Printed as "Weight 5.7lbs(2.7kg)" in the DS3 series datasheet (Region USA, Rev2.2, 2025/01/20) and in the DS3 Series User manual's section 8.1 datasheet table (Rev2.1, 2025/01/20), row "Weight", DS3-S column. Both documents print the same figure.
Printed as "Maximum Continuous Output Power 640VA" in the DS3-S column of the DS3 series datasheet and the DS3 Series User manual's section 8.1 table. The documents label this row "Maximum Continuous Output Power", not "peak output power"; no separate peak (surge) output figure is printed, and none is inferred.
Printed as "Dimensions (W x H x D) 10.3” × 8.6” × 1.6” (263mm x 218mm x 41.2mm)" in the DS3 series datasheet and the DS3 Series User manual's section 8.1 datasheet table, DS3-S column. Axis order as printed (W x H x D); recorded here as width, height, depth to match this catalog's dimension fields.
Printed as "Peak Efficiency 97.3%" in the DS3 series datasheet and the DS3 Series User manual's section 8.1 table, one shared row for all three USA models. The same table also prints "CEC Efficiency 97%" and "Nominal MPPT Efficiency 99.5%"; this field records the peak efficiency figure, to match how this catalog's other microinverter records use this field.
Printed as "Peak Power Tracking Voltage 28V-45V" in the DS3 series datasheet, one shared row for all three USA models. This row is not printed in the DS3 Series User manual's shorter section 8.1 table, so the datasheet is the only source.
Printed as "Nominal Output Voltage/Range(1) 208V/183.04-228.8V; 240V/211V-264V" in the DS3 series datasheet, one shared row for all three USA models; the DS3 Series User manual's section 8.1 table prints the same figures with a space before each slash ("208V / 183.04-228.8V; 240V / 211V-264V"). Footnote (1): nominal voltage/frequency range can be extended beyond nominal if required by the utility.
Printed as "Maximum Input Voltage 60V" in the DS3 series datasheet and the DS3 Series User manual's section 8.1 table, one shared row for all three USA models.
Printed as "Maximum Continuous Output Power 640VA 768VA 880VA" in the APsystems DS3 Series User manual for North America (Rev2.1, section 8.1, columns "Model DS3-S DS3-L DS3") and in the DS3 series datasheet (Rev2.2); 640VA is the DS3-S (first) column. Both copies are third-party-hosted copies of APsystems' own documents. Stored in VA as printed.
Location: DS3 Series User manual (Rev2.1), 8.1 DS3 series Microinverter Datasheet, Output Data (AC), "Maximum Continuous Output Power" row, DS3-S column, PDF page 22; DS3 series datasheet (Rev2.2), same row
Printed as "Maximum Continuous Output Power 640VA" in the DS3-S column of the DS3 series datasheet and the DS3 Series User manual's section 8.1 table. The documents label this row "Maximum Continuous Output Power", not "peak output power"; no separate peak (surge) output figure is printed, and none is inferred.
Printed as "Peak Efficiency 97.3%" in the DS3 series datasheet and the DS3 Series User manual's section 8.1 table, one shared row for all three USA models. The same table also prints "CEC Efficiency 97%" and "Nominal MPPT Efficiency 99.5%"; this field records the peak efficiency figure, to match how this catalog's other microinverter records use this field.
Printed as "Nominal Output Voltage/Range(1) 208V/183.04-228.8V; 240V/211V-264V" in the DS3 series datasheet, one shared row for all three USA models; the DS3 Series User manual's section 8.1 table prints the same figures with a space before each slash ("208V / 183.04-228.8V; 240V / 211V-264V"). Footnote (1): nominal voltage/frequency range can be extended beyond nominal if required by the utility.
Printed as "Maximum Continuous Output Power 640VA 768VA 880VA" in the APsystems DS3 Series User manual for North America (Rev2.1, section 8.1, columns "Model DS3-S DS3-L DS3") and in the DS3 series datasheet (Rev2.2); 640VA is the DS3-S (first) column. Both copies are third-party-hosted copies of APsystems' own documents. Stored in VA as printed.
Location: DS3 Series User manual (Rev2.1), 8.1 DS3 series Microinverter Datasheet, Output Data (AC), "Maximum Continuous Output Power" row, DS3-S column, PDF page 22; DS3 series datasheet (Rev2.2), same row
Printed as "Peak Power Tracking Voltage 28V-45V" in the DS3 series datasheet, one shared row for all three USA models. This row is not printed in the DS3 Series User manual's shorter section 8.1 table, so the datasheet is the only source.
