CSA22.2 NO.107; FCC part 15 class BSource [1] |
| Enclosure volume | 46.13 L** Calculated from recorded external dimensions |
| Warranty term | 12.5 yearsSource [1] |
All recorded specifications
| Communications | CAN; RS485Documented claim ConditionsPrinted as "CAN, RS485" in the row "Communication". Location: Page 2, Additional features, Communication Printed as "CAN, RS485" in the row "Communication". Location: Page 2, Additional features, Communication |
|---|---|
| Dimensions | 156.6 D × 443 W × 665 H mm6.17 D × 17.4 W × 26.2 H in convertedDocumented claim ConditionsPrinted as "26.2*17.4*6.2 /665*443*156.6" in the row "Dimensions (H*W*D) [inch/mm]"; the millimeter figures are the ones printed. Location: Page 2, Installation specifications, Dimensions (H*W*D) [inch/mm] Printed as "26.2*17.4*6.2 /665*443*156.6" in the row "Dimensions (H*W*D) [inch/mm]"; the millimeter figures are the ones printed. Location: Page 2, Installation specifications, Dimensions (H*W*D) [inch/mm] |
| Enclosure | Type 3RDocumented claim ConditionsPrinted as "Type 3R" in the row "Protection Rating". Location: Page 2, Installation specifications, Protection Rating Printed as "Type 3R" in the row "Protection Rating". Location: Page 2, Installation specifications, Protection Rating |
| Generator input | Optional generator input: 48 kW maximum rated AC power, 211 to 264 Vac, 200 A maximum continuous input current, 2-wire start switchDocumented claim ConditionsPrinted as "48" (Maximum Rated AC Power [kW]), "211 ~ 264" (AC Voltage Range [Vac]), "200" (Maximum Continuous Input Current, printed with the unit "[Adc]"), "Yes" (2-wire Start Switch); dry contact rating "250/30" Vac/Vdc and "0.5(250Vac) / 3(30Vdc)" A. Location: Page 2, Generator (Optional) Printed as "48" (Maximum Rated AC Power [kW]), "211 ~ 264" (AC Voltage Range [Vac]), "200" (Maximum Continuous Input Current, printed with the unit "[Adc]"), "Yes" (2-wire Start Switch); dry contact rating "250/30" Vac/Vdc and "0.5(250Vac) / 3(30Vdc)" A. Location: Page 2, Generator (Optional) |
| Maximum current | 200 ADocumented claim ConditionsPrinted as "200" in the row "Microgrid Interconnection Device Rated Current [A]"; the rows "AC Current (Nominal) [A]", "Non-Backup Load [A]" and "Backup Load Terminal [A]" also print 200, and "Busbar Rating [A]" prints 280. Location: Page 2, General electrical, Microgrid Interconnection Device Rated Current [A] Printed as "200" in the row "Microgrid Interconnection Device Rated Current [A]"; the rows "AC Current (Nominal) [A]", "Non-Backup Load [A]" and "Backup Load Terminal [A]" also print 200, and "Busbar Rating [A]" prints 280. Location: Page 2, General electrical, Microgrid Interconnection Device Rated Current [A] |
| Operating temperature | -20 to 50 °C-4 to 122 °F convertedDocumented claim ConditionsPrinted as "–4 ~ +122 / –20 ~ +50" in the row "Operating Temeprature Range [°F/°C]" (spelling as printed). Location: Page 2, Installation specifications, Operating Temperature Range [°F/°C] Printed as "–4 ~ +122 / –20 ~ +50" in the row "Operating Temeprature Range [°F/°C]" (spelling as printed). Location: Page 2, Installation specifications, Operating Temperature Range [°F/°C] |
| PV and storage ports | Solar terminal 80 A; FOX inverter 80 A; Smart Circuit 1 (240 V) 80 A; Smart Circuits 2 and 3 (120 V) 80 A; up to 4 invertersDocumented claim ConditionsPrinted as "80" in the rows "Solar terminal [A]", "FOX Inverter [A]", "Smart Circuits 1 (240V) [A]" and "Smart Circuit 2, 3 (120V) [A]", and "4" in the row "Maximum Number of Inverter"; supported inverters printed as "FOX US Series". Location: Page 2, External connection and Additional features Printed as "80" in the rows "Solar terminal [A]", "FOX Inverter [A]", "Smart Circuits 1 (240V) [A]" and "Smart Circuit 2, 3 (120V) [A]", and "4" in the row "Maximum Number of Inverter"; supported inverters printed as "FOX US Series". Location: Page 2, External connection and Additional features |
| Safety listing | UL67, UL869A, UL916, UL1741, CSA22.2 NO.107; FCC part 15 class BDocumented claim ConditionsPrinted as "UL67, UL869A, UL916, UL1741, CSA22.2 NO.107" (Safety) and "FCC part 15 class B" (Emissions). Manufacturer compliance claims; no certificate was checked. Location: Page 2, Standard compliance, Safety and Emissions Printed as "UL67, UL869A, UL916, UL1741, CSA22.2 NO.107" (Safety) and "FCC part 15 class B" (Emissions). Manufacturer compliance claims; no certificate was checked. Location: Page 2, Standard compliance, Safety and Emissions |
| Service voltage | 120/240 Vac nominal output, 240 Vac nominal input, 60 HzDocumented claim ConditionsPrinted as "240" (AC Input Voltage (Nominal) [Vac]), "120/240" (AC Output Voltage (Nominal) [Vac]), "211 ~ 264" (AC Voltage Range [Vac]) and "60" (AC Frequency (Nominal) [Hz]). Location: Page 2, General electrical, AC Input Voltage, AC Output Voltage and AC Frequency (Nominal) Printed as "240" (AC Input Voltage (Nominal) [Vac]), "120/240" (AC Output Voltage (Nominal) [Vac]), "211 ~ 264" (AC Voltage Range [Vac]) and "60" (AC Frequency (Nominal) [Hz]). Location: Page 2, General electrical, AC Input Voltage, AC Output Voltage and AC Frequency (Nominal) |
| Weight | 17 kg37 lb convertedDocumented claim ConditionsPrinted as "37.4 / 17" in the row "Weight [lbs/kg]". Location: Page 2, Installation specifications, Weight [lbs/kg] Printed as "37.4 / 17" in the row "Weight [lbs/kg]". Location: Page 2, Installation specifications, Weight [lbs/kg] |
Warranty
| Warranty term | 12.5 yearsDocumented claim ConditionsPrinted as "12.5" in the row "Warranty [year]". Location: Page 2, Installation specifications, Warranty [year] Printed as "12.5" in the row "Warranty [year]". Location: Page 2, Installation specifications, Warranty [year] |
|---|
Certificate records
No records documented.
Sources and revisions
- Fox ESS datasheet (US): FOX HUB G2, V2.0 | 2026/05/29Official datasheet · Revision V2.0 | 2026/05/29 · Checked https://us.fox-ess.com/Public/Uploads/uploadfile/files/20261009/USFOXHUBG2DatasheetV2.020260529.pdf