AC output
- Continuous output
- 16 kW [1]
- Peak output
- 2 times rated power, 10s [2]
- AC configuration
- 120/240 V split phase (L1-N 120 V, L1-L2 240 V) [1]
- AC output voltage
- ?
- AC frequency
- ?
- Grid pass-through
- 100 A [1]
- Maximum output per leg
- ?
Battery
- Battery voltage range
- ?
- Maximum charge current
- 300 A [1]
- Maximum discharge current
- 300 A [1]
- Battery-only output
- ?
- Maximum grid charging
- 300 A [1]
- Compatible batteries / BMS
- Li-ion, lead-acid or user-defined batteries; Li-ion charging adapts to the BMS [1]
PV input
- PV array limit (connected)
- ?
- PV input limit (converted)
- ?
- Maximum PV voltage (Voc)
- 650 V [2]
- MPPT voltage range
- 120 to 600 V [2]
- String inputs per MPPT
- ?
- PV current per MPPT
- ?
- PV short-circuit current
- 50 A [1]
- PV startup voltage
- 90 V [1]
Efficiency and modes
- Peak efficiency
- 94.3 % [2]
- CEC weighted efficiency
- ?
- Battery conversion efficiency
- ?
- Grid / off-grid modes
- ?
- Generator input
- Generator input; generator bypass overload current 66.7A [1]
- Transfer time
- typical: 10 [1]
- Idle consumption
- ?
- Parallel units
- 6 count [2]
Communication and environment
- Communications
- ?
- Operating temperature
- ?
- Operating noise
- ?
Mechanical
- Dimensions
- W 514 × H 848.7 × D 190 mm / W 20.2 × H 33.41 × D 7.48 in converted [2]
- Weight
- 47.5 kg / 105 lb converted [2]
Installation (from the manual)
Conductors
- Battery conductors
- 85mm²/000 AWG, two cables per terminal [1]
- AC output conductors
- 35mm²/2 AWG [1]
- PV conductors
- 6mm²/10 AWG [1]
- Ground conductor
- ?
Protection
- Breakers / fuses
- Battery breaker 2P-350A; PV breaker 2P-45A; grid breaker 2P-125A; generator breaker 2P-100A; load breaker 2P-125A [1]
- AC input breaker
- ?
- AC output breaker
- ?
- Battery fuse or breaker
- ?
- PV disconnect
- ?
Not in the manual: Torque, Clearances and orientation, Grounding, Communication