Charged Reviews
Quick reference
Sungrow PowerTitan 2.0 ST5015UX-2H-US
Model: ST5015UX-2H-US · SKU: ST5015UX-2H-US
Prepared Nov 12, 2026
Common specifications
| Container type | AC blockSource [1] |
|---|---|
| Rated capacity | 5,015 kWhSource [1] |
| Usable capacity | Not documented |
| Battery voltage | Not documented |
| Continuous output | Not documented |
| Apparent power | 2,520,000 VACalculatedSource [1] |
| Chemistry | LFPSource [1] |
| Cycle life | Not documented |
| Round-trip efficiency | Not documented |
| Cabinets | Not documented |
| AC voltage | 690 VSource [1] |
| AC frequency | 60 HzSource [1] |
| Cooling | Intelligent Liquid CoolingSource [1] |
| Fire suppression | Default: NFPA 68 compliance vent panel, smoke and heat, detectors, Mini FACP. Optional: Sprinkler, sound beacon, NFPA 69, compliance ventilation system, Flammable gas detectorSource [1] |
| Enclosure | Type 3SSource [1] |
| Safety listing | UL 9540A, UL 1973, UL 1741SB, UL 9540Source [1] |
| Communications | EthernetSource [1] |
| Operating temperature | |
| Weight | |
| Dimensions | |
| Enclosure volume | 42,772.19 L** Calculated from recorded external dimensions |
| Warranty term | Not documented |
All recorded specifications
| AC frequency | 60 HzDocumented claim ConditionsPrinted as "60 Hz" (Nominal frequency); isolation method "Transformerless". Location: ST5015UX-2H/4H-US Datasheet (Version 5), page 2, AC side, Nominal frequency Printed as "60 Hz" (Nominal frequency); isolation method "Transformerless". Location: ST5015UX-2H/4H-US Datasheet (Version 5), page 2, AC side, Nominal frequency |
|---|---|
| AC voltage | 690 VDocumented claim ConditionsPrinted as "690 V" (Nominal AC voltage), with an AC voltage range of "607 V ~ 759 V". Location: ST5015UX-2H/4H-US Datasheet (Version 5), page 2, AC side, Nominal AC voltage Printed as "690 V" (Nominal AC voltage), with an AC voltage range of "607 V ~ 759 V". Location: ST5015UX-2H/4H-US Datasheet (Version 5), page 2, AC side, Nominal AC voltage |
| Apparent power | 2,520,000 VACalculated210 kVA * 12 = 210 kVA x 12 = 2520 kVA x 1000 VA/kVA ConditionsPrinted as "210 kVA * 12" (Nominal AC power) for ST5015UX-2H-US: 12 power units of 210 kVA, 2520 kVA in all, recorded in VA. Sungrow prints no kW figure, so the continuous AC output in kW stays unknown. Location: ST5015UX-2H/4H-US Datasheet (Version 5), page 2, AC side, Nominal AC power Printed as "210 kVA * 12" (Nominal AC power) for ST5015UX-2H-US: 12 power units of 210 kVA, 2520 kVA in all, recorded in VA. Sungrow prints no kW figure, so the continuous AC output in kW stays unknown. Location: ST5015UX-2H/4H-US Datasheet (Version 5), page 2, AC side, Nominal AC power |
| Chemistry | LFPDocumented claim ConditionsPrinted as "LFP" (Cell type), with "3.2 V / 314 Ah" cells in a "416S12P" battery configuration. Location: ST5015UX-2H/4H-US Datasheet (Version 5), page 2, DC side, Cell type Printed as "LFP" (Cell type), with "3.2 V / 314 Ah" cells in a "416S12P" battery configuration. Location: ST5015UX-2H/4H-US Datasheet (Version 5), page 2, DC side, Cell type |
| Communications | EthernetDocumented claim ConditionsPrinted as "Ethernet" (Communication). Location: ST5015UX-2H/4H-US Datasheet (Version 5), page 2, System parameter, Communication Printed as "Ethernet" (Communication). Location: ST5015UX-2H/4H-US Datasheet (Version 5), page 2, System parameter, Communication |
| Container type | AC blockDocumented claim ConditionsRecorded as "AC block": Sungrow titles it "PowerTitan 2.0 Liquid Cooled Battery Energy Storage System Container" and the datasheet prints an AC side for the container itself (Nominal AC power, 690 V nominal AC voltage, transformerless); the product page prints "System is delivered pre assembled and complete". Location: ST5015UX-2H/4H-US Datasheet (Version 5), page 2, title and AC side Recorded as "AC block": Sungrow titles it "PowerTitan 2.0 Liquid Cooled Battery Energy Storage System Container" and the datasheet prints an AC side for the container itself (Nominal AC power, 690 V nominal AC voltage, transformerless); the product page prints "System is delivered pre assembled and complete". Location: ST5015UX-2H/4H-US Datasheet (Version 5), page 2, title and AC side |
| Cooling | Intelligent Liquid CoolingDocumented claim ConditionsPrinted as "Intelligent Liquid Cooling". Location: ST5015UX-2H/4H-US Datasheet (Version 5), page 2, System parameter, Temperature control method Printed as "Intelligent Liquid Cooling". Location: ST5015UX-2H/4H-US Datasheet (Version 5), page 2, System parameter, Temperature control method |