Printed as "Maximum Input Voltage 60V" in the DS3 series datasheet and the DS3 Series User manual's section 8.1 table, one shared row for all three USA models.
Printed as "Weight 5.7lbs(2.7kg)" in the DS3 series datasheet (Region USA, Rev2.2, 2025/01/20) and in the DS3 Series User manual's section 8.1 datasheet table (Rev2.1, 2025/01/20), row "Weight", DS3-S column. Both documents print the same figure.
Printed as "Dimensions (W x H x D) 10.3” × 8.6” × 1.6” (263mm x 218mm x 41.2mm)" in the DS3 series datasheet and the DS3 Series User manual's section 8.1 datasheet table, DS3-S column. Axis order as printed (W x H x D); recorded here as width, height, depth to match this catalog's dimension fields.
Printed as "Operating Ambient Temperature Range(3) -40°F to +149°F (-40°C to +65°C)" in the DS3 series datasheet and the DS3 Series User manual's section 8.1 table, one shared row for all three USA models. Footnote (3): the inverter may enter power de-grade mode under poor ventilation and heat dissipation installation environments.
Location: Mechanical Data, Operating Ambient Temperature Range row
Documented
Published claims and calculations, not independent test results.
Documents
3 on file
PDF
APsystems DS3 Microinverter Series datasheet, USA region, Rev2.2 (2025/01/20 in the file, third-party-hosted copy)APsystemsDistributor datasheetJanuary 20, 2025
Certificate & compliance claims (10)
UL1741Manufacturer claim · unresolved document setClaimedListed when checked
The DS3 series datasheet (Region USA, Rev2.2) prints, in one row shared across all three USA models: "Safety and EMC Compliance UL1741; CSA C22.2 No.107.1-16; FCC Part15B; ICES-003 Class B; IEEE1547; UL1741SB;CA Rule 21 (UL1741-SA);SRD-V2.0; NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.11 DC Arc-Fault circuit Protection NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.12 Rapid Shutdown of PV systems on Buildings". This row records "UL1741". UL 1741, Standard for Inverters, Converters, Controllers and Interconnection System Equipment for Use With Distributed Energy Resources. Printed without a specific sub-standard edition or scope. No certificate, report number or issuer record was read; this is the manufacturer's own printed claim only, not independently verified against the standard issuer's directory.
CSA C22.2 No.107.1-16Manufacturer claim · unresolved document setClaimedListed when checked
The DS3 series datasheet (Region USA, Rev2.2) prints, in one row shared across all three USA models: "Safety and EMC Compliance UL1741; CSA C22.2 No.107.1-16; FCC Part15B; ICES-003 Class B; IEEE1547; UL1741SB;CA Rule 21 (UL1741-SA);SRD-V2.0; NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.11 DC Arc-Fault circuit Protection NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.12 Rapid Shutdown of PV systems on Buildings". This row records "CSA C22.2 No.107.1-16". CSA Group standard C22.2 No.107.1-16, Power conversion equipment, the Canadian counterpart cited alongside the UL entries. No certificate, report number or issuer record was read; this is the manufacturer's own printed claim only, not independently verified against the standard issuer's directory.
FCC Part15BManufacturer claim · unresolved document setClaimedListed when checked
The DS3 series datasheet (Region USA, Rev2.2) prints, in one row shared across all three USA models: "Safety and EMC Compliance UL1741; CSA C22.2 No.107.1-16; FCC Part15B; ICES-003 Class B; IEEE1547; UL1741SB;CA Rule 21 (UL1741-SA);SRD-V2.0; NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.11 DC Arc-Fault circuit Protection NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.12 Rapid Shutdown of PV systems on Buildings". This row records "FCC Part15B". US FCC Part 15 Subpart B, radio-frequency emissions. No certificate, report number or issuer record was read; this is the manufacturer's own printed claim only, not independently verified against the standard issuer's directory.
