SRNE HESP4865U140-HUS
- Brand
- SRNE
- Model
- HESP4865U140-HUS
- SKU / part number
- ?
- Category
- Inverters

AC output
| Continuous output | 6.5 kW[4]Calculated |
|---|---|
| Peak output | 2× rated power for 10 seconds[1] |
| AC configuration | 120/240 V AC (Split-phase); 120/208 V AC (Three-phase)[1] |
| AC output voltage | 120/240Vac (Split-phase); 120/208Vac (Three-phase)[3] |
| AC frequency | 50/60Hz[4] |
| Grid pass-through | 60 A[4] |
| Maximum output per leg | 4.5 kW[4]Calculated |
Battery
| Battery voltage | 48 V[1] |
|---|---|
| Battery voltage range | 40 to 60 V[3] |
| Maximum charge current | 140 A[3] |
| Maximum discharge current | 140 A[3] |
| Battery-only output | ? |
| Maximum grid charging | 140 A[4] |
| Compatible batteries / BMS | Lithium-ion, lead-acid or user-defined batteries[4] |
PV input
| PV array limit (connected) | 6000W + 6000W[4] |
|---|---|
| PV input limit (converted) | 6 kW[4]Calculated |
| Maximum PV voltage (Voc) | 600 V[3] |
| MPPT voltage range | 120 to 500 V[3] |
| MPPT trackers | 2[3] |
| String inputs per MPPT | ? |
| PV current per MPPT | 32 A[3] |
| PV short-circuit current | ? |
| PV startup voltage | ? |
Efficiency and modes
| Peak efficiency | 97.6 %[3] |
|---|---|
| CEC weighted efficiency | 96.5 %[3] |
| Battery conversion efficiency | ? |
| Grid / off-grid modes | ? |
| Generator input | Generator input; max. generator charging current 140A[4] |
| Transfer time | typical: 10[4] |
| Idle consumption | ? |
| Parallel units | 6[3] |
Communication and environment
| Communications | RS485/CAN/USB/Dry Contact[3] |
|---|---|
| Operating temperature | -40 to 60 °C[3] |
| Enclosure rating | IP65[3] |
| Operating noise | ? |
Mechanical
| Dimensions | 400 D × 760 D × 250 D mm[3] |
|---|---|
| Weight | 42 kg / 92.59 lb[3] |
Installation (from the manual)
Conductors
| Battery conductors | 43mm²/ 1 AWG[4] |
|---|---|
| AC input conductors | 14mm²/6AWG (L1/L2/N)[4] |
| AC output conductors | 14mm²/6AWG (L1/L2/N)[4] |
| PV conductors | 4mm²/ 12 AWG[4] |
| Ground conductor | ? |
Protection
| Breakers / fuses | Battery breaker 2P-200A; PV breaker 4P-25A per two strings; grid, generator and load breakers 3P-100A[4] |
|---|---|
| AC input breaker | ? |
| AC output breaker | ? |
| Battery fuse or breaker | ? |
| PV disconnect | ? |
Not in the manual: Torque, Clearances and orientation, Grounding, Communication
Page 1 of 2 · Installation values · ? means nothing is recordedAggregated, often community-reported information, not official documentation. Do not rely on it for installation, purchase or compliance decisions; always confirm values with the manufacturer’s official documentation. Charged Reviews accepts no responsibility for errors.