| Dimensions | 2,438 D × 6,058 W × 2,896 H mm95.98 D × 238.5 W × 114 H in convertedDocumented claim ConditionsPrinted as "6058 mm * 2896 mm * 2438 mm" (W * H * D) and "238.5'' * 114.0'' * 96.0"", one value for both models. Location: ST5015UX-2H/4H-US Datasheet (Version 5), page 2, System parameter, Dimension (W * H * D) Printed as "6058 mm * 2896 mm * 2438 mm" (W * H * D) and "238.5'' * 114.0'' * 96.0"", one value for both models. Location: ST5015UX-2H/4H-US Datasheet (Version 5), page 2, System parameter, Dimension (W * H * D) |
| Enclosure | Type 3SDocumented claim ConditionsPrinted as "Type 3S" (Degree of protection); anti-corrosion degree "C4". Location: ST5015UX-2H/4H-US Datasheet (Version 5), page 2, System parameter, Degree of protection Printed as "Type 3S" (Degree of protection); anti-corrosion degree "C4". Location: ST5015UX-2H/4H-US Datasheet (Version 5), page 2, System parameter, Degree of protection |
| Fire suppression | Default: NFPA 68 compliance vent panel, smoke and heat, detectors, Mini FACP. Optional: Sprinkler, sound beacon, NFPA 69, compliance ventilation system, Flammable gas detectorDocumented claim ConditionsAs printed under "Fire suppression system", default and optional equipment. Location: ST5015UX-2H/4H-US Datasheet (Version 5), page 2, System parameter, Fire suppression system As printed under "Fire suppression system", default and optional equipment. Location: ST5015UX-2H/4H-US Datasheet (Version 5), page 2, System parameter, Fire suppression system |
| Operating temperature | -30 to 50 °C-22 to 122 °F convertedDocumented claim ConditionsPrinted as "﹣30 ℃ ~ 50 ℃ ( > 45 ℃ Derating )" and "-22 °F ~ 122 °F ( > 113 °F Derating )"; derating above 45 °C. Location: ST5015UX-2H/4H-US Datasheet (Version 5), page 2, System parameter, Operation temperature range Printed as "﹣30 ℃ ~ 50 ℃ ( > 45 ℃ Derating )" and "-22 °F ~ 122 °F ( > 113 °F Derating )"; derating above 45 °C. Location: ST5015UX-2H/4H-US Datasheet (Version 5), page 2, System parameter, Operation temperature range |
| Rated capacity | 5,015 kWhDocumented claim ConditionsPrinted as "5015 kWh" (Nominal capacity), one value for both models; the product page prints "5015 kWh Nominal Capacity". Location: ST5015UX-2H/4H-US Datasheet (Version 5), page 2, DC side, Nominal capacity Printed as "5015 kWh" (Nominal capacity), one value for both models; the product page prints "5015 kWh Nominal Capacity". Location: ST5015UX-2H/4H-US Datasheet (Version 5), page 2, DC side, Nominal capacity |
| Safety listing | UL 9540A, UL 1973, UL 1741SB, UL 9540Documented claim ConditionsThe UL entries of the Standard row, which prints "UL 9540A, NFPA 855, NFPA 68, NFPA 69 ( optional ) IEEE 1547, UL 1973, UL 1741SB, UL 9540". UL 9540A is a test method, not a listing. Recorded as Sungrow's claim; no certificate number is printed. Location: ST5015UX-2H/4H-US Datasheet (Version 5), page 2, System parameter, Standard The UL entries of the Standard row, which prints "UL 9540A, NFPA 855, NFPA 68, NFPA 69 ( optional ) IEEE 1547, UL 1973, UL 1741SB, UL 9540". UL 9540A is a test method, not a listing. Recorded as Sungrow's claim; no certificate number is printed. Location: ST5015UX-2H/4H-US Datasheet (Version 5), page 2, System parameter, Standard |
| Weight | 42,500 kg93,700 lb convertedDocumented claim ConditionsPrinted as "42500 kg / 93696.5 lbs" for ST5015UX-2H-US. In the datasheet's two-column table the ST5015UX-2H-US column prints "210 kVA * 12" (Nominal AC power), "352 A * 3 Phase * 6" (Termination (LV)) and "42500 kg / 93696.5 lbs" (Weight); the column order was checked on the page's text positions. Location: ST5015UX-2H/4H-US Datasheet (Version 5), page 2, System parameter, Weight Printed as "42500 kg / 93696.5 lbs" for ST5015UX-2H-US. In the datasheet's two-column table the ST5015UX-2H-US column prints "210 kVA * 12" (Nominal AC power), "352 A * 3 Phase * 6" (Termination (LV)) and "42500 kg / 93696.5 lbs" (Weight); the column order was checked on the page's text positions. Location: ST5015UX-2H/4H-US Datasheet (Version 5), page 2, System parameter, Weight |
Warranty
Certificate records
No records documented.
Sources and revisions
- ST5015UX-2H/4H-US Datasheet (PowerTitan 2.0, Version 5)Official datasheet · Revision Version 5 · Checked https://info-support.sungrowpower.com/datasheet-materials/1a38db5b-a599-43d3-ac10-dfe06dee5d2a.pdf
- PowerTitan 2.0 - ST5015UX-2H-US ST5015UX-4H-US (Sungrow USA product page, October 13, 2026 capture)Official product page · Checked https://www.sungrowpower.com/us/en/products/energy-storage-systems/powertitan-20-st5015ux-2h-us-st5015ux-4h-us