ICES-003 Class BManufacturer claim · unresolved document setClaimedListed when checked
The DS3 series datasheet (Region USA, Rev2.2) prints, in one row shared across all three USA models: "Safety and EMC Compliance UL1741; CSA C22.2 No.107.1-16; FCC Part15B; ICES-003 Class B; IEEE1547; UL1741SB;CA Rule 21 (UL1741-SA);SRD-V2.0; NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.11 DC Arc-Fault circuit Protection NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.12 Rapid Shutdown of PV systems on Buildings". This row records "ICES-003 Class B". Industry Canada ICES-003 Class B, radio-frequency emissions for Canada. No certificate, report number or issuer record was read; this is the manufacturer's own printed claim only, not independently verified against the standard issuer's directory.
IEEE1547Manufacturer claim · unresolved document setClaimedListed when checked
The DS3 series datasheet (Region USA, Rev2.2) prints, in one row shared across all three USA models: "Safety and EMC Compliance UL1741; CSA C22.2 No.107.1-16; FCC Part15B; ICES-003 Class B; IEEE1547; UL1741SB;CA Rule 21 (UL1741-SA);SRD-V2.0; NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.11 DC Arc-Fault circuit Protection NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.12 Rapid Shutdown of PV systems on Buildings". This row records "IEEE1547". IEEE 1547, Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces. No certificate, report number or issuer record was read; this is the manufacturer's own printed claim only, not independently verified against the standard issuer's directory.
UL1741SBManufacturer claim · unresolved document setClaimedListed when checked
The DS3 series datasheet (Region USA, Rev2.2) prints, in one row shared across all three USA models: "Safety and EMC Compliance UL1741; CSA C22.2 No.107.1-16; FCC Part15B; ICES-003 Class B; IEEE1547; UL1741SB;CA Rule 21 (UL1741-SA);SRD-V2.0; NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.11 DC Arc-Fault circuit Protection NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.12 Rapid Shutdown of PV systems on Buildings". This row records "UL1741SB". UL 1741 SB, the Supplement B grid-support utility-interactive inverter requirements. No certificate, report number or issuer record was read; this is the manufacturer's own printed claim only, not independently verified against the standard issuer's directory.
CA Rule 21 (UL1741-SA)Manufacturer claim · unresolved document setClaimedListed when checked
The DS3 series datasheet (Region USA, Rev2.2) prints, in one row shared across all three USA models: "Safety and EMC Compliance UL1741; CSA C22.2 No.107.1-16; FCC Part15B; ICES-003 Class B; IEEE1547; UL1741SB;CA Rule 21 (UL1741-SA);SRD-V2.0; NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.11 DC Arc-Fault circuit Protection NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.12 Rapid Shutdown of PV systems on Buildings". This row records "CA Rule 21 (UL1741-SA)". California Rule 21 smart inverter requirements, printed with UL1741-SA in parentheses. No certificate, report number or issuer record was read; this is the manufacturer's own printed claim only, not independently verified against the standard issuer's directory.
SRD-V2.0Manufacturer claim · unresolved document setClaimedListed when checked
The DS3 series datasheet (Region USA, Rev2.2) prints, in one row shared across all three USA models: "Safety and EMC Compliance UL1741; CSA C22.2 No.107.1-16; FCC Part15B; ICES-003 Class B; IEEE1547; UL1741SB;CA Rule 21 (UL1741-SA);SRD-V2.0; NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.11 DC Arc-Fault circuit Protection NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.12 Rapid Shutdown of PV systems on Buildings". This row records "SRD-V2.0". Printed as "SRD-V2.0" with no further description; recorded as printed, not expanded. No certificate, report number or issuer record was read; this is the manufacturer's own printed claim only, not independently verified against the standard issuer's directory.
NEC 690.11 DC Arc-Fault Circuit ProtectionManufacturer claim · unresolved document setClaimedListed when checked
The DS3 series datasheet (Region USA, Rev2.2) prints, in one row shared across all three USA models: "Safety and EMC Compliance UL1741; CSA C22.2 No.107.1-16; FCC Part15B; ICES-003 Class B; IEEE1547; UL1741SB;CA Rule 21 (UL1741-SA);SRD-V2.0; NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.11 DC Arc-Fault circuit Protection NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.12 Rapid Shutdown of PV systems on Buildings". This row records "NEC 690.11 DC Arc-Fault Circuit Protection". NEC 2014, 2017, 2020 and 2023 Section 690.11, DC arc-fault circuit protection for PV systems, printed as one combined entry across the four code editions. No certificate, report number or issuer record was read; this is the manufacturer's own printed claim only, not independently verified against the standard issuer's directory.
