Charged Reviews · Quick reference
SunGoldPower SGN7.6K1HB-48
- Brand
- SunGoldPower
- Model
- SGN7.6K1HB-48
- SKU / part number
- SGN7.6K1HB-48[6]
- Category
- Inverters

AC output
| Continuous output | 7.6 kW[2]Calculated |
|---|---|
| Peak output | 15,200 VA for 1 s[2] |
| AC configuration | ? |
| AC output voltage | 120 V / 240 V (Split phase) / 208 V (2/3 phase) V AC[2] |
| AC frequency | 50 Hz / 60 Hz[2] |
| Grid pass-through | ? |
| Maximum output per leg | ? |
Battery
| Battery voltage | 48 V[2] |
|---|---|
| Battery voltage range | 40 to 64 V[2] |
| Maximum charge current | 210 A[2] |
| Maximum discharge current | 180 A[2] |
| Battery-only output | 7.6 kW[2]Calculated |
| Maximum grid charging | ? |
| Compatible batteries / BMS | Lithium-ion/Lead-acid[2] |
PV input
| PV array limit (connected) | 12 kW[2, 4] |
|---|---|
| PV input limit (converted) | ? |
| Maximum PV voltage (Voc) | 600 V[2] |
| MPPT voltage range | 70 to 540 V[2] |
| MPPT trackers | 3[2] |
| String inputs per MPPT | ? |
| PV current per MPPT | 30 A / 22 A / 22 A[2] |
| PV short-circuit current | 40 A / 30 A / 30 A[2] |
| PV startup voltage | 90 V[2] |
Efficiency and modes
| Peak efficiency | ? |
|---|---|
| CEC weighted efficiency | ? |
| Battery conversion efficiency | ? |
| Grid / off-grid modes | Self-consumption, Feed-in Priority, Back-up and Off Grid modes[2] |
| Generator input | Yes (GEN port)[2] |
| Transfer time | < 10 ms (typical)[2] |
| Idle consumption | ? |
| Parallel units | 9[2, 4] |
Communication and environment
| Communications | CAN (for BMS); DRM/RS485 (for meter); RS485; optional: Wi-Fi/LAN[2] |
|---|---|
| Operating temperature | -25 to 60 °C[2] |
| Enclosure rating | NEMA 3R[2] |
| Operating noise | ? |
Mechanical
| Dimensions | 240 D × 420 W × 800 H mm[2] |
|---|---|
| Weight | 40 kg / 88.18 lb[2] |
Installation (from the manual)
Torque
| AC terminal torque | 3.95 N·m(34.96 in-lb*)[2] |
|---|---|
| Battery terminal torque | 20 N·m(177.01 in-lb*)[2] |
| PV terminal torque | ? |
| Ground terminal torque | 3.95 N·m(34.96 in-lb*)[2] |
Conductors
| Battery conductors | 3/0 AWG[2] |
|---|---|
| AC input conductors | Min. 6 AWG[2] |
| AC output conductors | Min. 6 AWG[2] |
| PV conductors | 10 to 8 AWG[2] |
| Ground conductor | Min. 8 AWG[2] |
Protection
| AC input breaker | ≥60A/250V[2] |
|---|---|
| AC output breaker | ≥60A/250V[2] |
| Battery fuse or breaker | 300A/80V[2] |
| PV disconnect | Integrated PV switch (DC Switch)[2] |
Clearances and orientation
| Installation clearances | Top 500 mm, bottom 500 mm, sides 350 mm, front 1000 mm (doors or windows)[2] |
|---|---|
| Mounting orientation | Vertical or up to 15° back tilt; connection area downward[2] |
Grounding
| Grounding and neutral-ground bonding | PE busbar in the wiring box; inverter must be grounded; BACKUP/GEN neutral and GRID neutral on separate terminals[2] |
|---|
Communication
| Communication ports | BMS; CT/METER; RS485 (4-pin); PARA (4-pin); DRM; RSD; DRY (9-pin: GEN, NTC, RMO, DRY); GPRS/WIFI/LAN[2] |
|---|
Page 1 of 2 · Installation values · ? means nothing is recordedAggregated, often community-reported information, not official documentation. Do not rely on it for installation, purchase or compliance decisions; always confirm values with the manufacturer’s official documentation. Charged Reviews accepts no responsibility for errors.