Charged ReviewsSaved 0Compare 0Login

Charged Reviews · Quick reference

Victron Energy Quattro 48/15000/200-100/100

Brand
Victron Energy
Model
Quattro 48/15000/200-100/100
SKU / part number
QUA483150000 [1]
Category
Inverters

chargedreviews.com/inverters/victron-energy-quattro-48-15000-200-100-100

AC output

Continuous output
12 kW [2]
Peak output
25000 W [2]
AC configuration
230 VAC [2]
AC output voltage
230 V [3]
AC frequency
50 Hz [4]
Grid pass-through
?
Maximum output per leg
?

Battery

Battery voltage
48 V [4]
Battery voltage range
[38, 66] VDC V [4]
Maximum charge current
200 A [4]
Maximum discharge current
?
Battery-only output
?
Maximum grid charging
200 A [3]
Compatible batteries / BMS
?

PV input

PV array limit (connected)
?
PV input limit (converted)
?
Maximum PV voltage (Voc)
?
MPPT voltage range
?
MPPT trackers
?
String inputs per MPPT
?
PV current per MPPT
?
PV short-circuit current
?
PV startup voltage
?

Efficiency and modes

Peak efficiency
96 % [4]
CEC weighted efficiency
?
Battery conversion efficiency
?
Grid / off-grid modes
?
Generator input
Programmable relay that can a.o. be set for general alarm, DC under voltage or genset start/stop function [3]
Transfer time
?
Idle consumption
110 W [4]
Parallel units
6 count [5]

Communication and environment

Communications
VE.Bus [4]
Operating temperature
[-20, 60] °C °C [4]
Enclosure rating
IP20 [4]
Operating noise
?

Mechanical

Dimensions
W 488 × H 572 × D 344 mm / W 19.2 × H 22.5 × D 13.5 in converted [4]
Weight
72 kg / 160 lb converted [4]

Installation (from the manual)

Torque

Terminal torque
14 N·m [5]
AC terminal torque
?
Battery terminal torque
?
PV terminal torque
?
Ground terminal torque
?

Conductors

Battery conductors
2x 95 mm² (cables 0 to 5 m); 2x 150 mm² (5 to 10 m) [5]
AC input conductors
?
AC output conductors
?
PV conductors
?
Ground conductor
?

Protection

AC input breaker
AC-in-1 and AC-in-2: fuse or magnetic circuit breaker rated at 100 A or less [3]
AC output breaker
AC-out-1: maximum rating of the fuse or circuit breaker 165 A (15 kVA); AC-out-2: earth leakage circuit breaker and fuse rated at max. 50 A [3]
Battery fuse or breaker
Recommended DC fuse 600 A. The Quattro has no internal DC fuse; the DC fuse should be installed outside the Quattro. [3]
PV disconnect
?

Clearances and orientation

Installation clearances
The device should be surrounded by a free space of at least 10 cm for cooling purposes. [3]
Mounting orientation
The device can be fitted either horizontally or vertically. For optimal cooling, vertical fitting is preferred. [3]

Grounding

Grounding and neutral-ground bonding
The Quattro is a safety class I product (supplied with an ground terminal for safety purposes), only a TN-S grounding system is allowed).; In a fixed installation, an uninterruptable grounding can be secured by means of the grounding wire of the AC input. Otherwise the casing must be grounded. [3]

Communication

Communication ports
VE.Bus communication port: for parallel and three phase operation, remote monitoring and system integration; General purpose com. port: 2x [3]
Page 1 of 2 · Installation values · ? means nothing is recordedAggregated, often community-reported information, not official documentation. Do not rely on it for installation, purchase or compliance decisions; always confirm values with the manufacturer’s official documentation. Charged Reviews accepts no responsibility for errors.

Charged Reviews · Quick reference

Victron Energy Quattro 48/15000/200-100/100 · Quattro 48/15000/200-100/100

Warranty

Warranty term5 years[6]
Optional extension5 more years (10 years total) for a 10% surcharge, bought by Victron's direct customers at least one year before the original term ends[6]
Coverage startsDate of purchase by the original end-user, with a maximum of 66 months from the Victron Energy invoice date[6]
Coverage conditionsVoid after physical damage or alteration; excludes improper use such as reversed battery polarity, inadequate connection, mechanical shock, liquid or condensation, unsuitable environment, lightning, and terminals damaged by insufficient tightening; not for products misused, neglected, improperly installed, disassembled, modified or repaired by anyone other than Victron Energy or its authorized Repair Centres[6]
RemedyRepair, replace or (partly) credit the defective product free of charge, at Victron Energy's discretion[6]
Labor and shippingNot included: the warranty does not perform or reimburse de-installation, transportation and re-installation[6]
Transfer to another owner?
Registration?
Territory?

Certifications and listings

UL 1741?
UL 1741 SA?
UL 1741 SB?
IEEE 1547?
CA Rule 21?
UL 9540?
FCC Part 15?
EN-IEC 60335-1Claimed [4]
EN-IEC 60335-2-29Claimed [4]
EN-IEC 62109-1Claimed [4]

Documents and sources

  1. Victron Energy price list 2026-Q3 (EUR C, web edition) Manufacturer price list · Revision 2026-Q3 · Checked Sep 22, 2026 https://www.victronenergy.com/media/pricelist/Pricelist_Victron_EUR_C_2026-Q3_Web.pdf
  2. Quattro 3kVA - 15kVA 230V Manufacturer datasheet (PDF) · Checked Sep 18, 2026 https://www.victronenergy.com/upload/documents/Datasheet-Quattro-3kVA-15kVA-EN-.pdf
  3. Quattro 5k 8k 10k 15k 100-100A 230V (firmware xxxx4xx) Manufacturer manual · Checked Sep 18, 2026 https://www.victronenergy.com/upload/documents/Manual-Quattro-5k-8k-10k-15K-100-100A-230V-(firmware-xxxx4xx)-EN-NL-FR-DE-ES-SE-IT.pdf
  4. Victron Energy public API record for SKU QUA483150000 (Quattro) Manufacturer product API record · Revision 2026-09-04 19:09:18 · Checked Sep 18, 2026 https://www.victronenergy.com/api/v1/product/sku/QUA483150000?format=json
  5. Quattro 5k-15k 100/100A 230V manual (firmware xxxx400 or higher) Manufacturer installation manual · Checked Sep 25, 2026 https://www.victronenergy.com/upload/documents/Manual-Quattro-5k-8k-10k-15K-100-100A-230V-%28firmware-xxxx4xx%29-EN-NL-FR-DE-ES-SE-IT.pdf
  6. Victron Energy victron warranty Manufacturer warranty policy · Checked Sep 10, 2026 https://www.victronenergy.com/upload/documents/Victron-Energy-Limited-Warranty-Policy.pdf

Unofficial reference. Information may be incorrect. This sheet aggregates the public sources listed above, much of it community-reported. It is not official manufacturer documentation, not an installation guide and not a compliance record. Community-reported values are checked against official manufacturer information before publication; we cannot guarantee accuracy or completeness. Do not rely on this sheet for installation, purchase or compliance decisions: always confirm every value with the manufacturer’s official documentation before buying, wiring or installing equipment. Charged Reviews accepts no responsibility for errors or omissions. Manufacturers can submit documents or corrections.

Page 2 of 2 · Charged Reviews LLC · chargedreviews.com/inverters/victron-energy-quattro-48-15000-200-100-100Some links pay us a commission. That does not affect what we record.