Charged Reviews · Quick reference
Hoymiles HAS-3.8LV-USG1
- Brand
- Hoymiles
- Model
- HAS-3.8LV-USG1
- SKU / part number
- HAS-3.8LV-USG1[1]
- Category
- Inverters
AC output
| Continuous output | 3.84 kW[1]Calculated |
|---|---|
| Peak output | 7680 VA for 10 s (off-grid output)[1] |
| AC configuration | Grid: 240 V (211 to 264 V) or 208 V (183 to 229 V), 60 Hz; backup output: 120/240 V split phase or 120/208 V, 60 Hz[1] |
| AC output voltage | ? |
| AC frequency | ? |
| Grid pass-through | ? |
| Maximum output per leg | ? |
Battery
| Battery voltage | ? |
|---|---|
| Battery voltage range | 40 to 60 V[1] |
| Maximum charge current | 80 A[1] |
| Maximum discharge current | 80 A[1] |
| Battery-only output | ? |
| Maximum grid charging | ? |
| Compatible batteries / BMS | ? |
PV input
| PV array limit (connected) | ? |
|---|---|
| PV input limit (converted) | ? |
| Maximum PV voltage (Voc) | ? |
| MPPT voltage range | ? |
| MPPT trackers | ? |
| String inputs per MPPT | ? |
| PV current per MPPT | ? |
| PV short-circuit current | ? |
| PV startup voltage | ? |
Efficiency and modes
| Peak efficiency | ? |
|---|---|
| CEC weighted efficiency | ? |
| Battery conversion efficiency | 95 %[1] |
| Grid / off-grid modes | ? |
| Generator input | ? |
| Transfer time | 40 ms[1] |
| Idle consumption | ? |
| Parallel units | 10[1] |
Communication and environment
| Communications | RS485; Wi-Fi (optional); Ethernet (optional, printed as coming soon); 4G (optional, printed as coming soon)[1] |
|---|---|
| Operating temperature | -25 to 65 °C[1] |
| Enclosure rating | Type 4X[1] |
| Operating noise | ? |
Mechanical
| Dimensions | 202 D × 502 W × 615 H mm[1] |
|---|---|
| Weight | 28 kg / 61.73 lb[1] |
Installation (from the manual)
Torque
| AC terminal torque | ? |
|---|---|
| Battery terminal torque | 15 N·m(132.76 in-lb*)[2] |
| PV terminal torque | ? |
| Ground terminal torque | 3 N·m(26.55 in-lb*)[2] |
Conductors
| Battery conductors | ? |
|---|---|
| AC input conductors | ? |
| AC output conductors | ? |
| PV conductors | ? |
| Ground conductor | Grid Ground Cable 8 AWG; Battery Ground Cable 8 AWG; EPS/GEN Ground Cable 8 AWG[2] |
Protection
| AC input breaker | GEN port recommended AC breaker 20 A/240 V[2] |
|---|---|
| AC output breaker | Recommended circuit breaker: Grid L1/L2 40 A; EPS/GEN L1/L2 20 A[2] |
| Battery fuse or breaker | two-pole DC breaker with OCP between inverter and battery (recommended 100 A)[2] |
| PV disconnect | ? |
Clearances and orientation
| Installation clearances | ≥300 mm above, ≥500 mm below, ≥200 mm on the left, ≥200 mm on the right, ≥300 mm in front[2] |
|---|---|
| Mounting orientation | vertically or at a maximum back tilt of 15°; wall mount on the supplied bracket[2] |
Grounding
| Grounding and neutral-ground bonding | ground cables (battery, grid, EPS/GEN) to the inverter grounding bar; PV positive and negative not grounded[2] |
|---|
Communication
| Communication ports | Parallel; BMS; Meter; DI; EPO_P/EPO_N; DO1; DO2; USB port (DTS)[2] |
|---|
Page 1 of 2 · Installation values · ? means nothing is recordedAggregated, often community-reported information, not official documentation. Do not rely on it for installation, purchase or compliance decisions; always confirm values with the manufacturer’s official documentation. Charged Reviews accepts no responsibility for errors.