NEC 690.12 Rapid ShutdownManufacturer claim · unresolved document setClaimedListed when checked
The DS3 series datasheet (Region USA, Rev2.2) prints, in one row shared across all three USA models: "Safety and EMC Compliance UL1741; CSA C22.2 No.107.1-16; FCC Part15B; ICES-003 Class B; IEEE1547; UL1741SB;CA Rule 21 (UL1741-SA);SRD-V2.0; NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.11 DC Arc-Fault circuit Protection NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.12 Rapid Shutdown of PV systems on Buildings". This row records "NEC 690.12 Rapid Shutdown". NEC 2014, 2017, 2020 and 2023 Section 690.12, rapid shutdown of PV systems on buildings, printed as one combined entry across the four code editions. No certificate, report number or issuer record was read; this is the manufacturer's own printed claim only, not independently verified against the standard issuer's directory.
APsystems' own DS3 Series USA-region datasheet ("Region USA", printed revision "2025/01/20 Rev2.2"), as a copy hosted by the distributor American Solar (american-solar.com), captured September 27, 2026. APsystems' own document library serves this datasheet only through apsystems.filecloudonline.com, whose robots.txt disallows every path, so a third-party-hosted copy of the manufacturer's own datasheet is cited instead, labeled as that kind of source. It covers all three USA DS3 models (DS3-S, DS3-L, DS3) in one table, distinguished by column.
APsystems DS3 Series User manual, for North America, Rev2.1 (2025/01/20 in the file, third-party-hosted copy)OfficialAPsystemsOfficial instruction manualJanuary 20, 2025
Source details
Revision
Rev2.1
Revision date
January 20, 2025
Location: Section 8.1, DS3 series Microinverter Datasheet, page 21
Retrieved
APsystems' own DS3 series (DS3-S, DS3-L, DS3) installation and operation manual "For North America" (printer's legal entity ALTENERGY POWER SYSTEM Inc., address 8627 N. Mopac Expy, Suite 150, Austin, TX 78759; printed revision "2025/01/20 REV2.1"), as a copy hosted by the retailer Coast2Coast Solar (coast2coastsolar.com), captured September 27, 2026. APsystems' own document library serves this manual only through apsystems.filecloudonline.com, whose robots.txt disallows every path, so a third-party-hosted copy of the manufacturer's own manual is cited instead. Its section 8.1 ("DS3 series Microinverter Datasheet", page 21) repeats a shorter version of the standalone datasheet's table (no warranty duration, no Peak Power Tracking Voltage, no Recommended PV Module Power range, no compliance list); manual-first applies to the rows it does carry, and the standalone datasheet is the only source for the rows it does not.
Archived copies
Archived copy of a document published by APsystems. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email legal@chargedreviews.com.
Location: Product summary, SKU line (ap-single-sku); product photograph
Retrieved
APsystems' own US store product page for the DS3-S, captured September 27, 2026. Its WooCommerce product summary prints the manufacturer's own ordering SKU (119001) and lists the product's own photograph; the page's SPECIFICATIONS tab loads by script and was not read from this static capture, so specification figures for this model are taken from the DS3 datasheet and installation manual instead.
Earlier revisions, archived captures and copies published by someone other than the manufacturer. Every one stays reachable.
WEB
APsystems DS3 Microinverter, family page (usa.apsystems.com, September 27, 2026 capture)OfficialAPsystemsOfficial product page
Source details
Revision
Not stated
Revision date
Not stated
Location: Product family description; PRODUCT MODELS list
Retrieved
APsystems' own US product family page for the DS3 series, captured September 27, 2026. Names the three models (DS3-S, DS3-L, DS3) and their maximum continuous output power, and links the DS3 datasheet and manual through the document library, which APsystems hosts on apsystems.filecloudonline.com (robots.txt disallow: / for the whole filecloudonline.com site, so that copy could not be fetched; a third-party-hosted copy of the same documents is cited instead). No revision date is printed on the page itself.
APsystems DS3 Series User manual, for North America, Rev2.1 (2025/01/20 in the file, third-party-hosted copy)
Archived copy of a document published by APsystems. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email legal@chargedreviews.com.
Printed as "Warranty(5) 25 Years Standard" in the DS3 series datasheet, one shared row for all three USA models. Footnote (5): to be eligible for the warranty, APsystems microinverters need to be monitored via the EMA portal; Not printed in the DS3 Series User manual's shorter section 8.1 table.
