About brandRiello Solartech is the solar business of Riello Elettronica: its own site says Riello Solartech is an integral part of Riello Elettronica, a holding whose Energy area designs, makes and sells UPS and photovoltaic inverters under the Riello UPS and Riello Solartech brands. Riello Solartech makes string, hybrid and central photovoltaic inverters and storage batteries; its datasheets are published by RPS S.p.A. of Legnago, Italy, Riello Solartech Division, Cormano, Italy.
SKU detail
locator: Datasheet model table
conditions: Riello Solartech's datasheet names the model "SIRIO K250 HV" in its model table and prints no separate SKU, part number or order code.
Sources: No source on record
No spec by that name.
Units
Field
Value
Conditions
Source
Weight
1,750 kg / 3,858 lb converted
The installation manual prints "1750" kg in the row "Weight" (General characteristics, page 30, K250 HV column under "SIRIO HV Model K200 HV K250 HV", Mechanical, Weight), the same value as the datasheet. Datasheet: Printed as "1750" in the row "Weight [kg]", SIRIO K250 HV column.
Where: Installation manual, General characteristics, page 30, K250 HV column under "SIRIO HV Model K200 HV K250 HV", Mechanical, Weight; datasheet, Page 4, Mechanical, Weight [kg], SIRIO K250 HV column
W 1,600 × H 1,900 × D 1,000 mm / W 62.99 × H 74.8 × D 39.37 in converted
The installation manual prints the same dimensions in the row "Dimensions mm" (General characteristics, page 30, K250 HV column under "SIRIO HV Model K200 HV K250 HV", Mechanical, Dimensions), the same value as the datasheet. Datasheet: Printed as "1600x1000x1900" in the row "Dimensions (WxDxH) [mm]" for this model; recorded as width, depth and height in millimeters.
Where: Installation manual, General characteristics, page 30, K250 HV column under "SIRIO HV Model K200 HV K250 HV", Mechanical, Dimensions; datasheet, Page 4, Mechanical, Dimensions (WxDxH) [mm]
Printed as "Ethernet, USB, 2xRS232, 2 inputs for remote controls (inverter trip and EPO) and 3 operating status signal relays. Optional RS485 and ModBUS RTU (slot version)" under "COMMUNICATION INTERFACE" and "ModBUS / TCP" under "PROTOCOL", for every Sirio Central model.
The installation manual prints "450-760 V" in the row "DC voltage range, MPPT" (General characteristics, page 30, K250 HV column under "SIRIO HV Model K200 HV K250 HV", DC voltage range, MPPT Vcc), the same value as the datasheet. Datasheet: Printed as "450 - 760" in the row "DC voltage range, MPPT (Vdc) [V]" for this model.
Where: Installation manual, General characteristics, page 30, K250 HV column under "SIRIO HV Model K200 HV K250 HV", DC voltage range, MPPT Vcc; datasheet, Page 4, Input, DC voltage range, MPPT (Vdc) [V]
The installation manual prints "320" kWp in the row "Max PV power Pmax" (General characteristics, page 30, K250 HV column under "SIRIO HV Model K200 HV K250 HV", Max PV power Pmax), the same value as the datasheet. Datasheet: Printed as "320" in the row "PV max power (Pmax) [kWp]", SIRIO K250 HV column; the largest PV array the model takes, in kWp.
Where: Installation manual, General characteristics, page 30, K250 HV column under "SIRIO HV Model K200 HV K250 HV", Max PV power Pmax; datasheet, Page 4, Input, PV max power (Pmax) [kWp], SIRIO K250 HV column
Riello Solartech documents print different frequency tolerances. The installation manual (0MNPV112K55ENUF), the primary source, prints "50 Hz (+3/-2Hz)" for the K200 HV and K250 HV, which is recorded; every other Sirio table in the manual and the datasheet (DATSIHX0Y26GSEN, page 4) print "50 (+2 / -3)". Both are kept.
Printed as "50 Hz (+3/-2Hz)" in the row "Rated frequency Fca" of the manual's Sirio HV K200 HV and K250 HV table. The datasheet's "50 (+2 / -3)" is kept as an alternative.
Where: Installation manual, General characteristics, page 30, K250 HV column under "SIRIO HV Model K200 HV K250 HV", Rated frequency Fca
Sources
50 Hz (+2 / -3)
Datasheet value, kept beside the installation manual value: Printed as "50 (+2 / -3)" in the row "Nominal frequency (Fca) [Hz]", one value for every model.
