Charged ReviewsSaved 0Compare 0Login

Charged Reviews · Quick reference

Sol-Ark 60K-3P-480V

Brand
Sol-Ark
Model
60K-3P-480V
SKU / part number
?
Category
Inverters

chargedreviews.com/inverters/sol-ark-60k-3p-480v

AC output

Continuous output
60 kW [1]
Peak output
90,000 VA for 10 s (off-grid, three phase) [1]
AC configuration
Three-phase [1]
AC output voltage
480 V [1]
AC frequency
?
Grid pass-through
180 A [2]
Maximum output per leg
?

Battery

Battery voltage
?
Battery voltage range
160 to 700 V [2]
Maximum charge current
?
Maximum discharge current
?
Battery-only output
?
Maximum grid charging
?
Compatible batteries / BMS
?

PV input

PV array limit (connected)
78 kW [1]
PV input limit (converted)
?
Maximum PV voltage (Voc)
1,000 V [1]
MPPT voltage range
150 to 850 [1]
MPPT trackers
4 count [1]
String inputs per MPPT
?
PV current per MPPT
?
PV short-circuit current
?
PV startup voltage
180 V [1]

Efficiency and modes

Peak efficiency
97.5 % [1]
CEC weighted efficiency
96.5 % [1]
Battery conversion efficiency
?
Grid / off-grid modes
?
Generator input
It’s possible to connect a generator, or an AC-coupled source such as grid-tied string or micro inverters, to the GEN terminal of the inverter [2]
Transfer time
15 ms [1]
Idle consumption
?
Parallel units
10 count [1]

Communication and environment

Communications
?
Operating temperature
-40 to 60 °C / -40 to 140 °F converted [1]
Enclosure rating
IP65 [1]
Operating noise
?

Mechanical

Dimensions
W 894 × H 528 × D 295 mm / W 35.2 × H 20.8 × D 11.6 in converted [1]
Weight
80 kg / 180 lb converted [1]

Installation (from the manual)

Torque

AC terminal torque
25.5 N·m [2]
Battery terminal torque
?
PV terminal torque
?
Ground terminal torque
25.5 N·m [2]

Conductors

Battery conductors
6 to 4 AWG (Battery Port A and Battery Port B, 50 A DC each, 105 °C) [2]
AC input conductors
2 AWG to 250 kcmil (GRID terminal, 200 A AC, 105 °C) [2]
AC output conductors
2 AWG to 250 kcmil (LOAD terminal, 200 A AC, 105 °C) [2]
PV conductors
12 to 10 AWG (MPPT, 55 A Isc, 105 °C) [2]
Ground conductor
?

Protection

AC input breaker
?
AC output breaker
?
Battery fuse or breaker
?
PV disconnect
2x PV DC disconnects [2]

Clearances and orientation

Installation clearances
There must be at least 6 in [15 cm] of vertical clearance and 2 in [5 cm] of side clearance for proper heat dissipation. [2]
Mounting orientation
?

Not in the manual: Grounding, Communication

Page 1 of 2 · Installation values · ? means nothing is recordedAggregated, often community-reported information, not official documentation. Do not rely on it for installation, purchase or compliance decisions; always confirm values with the manufacturer’s official documentation. Charged Reviews accepts no responsibility for errors.

Charged Reviews · Quick reference

Sol-Ark 60K-3P-480V · 60K-3P-480V

Warranty

Warranty term10 years[3]
Optional extension?
Coverage startsThe term of this warranty begins on the Product(s) initial purchase date, or the date of receipt of the Product(s) by the end user, whichever is later.[3]
Coverage conditionsExcludes damage from installation or removal, alteration or disassembly, normal wear and tear, accident or abuse, unauthorized firmware or software changes, corrosion, lightning (unless an EMP hardened system), unauthorized repair, operation contrary to instructions, fire, floods or acts of nature, shipping, damage caused by other system components, and altered or removed serial numbers. LCD screen and fans are covered for 5 years from date of purchase.[3]
RemedyRepair or replacement of the Product, at Sol-Ark discretion.[3]
Labor and shippingThis warranty does not cover the costs of installation, removal, shipping (except as described below), or reinstallation of Products or parts of Products.[3]
Transfer to another ownerApplies to the original purchaser and is transferable only if the Product remains installed in the original use location.[3]
RegistrationInstall Operational Verification Checklist Questionnaire must be filled out, signed, and dated to secure full warranty coverage.[3]
Territory?

Certifications and listings

UL 1741?
UL 1741 SA?
UL 1741 SBVerified listed as of snapshot [4]
IEEE 1547?
CA Rule 21?
UL 9540Claimed [5]
FCC Part 15?
CECVerified listed as of snapshot [4]
CECVerified listed as of snapshot [4]

Documents and sources

  1. Sol-Ark datasheet Datasheet · Checked Sep 15, 2026 https://sol-ark.com/wp-content/uploads/2024/05/60K-3P-480V_Datasheet_Rev_10_31July2026.pdf
  2. 60K-3P-480V Installation Manual MA-00021 Rev9 Instruction manual · Checked Sep 19, 2026 https://sol-ark.com/wp-content/uploads/2026/08/60K-3P-480V_Installation_Manual_MA-00021_Rev9_25Au.pdf
  3. 60K-3P-480V Limited Product Warranty V2.0 (EN) Warranty · Checked Sep 19, 2026 https://sol-ark.com/wp-content/uploads/2024/05/60K_3P_480V_Limited_Warranty-1.pdf
  4. CEC Grid Support Inverter Lists (solar and battery inverters), official spreadsheet (data unchanged since October 1, 2026; downloaded October 11, 2026) Government equipment list (spreadsheet) · Revision Data unchanged since October 1, 2026 · Revised Oct 1, 2026 · Checked Oct 10, 2026 https://solarequipment.energy.ca.gov/Home/DownloadtoExcel?filename=InvertersList
  5. Sol-Ark datasheet Datasheet · Checked Sep 15, 2026 https://sol-ark.com/wp-content/uploads/2024/05/PS-00019_Rev-11_480V_Datasheet_16July2025.pdf

Unofficial reference. Information may be incorrect. This sheet aggregates the public sources listed above, much of it community-reported. It is not official manufacturer documentation, not an installation guide and not a compliance record. Community-reported values are checked against official manufacturer information before publication; we cannot guarantee accuracy or completeness. Do not rely on this sheet for installation, purchase or compliance decisions: always confirm every value with the manufacturer’s official documentation before buying, wiring or installing equipment. Charged Reviews accepts no responsibility for errors or omissions. Manufacturers can submit documents or corrections.

Page 2 of 2 · Charged Reviews LLC · chargedreviews.com/inverters/sol-ark-60k-3p-480vSome links pay us a commission. That does not affect what we record.