The Evidence score uses the priorities you choose. It counts published documents, such as certificates and warranty terms, and it compares a documented figure with the best documented figure of the same kind. It does not count owner reviews, and it is not a verdict on product quality or on how many people have reviewed it. A low score can mean little is documented, or that a documented figure is below the best of its kind. Undisclosed data scores 0.
Missing details. This number counts only the evidence recorded so far. The source review for this product is not finished, or the maker has not disclosed enough, so the number can only go up.
Missing for this product: Battery conversion efficiency needed; Idle consumption needed.
Each input is scored against the best documented value for an inverter: warranty term and battery conversion efficiency against every published inverter, idle consumption (lower is better) against the inverters in the same output band, or against every published inverter when the output is not documented. A documented value always earns points; an undisclosed one earns 0 and is listed as missing. Researched products receive a score. Certificates earn points for the evidence itself. Size and weight do not affect scores.
This is the best documented for an inverter, printed by the maker. 47 inverters share this value.
Printed as "Warranty(5) 25 Years Standard" in the DS3 series datasheet, one shared row for all three USA models. Footnote (5): to be eligible for the warranty, APsystems microinverters need to be monitored via the EMA portal; full terms are stated to be at usa.APsystems.com, not read in this pass. Not printed in the DS3 Series User manual's shorter section 8.1 table.
Research pending, 0 points: Battery conversion efficiency, Idle consumption.
Warranty term and battery conversion efficiency are compared with every published inverter; idle consumption with every published inverter because its output is not documented. · Method version 0.5
UL1741Product / system scope unresolvedClaimedListed when checked
The DS3 series datasheet (Region USA, Rev2.2) prints, in one row shared across all three USA models: "Safety and EMC Compliance UL1741; CSA C22.2 No.107.1-16; FCC Part15B; ICES-003 Class B; IEEE1547; UL1741SB;CA Rule 21 (UL1741-SA);SRD-V2.0; NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.11 DC Arc-Fault circuit Protection NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.12 Rapid Shutdown of PV systems on Buildings". This row records "UL1741". UL 1741, Standard for Inverters, Converters, Controllers and Interconnection System Equipment for Use With Distributed Energy Resources. Printed without a specific sub-standard edition or scope. No certificate, report number or issuer record was read; this is the manufacturer's own printed claim only, not independently verified against the standard issuer's directory.
CSA C22.2 No.107.1-16Product / system scope unresolvedClaimedListed when checked
The DS3 series datasheet (Region USA, Rev2.2) prints, in one row shared across all three USA models: "Safety and EMC Compliance UL1741; CSA C22.2 No.107.1-16; FCC Part15B; ICES-003 Class B; IEEE1547; UL1741SB;CA Rule 21 (UL1741-SA);SRD-V2.0; NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.11 DC Arc-Fault circuit Protection NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.12 Rapid Shutdown of PV systems on Buildings". This row records "CSA C22.2 No.107.1-16". CSA Group standard C22.2 No.107.1-16, Power conversion equipment, the Canadian counterpart cited alongside the UL entries. No certificate, report number or issuer record was read; this is the manufacturer's own printed claim only, not independently verified against the standard issuer's directory.
FCC Part15BProduct / system scope unresolvedClaimedListed when checked
The DS3 series datasheet (Region USA, Rev2.2) prints, in one row shared across all three USA models: "Safety and EMC Compliance UL1741; CSA C22.2 No.107.1-16; FCC Part15B; ICES-003 Class B; IEEE1547; UL1741SB;CA Rule 21 (UL1741-SA);SRD-V2.0; NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.11 DC Arc-Fault circuit Protection NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.12 Rapid Shutdown of PV systems on Buildings". This row records "FCC Part15B". US FCC Part 15 Subpart B, radio-frequency emissions. No certificate, report number or issuer record was read; this is the manufacturer's own printed claim only, not independently verified against the standard issuer's directory.
ICES-003 Class BProduct / system scope unresolvedClaimedListed when checked
The DS3 series datasheet (Region USA, Rev2.2) prints, in one row shared across all three USA models: "Safety and EMC Compliance UL1741; CSA C22.2 No.107.1-16; FCC Part15B; ICES-003 Class B; IEEE1547; UL1741SB;CA Rule 21 (UL1741-SA);SRD-V2.0; NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.11 DC Arc-Fault circuit Protection NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.12 Rapid Shutdown of PV systems on Buildings". This row records "ICES-003 Class B". Industry Canada ICES-003 Class B, radio-frequency emissions for Canada. No certificate, report number or issuer record was read; this is the manufacturer's own printed claim only, not independently verified against the standard issuer's directory.