Three-phase, 400 V, TT, TN-S, TN-C distribution system
The installation manual prints the same rated voltage in the row "Rated voltage Vca" and the same distribution system (General characteristics, page 30, K250 HV column under "SIRIO HV Model K200 HV K250 HV", Rated voltage Vca and Distribution system), the same value as the datasheet. Datasheet: Printed as "400 three-phase (+ / -15%)" in the row "Nominal voltage (Vac) [V]" and "TT, TN-S, TN-C" in the row "Distribution system" for this model.
Where: Installation manual, General characteristics, page 30, K250 HV column under "SIRIO HV Model K200 HV K250 HV", Rated voltage Vca and Distribution system; datasheet, Page 4, Output, Nominal voltage (Vac) [V] and Distribution system
The installation manual prints "IP20" (General characteristics, page 30, K250 HV column under "SIRIO HV Model K200 HV K250 HV", Ingress protection EN60529), the same value as the datasheet. Datasheet: Printed as "IP20" in the row "Protection level EN60529"; the row "Environmental category" prints "Indoors, not air conditioned".
Where: Installation manual, General characteristics, page 30, K250 HV column under "SIRIO HV Model K200 HV K250 HV", Ingress protection EN60529; datasheet, Page 4, Environmental protections and conditions, Protection level EN60529
The installation manual prints "880 V" in the row "Max DC voltage" (General characteristics, page 30, K250 HV column under "SIRIO HV Model K200 HV K250 HV", Max DC voltage), the same value as the datasheet. Datasheet: Printed as "880" in the row "Max DC voltage (Vdc, max) [V]", one value for every model on the page.
Where: Installation manual, General characteristics, page 30, K250 HV column under "SIRIO HV Model K200 HV K250 HV", Max DC voltage; datasheet, Page 4, Input, Max DC voltage (Vdc, max) [V]
The installation manual prints "540 V" in the row "Start-up voltage" (General characteristics, page 30, K250 HV column under "SIRIO HV Model K200 HV K250 HV", Start-up voltage), the same value as the datasheet. Datasheet: Printed as "540" in the row "Start-up voltage (Vstart-up) [V]" for this model.
Where: Installation manual, General characteristics, page 30, K250 HV column under "SIRIO HV Model K200 HV K250 HV", Start-up voltage; datasheet, Page 4, Input, Start-up voltage (Vstart-up) [V]
The installation manual prints "250" kW in the row "Rated AC power" (General characteristics, page 30, K250 HV column under "SIRIO HV Model K200 HV K250 HV", Rated AC power Pca), the same value as the datasheet. Datasheet: Printed as "250" in the row "Nominal AC power (p.f. =1) (Pca) [kW]", SIRIO K250 HV column.
Where: Installation manual, General characteristics, page 30, K250 HV column under "SIRIO HV Model K200 HV K250 HV", Rated AC power Pca; datasheet, Page 4, Output, Nominal AC power (p.f. =1) (Pca) [kW], SIRIO K250 HV column
The installation manual prints "361" A in the row "Rated current Ica" (General characteristics, page 30, K250 HV column under "SIRIO HV Model K200 HV K250 HV", Rated current Ica), the same value as the datasheet. Datasheet: Printed as "361" in the row "Rated current (Ica) [Aca]", SIRIO K250 HV column.
Where: Installation manual, General characteristics, page 30, K250 HV column under "SIRIO HV Model K200 HV K250 HV", Rated current Ica; datasheet, Page 4, Output, Rated current (Ica) [Aca], SIRIO K250 HV column
The installation manual prints "620" A in the row the manual labels "Max DC current" (the datasheet labels the same row "Max short circuit current") (General characteristics, page 30, K250 HV column under "SIRIO HV Model K200 HV K250 HV", Max DC current), the same value as the datasheet. Datasheet: Printed as "620" in the row "Max short circuit current (Icc, max) [A]", SIRIO K250 HV column.
Where: Installation manual, General characteristics, page 30, K250 HV column under "SIRIO HV Model K200 HV K250 HV", Max DC current; datasheet, Page 4, Input, Max short circuit current (Icc, max) [A], SIRIO K250 HV column
The installation manual prints "250" kW in the row "Max AC power Pca 1h" (General characteristics, page 30, K250 HV column under "SIRIO HV Model K200 HV K250 HV", Max AC power Pca 1h), the same value as the datasheet. Datasheet: Printed as "250" in the row "Max AC power (Pca 1h) [kW]", SIRIO K250 HV column; a one-hour rating as printed.
