AC output
- Continuous output
- 50 kW [1]
- Peak output
- 1.6 times of rated power, 10s [2]
- AC configuration
- Three-phase [2]
- AC output voltage
- 277/480Vac (3L+N+PE) [3]
- AC frequency
- 50/60Hz ± 0.3Hz [1]
- Grid pass-through
- 200 A [1]
- Maximum output per leg
- ?
Battery
- Battery voltage
- ?
- Battery voltage range
- 150 to 850 V [3]
- Maximum charge current
- 160 A [3]
- Maximum discharge current
- 160 A [3]
- Battery-only output
- ?
- Maximum grid charging
- ?
- Compatible batteries / BMS
- Lithium-ion or lead-acid batteries [1]
PV input
- PV array limit (connected)
- 100kW [1]
- Maximum PV voltage (Voc)
- 1,000 V [3]
- MPPT voltage range
- 150 to 850 V [3]
- String inputs per MPPT
- ?
- PV current per MPPT
- 40A*4 [1]
- PV short-circuit current
- 60 A [1]
- PV startup voltage
- 160 V [3]
Efficiency and modes
- Peak efficiency
- 97.6 % [3]
- CEC weighted efficiency
- 97 % [3]
- Battery conversion efficiency
- ?
- Grid / off-grid modes
- ?
- Generator input
- ?
- Idle consumption
- ?
- Parallel units
- 9 count [3]
Communication and environment
- Communications
- RS485 / CAN / USB / Dry Contact [3]
- Operating temperature
- -40F~140F, >113F derated F [1]
- Operating noise
- ?
Mechanical
- Dimensions
- 622.3 × 342.9 × 1,010.92 mm / 24.5 × 13.5 × 39.8 in converted [3]
- Weight
- 97.98 kg / 216 lb converted [3]
Installation (from the manual)
Conductors
- Battery conductors
- 21mm²/ 04 AWG (two battery inputs) [1]
- AC output conductors
- 33.6mm²/2AWG (L1/L2/L3/N) [1]
- PV conductors
- 5mm²/ 10 AWG [1]
- Ground conductor
- ?
Protection
- Breakers / fuses
- Battery breaker 2P-100A (single circuit) or 2P-200A (dual circuits); PV breaker 2P-50A; grid and generator breakers 4P-250A; load breaker 4P-200A [1]
- AC input breaker
- ?
- AC output breaker
- ?
- Battery fuse or breaker
- ?
- PV disconnect
- ?
Not in the manual: Torque, Clearances and orientation, Grounding, Communication