IEEE1547Product / system scope unresolvedClaimedListed when checked
The DS3 series datasheet (Region USA, Rev2.2) prints, in one row shared across all three USA models: "Safety and EMC Compliance UL1741; CSA C22.2 No.107.1-16; FCC Part15B; ICES-003 Class B; IEEE1547; UL1741SB;CA Rule 21 (UL1741-SA);SRD-V2.0; NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.11 DC Arc-Fault circuit Protection NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.12 Rapid Shutdown of PV systems on Buildings". This row records "IEEE1547". IEEE 1547, Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces. No certificate, report number or issuer record was read; this is the manufacturer's own printed claim only, not independently verified against the standard issuer's directory.
UL1741SBProduct / system scope unresolvedClaimedListed when checked
The DS3 series datasheet (Region USA, Rev2.2) prints, in one row shared across all three USA models: "Safety and EMC Compliance UL1741; CSA C22.2 No.107.1-16; FCC Part15B; ICES-003 Class B; IEEE1547; UL1741SB;CA Rule 21 (UL1741-SA);SRD-V2.0; NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.11 DC Arc-Fault circuit Protection NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.12 Rapid Shutdown of PV systems on Buildings". This row records "UL1741SB". UL 1741 SB, the Supplement B grid-support utility-interactive inverter requirements. No certificate, report number or issuer record was read; this is the manufacturer's own printed claim only, not independently verified against the standard issuer's directory.
CA Rule 21 (UL1741-SA)Product / system scope unresolvedClaimedListed when checked
The DS3 series datasheet (Region USA, Rev2.2) prints, in one row shared across all three USA models: "Safety and EMC Compliance UL1741; CSA C22.2 No.107.1-16; FCC Part15B; ICES-003 Class B; IEEE1547; UL1741SB;CA Rule 21 (UL1741-SA);SRD-V2.0; NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.11 DC Arc-Fault circuit Protection NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.12 Rapid Shutdown of PV systems on Buildings". This row records "CA Rule 21 (UL1741-SA)". California Rule 21 smart inverter requirements, printed with UL1741-SA in parentheses. No certificate, report number or issuer record was read; this is the manufacturer's own printed claim only, not independently verified against the standard issuer's directory.
SRD-V2.0Product / system scope unresolvedClaimedListed when checked
The DS3 series datasheet (Region USA, Rev2.2) prints, in one row shared across all three USA models: "Safety and EMC Compliance UL1741; CSA C22.2 No.107.1-16; FCC Part15B; ICES-003 Class B; IEEE1547; UL1741SB;CA Rule 21 (UL1741-SA);SRD-V2.0; NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.11 DC Arc-Fault circuit Protection NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.12 Rapid Shutdown of PV systems on Buildings". This row records "SRD-V2.0". Printed as "SRD-V2.0" with no further description; recorded as printed, not expanded. No certificate, report number or issuer record was read; this is the manufacturer's own printed claim only, not independently verified against the standard issuer's directory.
NEC 690.11 DC Arc-Fault Circuit ProtectionProduct / system scope unresolvedClaimedListed when checked
The DS3 series datasheet (Region USA, Rev2.2) prints, in one row shared across all three USA models: "Safety and EMC Compliance UL1741; CSA C22.2 No.107.1-16; FCC Part15B; ICES-003 Class B; IEEE1547; UL1741SB;CA Rule 21 (UL1741-SA);SRD-V2.0; NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.11 DC Arc-Fault circuit Protection NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.12 Rapid Shutdown of PV systems on Buildings". This row records "NEC 690.11 DC Arc-Fault Circuit Protection". NEC 2014, 2017, 2020 and 2023 Section 690.11, DC arc-fault circuit protection for PV systems, printed as one combined entry across the four code editions. No certificate, report number or issuer record was read; this is the manufacturer's own printed claim only, not independently verified against the standard issuer's directory.
