Charged Reviews · Quick reference
SunGoldPower SPH6548P
- Brand
- SunGoldPower
- Model
- SPH6548P
- SKU / part number
- SPH6548P[7]
- Category
- Inverters

AC output
| Continuous output | 6.5 kW[4] |
|---|---|
| Peak output | 13,000 VA[2, 4] |
| AC configuration | Split-phase mode (default); Single-phase mode[4] |
| AC output voltage | AC output phase voltage (L-N) 100 VAC−120 VAC, 120 VAC (default); AC output line voltage (L-L) 200 VAC−240 VAC, 240 VAC (default)[4] |
| AC frequency | 50/60 Hz[4] |
| Grid pass-through | 40 A[4] |
| Maximum output per leg | ? |
Battery
| Battery voltage | 48 V[4] |
|---|---|
| Battery voltage range | 40 to 60 V[4] |
| Maximum charge current | 140 A[4] |
| Maximum discharge current | ? |
| Battery-only output | ? |
| Maximum grid charging | 80 A[4] |
| Compatible batteries / BMS | Lithium-ion battery/lead-acid battery/user-defined battery[4] |
PV input
| PV array limit (connected) | ? |
|---|---|
| PV input limit (converted) | ? |
| Maximum PV voltage (Voc) | 550 V[4] |
| MPPT voltage range | 150 to 450 V[4] |
| MPPT trackers | 2[4] |
| String inputs per MPPT | ? |
| PV current per MPPT | 18/18 A[4] |
| PV short-circuit current | ? |
| PV startup voltage | ? |
Efficiency and modes
| Peak efficiency | 93 %[4] |
|---|---|
| CEC weighted efficiency | ? |
| Battery conversion efficiency | ? |
| Grid / off-grid modes | ? |
| Generator input | Generator input (L1+L2+N); dry contact remote generator start/stop[4] |
| Transfer time | 10 ms[4] |
| Idle consumption | ? |
| Parallel units | 6[4] |
Communication and environment
| Communications | RS485; CAN; USB; dry contact[4] |
|---|---|
| Operating temperature | -10 to 55 °C[4] |
| Enclosure rating | IP20[4] |
| Operating noise | ? |
Mechanical
| Dimensions | 584.2 D × 411.5 D × 132.1 D mm[4]Calculated |
|---|---|
| Weight | 18.9 kg / 41.67 lb[4] |
Installation (from the manual)
Conductors
| Battery conductors | 35mm2/2AWG[4] |
|---|---|
| AC input conductors | Split-phase mode: 10mm2/8AWG (L1, L2, N); single-phase mode: 10mm2/8AWG (L1/L2), 20mm2/4AWG (N)[4] |
| AC output conductors | Split-phase mode: 10mm2/8AWG (L1, L2, N); single-phase mode: 10mm2/8AWG (L1/L2), 16mm2/6AWG (N)[4] |
| PV conductors | 4mm2/12AWG[4] |
| Ground conductor | not less than 4 mm²[4] |
Protection
| AC input breaker | Split-phase mode: 3P-40A; single-phase mode: 2P-80A[4] |
|---|---|
| AC output breaker | Split-phase mode: 3P-40A; single-phase mode: 2P-80A[4] |
| Battery fuse or breaker | 2P-160A[4] |
| PV disconnect | 2P-25A[4] |
Clearances and orientation
| Installation clearances | Top 20cm, bottom 20cm, left 50cm, right 50cm[4] |
|---|---|
| Mounting orientation | ? |
Grounding
| Grounding and neutral-ground bonding | Please ensure that the grounding terminal is reliably connected to the grounding busbar.[4] |
|---|
Communication
| Communication ports | USB-B port; CT (under development); WIFI port; RS485/CAN port; Dry contact port; Parallel port[4] |
|---|
Not in the manual: Torque
Page 1 of 2 · Installation values · ? means nothing is recordedAggregated, often community-reported information, not official documentation. Do not rely on it for installation, purchase or compliance decisions; always confirm values with the manufacturer’s official documentation. Charged Reviews accepts no responsibility for errors.