Where: Installation manual, General characteristics, page 30, K250 HV column under "SIRIO HV Model K200 HV K250 HV", Max AC power Pca 1h; datasheet, Page 4, Output, Max AC power (Pca 1h) [kW], SIRIO K250 HV column
The installation manual prints "-10°C – 50°C" in the row "Permitted temperature range", noted "with ambient temperature over 45°C there will be a reduction of max power to the network" (General characteristics, page 30, K250 HV column under "SIRIO HV Model K200 HV K250 HV", Permitted temperature range), the same value as the datasheet. Datasheet: Printed as "-10 to 50" for every model on page 4; page 1 says the Sirio Central models deliver nominal power up to 45 °C ambient.
Where: Installation manual, General characteristics, page 30, K250 HV column under "SIRIO HV Model K200 HV K250 HV", Permitted temperature range; datasheet, Page 4, Environmental protections and conditions, Permissible temperature range (T) [°C]
320 kWMPPT trackersNot statedMPPT range450 to 760 V
AC output
Three-phase, 400 V, TT, TN-S, TN-C distribution system
Warranty
Not stated
Size
3,040 L* (Calculated from published dimensions)W: 1,600 × H: 1,900 × D: 1,000 mm / W: 62.99 × H: 74.8 × D: 39.37 inWeight1,750 kg / 3,858 lb
Evidence score
Research pending0% documented
The Evidence score uses the priorities you choose. It counts published documents, such as certificates and warranty terms, and it compares a documented figure with the best documented figure of the same kind. It does not count owner reviews, and it is not a verdict on product quality or on how many people have reviewed it. A low score can mean little is documented, or that a documented figure is below the best of its kind. Undisclosed data scores 0.
Missing for this product: Certificate evidence needed; Warranty term needed; Battery conversion efficiency needed; Idle consumption needed.
Each input is scored against the best documented value for an inverter: warranty term and battery conversion efficiency against every published inverter, idle consumption (lower is better) against the inverters in the same output band, or against every published inverter when the output is not documented. A documented value always earns points; an undisclosed one earns 0 and is listed as missing. Researched products receive a score. Certificates earn points for the evidence itself. Size and weight do not affect scores.
Warranty term and battery conversion efficiency are compared with every published inverter; idle consumption with the inverters in the same over 50 kW output band. · Method version 0.5
Location: General characteristics tables, manual pages 24 to 30
Retrieved Oct 21, 2026
Riello Solartech's own English user and installation manual (PDF), linked from the download area of www.riello-solartech.com and captured on October 22, 2026. It covers the Sirio K12 to K200 and Sirio HV K25 HV to K250 HV central inverters; its technical specifications appendix is the primary source for the values it prints for those exact models. Manufacturer document, not an independent test.
Archived copies
Archived copy of a document published by Riello Solartech. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email [email protected].
Location: Pages 3, 4, 7 and 8, model tables; pages 1 and 5, product photos
Retrieved Oct 21, 2026
Riello Solartech's own English datasheet (PDF, published by RPS S.p.A., Riello Solartech Division), linked from the product's download area on www.riello-solartech.com and captured on October 22, 2026. The tables merge cells that apply to several models; every value was paired with its model columns on the rendered page. The datasheet says the product photos are merely an indication and that features may change without notice. Manufacturer document, not an independent test.
Archived copies
Archived copy of a document published by Riello Solartech. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email [email protected].
Riello Solartech's own product page (www.riello-solartech.com, English edition), captured on October 22, 2026 with the paced research fetcher; the content is whatever the address served on that date. Manufacturer statements, not independent tests; the page carries no revision date.
Earlier revisions, archived captures and copies published by someone other than the manufacturer. Every one stays reachable.
Archived documents
Riello Solartech user manual: Sirio central inverters K12 to K250 and Sirio HV (no HV MT, no HHV MT), 0MNPV112K55ENUF Rev. 00
Archived copy of a document published by Riello Solartech. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email [email protected].
Riello Solartech datasheet: Sirio Central Inverters and Sirio Central Inverters MV, DATSIHX0Y26GSEN
Archived copy of a document published by Riello Solartech. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email [email protected].
Product prices and availability are accurate as of the date/time indicated and are subject to change. Any price and availability information displayed on Amazon.com at the time of purchase will apply to the purchase of this product. CERTAIN CONTENT THAT APPEARS ON THIS SITE COMES FROM AMAZON. THIS CONTENT IS PROVIDED ‘AS IS’ AND IS SUBJECT TO CHANGE OR REMOVAL AT ANY TIME.