NEC 690.12 Rapid ShutdownProduct / system scope unresolvedClaimedListed when checked
The DS3 series datasheet (Region USA, Rev2.2) prints, in one row shared across all three USA models: "Safety and EMC Compliance UL1741; CSA C22.2 No.107.1-16; FCC Part15B; ICES-003 Class B; IEEE1547; UL1741SB;CA Rule 21 (UL1741-SA);SRD-V2.0; NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.11 DC Arc-Fault circuit Protection NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.12 Rapid Shutdown of PV systems on Buildings". This row records "NEC 690.12 Rapid Shutdown". NEC 2014, 2017, 2020 and 2023 Section 690.12, rapid shutdown of PV systems on buildings, printed as one combined entry across the four code editions. No certificate, report number or issuer record was read; this is the manufacturer's own printed claim only, not independently verified against the standard issuer's directory.
UL1741Manufacturer claim · unresolved document setClaimedListed when checked
The DS3 series datasheet (Region USA, Rev2.2) prints, in one row shared across all three USA models: "Safety and EMC Compliance UL1741; CSA C22.2 No.107.1-16; FCC Part15B; ICES-003 Class B; IEEE1547; UL1741SB;CA Rule 21 (UL1741-SA);SRD-V2.0; NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.11 DC Arc-Fault circuit Protection NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.12 Rapid Shutdown of PV systems on Buildings". This row records "UL1741". UL 1741, Standard for Inverters, Converters, Controllers and Interconnection System Equipment for Use With Distributed Energy Resources. Printed without a specific sub-standard edition or scope. No certificate, report number or issuer record was read; this is the manufacturer's own printed claim only, not independently verified against the standard issuer's directory.
CSA C22.2 No.107.1-16Manufacturer claim · unresolved document setClaimedListed when checked
The DS3 series datasheet (Region USA, Rev2.2) prints, in one row shared across all three USA models: "Safety and EMC Compliance UL1741; CSA C22.2 No.107.1-16; FCC Part15B; ICES-003 Class B; IEEE1547; UL1741SB;CA Rule 21 (UL1741-SA);SRD-V2.0; NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.11 DC Arc-Fault circuit Protection NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.12 Rapid Shutdown of PV systems on Buildings". This row records "CSA C22.2 No.107.1-16". CSA Group standard C22.2 No.107.1-16, Power conversion equipment, the Canadian counterpart cited alongside the UL entries. No certificate, report number or issuer record was read; this is the manufacturer's own printed claim only, not independently verified against the standard issuer's directory.
FCC Part15BManufacturer claim · unresolved document setClaimedListed when checked
The DS3 series datasheet (Region USA, Rev2.2) prints, in one row shared across all three USA models: "Safety and EMC Compliance UL1741; CSA C22.2 No.107.1-16; FCC Part15B; ICES-003 Class B; IEEE1547; UL1741SB;CA Rule 21 (UL1741-SA);SRD-V2.0; NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.11 DC Arc-Fault circuit Protection NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.12 Rapid Shutdown of PV systems on Buildings". This row records "FCC Part15B". US FCC Part 15 Subpart B, radio-frequency emissions. No certificate, report number or issuer record was read; this is the manufacturer's own printed claim only, not independently verified against the standard issuer's directory.
ICES-003 Class BManufacturer claim · unresolved document setClaimedListed when checked
The DS3 series datasheet (Region USA, Rev2.2) prints, in one row shared across all three USA models: "Safety and EMC Compliance UL1741; CSA C22.2 No.107.1-16; FCC Part15B; ICES-003 Class B; IEEE1547; UL1741SB;CA Rule 21 (UL1741-SA);SRD-V2.0; NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.11 DC Arc-Fault circuit Protection NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.12 Rapid Shutdown of PV systems on Buildings". This row records "ICES-003 Class B". Industry Canada ICES-003 Class B, radio-frequency emissions for Canada. No certificate, report number or issuer record was read; this is the manufacturer's own printed claim only, not independently verified against the standard issuer's directory.
IEEE1547Manufacturer claim · unresolved document setClaimedListed when checked
The DS3 series datasheet (Region USA, Rev2.2) prints, in one row shared across all three USA models: "Safety and EMC Compliance UL1741; CSA C22.2 No.107.1-16; FCC Part15B; ICES-003 Class B; IEEE1547; UL1741SB;CA Rule 21 (UL1741-SA);SRD-V2.0; NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.11 DC Arc-Fault circuit Protection NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.12 Rapid Shutdown of PV systems on Buildings". This row records "IEEE1547". IEEE 1547, Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces. No certificate, report number or issuer record was read; this is the manufacturer's own printed claim only, not independently verified against the standard issuer's directory.
