Hoymiles HAS-9.6LV-USG1

Brand
Hoymiles
Model
HAS-9.6LV-USG1
SKU / part number
HAS-9.6LV-USG1 [1]
Category
Inverters

chargedreviews.com/inverters/hoymiles-has-9-6lv-usg1

AC output

Continuous output
9.6 kW [1]
Peak output
19200 VA for 10 s (off-grid output) [1]
AC configuration
Grid: 240 V (211 to 264 V) or 208 V (183 to 229 V), 60 Hz; backup output: 120/240 V split phase or 120/208 V, 60 Hz [1]
AC output voltage
?
AC frequency
?
Grid pass-through
?
Maximum output per leg
?

Battery

Battery voltage
?
Battery voltage range
40 to 60 V [1]
Maximum charge current
200 A [1]
Maximum discharge current
200 A [1]
Battery-only output
?
Maximum grid charging
?
Compatible batteries / BMS
?

PV input

PV array limit (connected)
?
PV input limit (converted)
?
Maximum PV voltage (Voc)
?
MPPT voltage range
?
MPPT trackers
?
String inputs per MPPT
?
PV current per MPPT
?
PV short-circuit current
?
PV startup voltage
?

Efficiency and modes

Peak efficiency
?
CEC weighted efficiency
?
Battery conversion efficiency
95 % [1]
Grid / off-grid modes
?
Generator input
?
Transfer time
40 ms [1]
Idle consumption
?
Parallel units
10 [1]

Communication and environment

Communications
RS485; Wi-Fi (optional); Ethernet (optional, printed as coming soon); 4G (optional, printed as coming soon) [1]
Operating temperature
-25 to 65 °C / -13 to 149 °F converted [1]
Enclosure rating
Type 4X [1]
Operating noise
?

Mechanical

Dimensions
W 502 × H 740 × D 202 mm / W 19.8 × H 29.1 × D 7.95 in converted [1]
Weight
37 kg / 82 lb converted [1]

Installation (from the manual)

Torque

AC terminal torque
?
Battery terminal torque
22.6 N·m [2]
PV terminal torque
?
Ground terminal torque
3 N·m [2]

Conductors

Battery conductors
?
AC input conductors
?
AC output conductors
?
PV conductors
?
Ground conductor
Grid Ground Cable 8 AWG; Battery Ground Cable 6 AWG; EPS/GEN Ground Cable 8 AWG [2]

Protection

AC input breaker
GEN port recommended AC breaker 50 A/240 V [2]
AC output breaker
Recommended circuit breaker: Grid L1/L2 100 A; EPS/GEN L1/L2 50 A [2]
Battery fuse or breaker
two-pole DC breaker with OCP between inverter and battery (recommended 250 A) [2]
PV disconnect
?

Clearances and orientation

Installation clearances
≥300 mm above, ≥500 mm below, ≥200 mm on the left, ≥200 mm on the right, ≥300 mm in front [2]
Mounting orientation
vertically or at a maximum back tilt of 15°; wall mount on the supplied bracket [2]

Grounding

Grounding and neutral-ground bonding
ground cables (battery, grid, EPS/GEN) to the inverter grounding bar; PV positive and negative not grounded [2]

Communication

Communication ports
Parallel; BMS; Meter; DI; EPO_P/EPO_N; DO1; DO2; USB port (DTS) [2]
Page 1 of 2 · Installation values · ? means nothing is recordedAggregated, often community-reported information, not official documentation. Do not rely on it for installation, purchase or compliance decisions; always confirm values with the manufacturer’s official documentation. Charged Reviews accepts no responsibility for errors.

Charged Reviews · Quick reference

Hoymiles HAS-9.6LV-USG1 · HAS-9.6LV-USG1

Warranty

Warranty term10 years[1]
Optional extension?
Coverage starts?
Coverage conditions?
Remedy?
Labor and shipping?
Transfer to another owner?
Registration?
Territory?

Certifications and listings

UL 1741?
UL 1741 SA?
UL 1741 SBVerified listed as of snapshot [3]
IEEE 1547?
CA Rule 21?
UL 9540?
FCC Part 15?
CECVerified listed as of snapshot [3]

Documents and sources

  1. Hoymiles Product Brochure for North America (hoymiles.com, September 27, 2026 capture) Manufacturer product brochure (PDF) · Checked Sep 26, 2026 https://www.hoymiles.com/uploadfile/1/202507/e84c726be6.pdf
  2. Hoymiles Hybrid/AC-coupled Inverter User Manual, HYS/HAS-(3.8-11.5)LV-USG1, Region: North America (REV2.5) User manual · Revision REV2.5 · Checked Oct 1, 2026 https://w3oss.hoymiles.com/uploadfile/1/202506/92cb159c9b.pdf
  3. CEC Grid Support Inverter Lists (solar and battery inverters), official spreadsheet (data unchanged since October 1, 2026; downloaded October 11, 2026) Government equipment list (spreadsheet) · Revision Data unchanged since October 1, 2026 · Revised Oct 1, 2026 · Checked Oct 10, 2026 https://solarequipment.energy.ca.gov/Home/DownloadtoExcel?filename=InvertersList

Unofficial reference. Information may be incorrect. This sheet aggregates the public sources listed above, much of it community-reported. It is not official manufacturer documentation, not an installation guide and not a compliance record. Community-reported values are checked against official manufacturer information before publication; we cannot guarantee accuracy or completeness. Do not rely on this sheet for installation, purchase or compliance decisions: always confirm every value with the manufacturer’s official documentation before buying, wiring or installing equipment. Charged Reviews accepts no responsibility for errors or omissions. Manufacturers can submit documents or corrections.

Page 2 of 2 · Charged Reviews LLC · chargedreviews.com/inverters/hoymiles-has-9-6lv-usg1Some links pay us a commission. That does not affect what we record.