Charged Reviews · Quick reference
Victron Energy Quattro 24/8000/200-100/100
- Brand
- Victron Energy
- Model
- Quattro 24/8000/200-100/100
- SKU / part number
- QUA248020010 [1]
- Category
- Inverters
chargedreviews.com/inverters/victron-energy-quattro-24-8000-200-100-100
AC output
Battery
PV input
- PV array limit (connected)
- ?
- PV input limit (converted)
- ?
- Maximum PV voltage (Voc)
- ?
- MPPT voltage range
- ?
- MPPT trackers
- ?
- String inputs per MPPT
- ?
- PV current per MPPT
- ?
- PV short-circuit current
- ?
- PV startup voltage
- ?
Efficiency and modes
Communication and environment
Mechanical
Installation (from the manual)
Torque
- Terminal torque
- 14 N·m [5]
- AC terminal torque
- ?
- Battery terminal torque
- ?
- PV terminal torque
- ?
- Ground terminal torque
- ?
Conductors
- Battery conductors
- 2x 70 mm² (cables 0 to 5 m); 2x 120 mm² (5 to 10 m) [5]
- AC input conductors
- ?
- AC output conductors
- ?
- PV conductors
- ?
- Ground conductor
- ?
Protection
- Breakers / fuses
- DC fuse 500 A; AC-in-1 fuse or magnetic circuit breaker rated at 100 A or less; AC-out-2 fuse or circuit breaker rated at max. 50 A [5]
- AC input breaker
- AC-in-1 and AC-in-2: fuse or magnetic circuit breaker rated at 100 A or less [3]
- AC output breaker
- AC-out-1: maximum rating of the fuse or circuit breaker 135 A (8 kVA); AC-out-2: earth leakage circuit breaker and fuse rated at max. 50 A [3]
- Battery fuse or breaker
- Recommended DC fuse 500 A. The Quattro has no internal DC fuse; the DC fuse should be installed outside the Quattro. [3]
- PV disconnect
- ?
Clearances and orientation
Grounding
- Grounding and neutral-ground bonding
- The Quattro is a safety class I product (supplied with an ground terminal for safety purposes), only a TN-S grounding system is allowed).; In a fixed installation, an uninterruptable grounding can be secured by means of the grounding wire of the AC input. Otherwise the casing must be grounded. [3]
Communication
- Communication ports
- VE.Bus communication port: for parallel and three phase operation, remote monitoring and system integration; General purpose com. port: 2x [3]