UL1741SBManufacturer claim · unresolved document setClaimedListed when checked
The DS3 series datasheet (Region USA, Rev2.2) prints, in one row shared across all three USA models: "Safety and EMC Compliance UL1741; CSA C22.2 No.107.1-16; FCC Part15B; ICES-003 Class B; IEEE1547; UL1741SB;CA Rule 21 (UL1741-SA);SRD-V2.0; NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.11 DC Arc-Fault circuit Protection NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.12 Rapid Shutdown of PV systems on Buildings". This row records "UL1741SB". UL 1741 SB, the Supplement B grid-support utility-interactive inverter requirements. No certificate, report number or issuer record was read; this is the manufacturer's own printed claim only, not independently verified against the standard issuer's directory.
CA Rule 21 (UL1741-SA)Manufacturer claim · unresolved document setClaimedListed when checked
The DS3 series datasheet (Region USA, Rev2.2) prints, in one row shared across all three USA models: "Safety and EMC Compliance UL1741; CSA C22.2 No.107.1-16; FCC Part15B; ICES-003 Class B; IEEE1547; UL1741SB;CA Rule 21 (UL1741-SA);SRD-V2.0; NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.11 DC Arc-Fault circuit Protection NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.12 Rapid Shutdown of PV systems on Buildings". This row records "CA Rule 21 (UL1741-SA)". California Rule 21 smart inverter requirements, printed with UL1741-SA in parentheses. No certificate, report number or issuer record was read; this is the manufacturer's own printed claim only, not independently verified against the standard issuer's directory.
SRD-V2.0Manufacturer claim · unresolved document setClaimedListed when checked
The DS3 series datasheet (Region USA, Rev2.2) prints, in one row shared across all three USA models: "Safety and EMC Compliance UL1741; CSA C22.2 No.107.1-16; FCC Part15B; ICES-003 Class B; IEEE1547; UL1741SB;CA Rule 21 (UL1741-SA);SRD-V2.0; NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.11 DC Arc-Fault circuit Protection NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.12 Rapid Shutdown of PV systems on Buildings". This row records "SRD-V2.0". Printed as "SRD-V2.0" with no further description; recorded as printed, not expanded. No certificate, report number or issuer record was read; this is the manufacturer's own printed claim only, not independently verified against the standard issuer's directory.
NEC 690.11 DC Arc-Fault Circuit ProtectionManufacturer claim · unresolved document setClaimedListed when checked
The DS3 series datasheet (Region USA, Rev2.2) prints, in one row shared across all three USA models: "Safety and EMC Compliance UL1741; CSA C22.2 No.107.1-16; FCC Part15B; ICES-003 Class B; IEEE1547; UL1741SB;CA Rule 21 (UL1741-SA);SRD-V2.0; NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.11 DC Arc-Fault circuit Protection NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.12 Rapid Shutdown of PV systems on Buildings". This row records "NEC 690.11 DC Arc-Fault Circuit Protection". NEC 2014, 2017, 2020 and 2023 Section 690.11, DC arc-fault circuit protection for PV systems, printed as one combined entry across the four code editions. No certificate, report number or issuer record was read; this is the manufacturer's own printed claim only, not independently verified against the standard issuer's directory.
NEC 690.12 Rapid ShutdownManufacturer claim · unresolved document setClaimedListed when checked
The DS3 series datasheet (Region USA, Rev2.2) prints, in one row shared across all three USA models: "Safety and EMC Compliance UL1741; CSA C22.2 No.107.1-16; FCC Part15B; ICES-003 Class B; IEEE1547; UL1741SB;CA Rule 21 (UL1741-SA);SRD-V2.0; NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.11 DC Arc-Fault circuit Protection NEC2014 & NEC2017 & NEC2020 & NEC2023 Section 690.12 Rapid Shutdown of PV systems on Buildings". This row records "NEC 690.12 Rapid Shutdown". NEC 2014, 2017, 2020 and 2023 Section 690.12, rapid shutdown of PV systems on buildings, printed as one combined entry across the four code editions. No certificate, report number or issuer record was read; this is the manufacturer's own printed claim only, not independently verified against the standard issuer's directory.