Charged Reviews
Quick reference
MidNite Solar MNLSOB-R1-600 Little SOB 600V rapid shutdown receiver
Model: MNLSOB-R1-600 · SKU: Not documented
Prepared Nov 12, 2026
Common specifications
| Device type | 600V ReceiverSource [1] |
|---|---|
| Rapid shutdown compliance | Not documented |
| Maximum input power | Not documented |
| Maximum input voltage | 600 VSource [1] |
| Maximum input current | 12 ASource [1] |
| Output voltage | Not documented |
| Maximum output current | Not documented |
| Communications | Encoded 484.84 kHz tone inductively coupled into the string PV+ lineSource [1] |
| Efficiency | Not documented |
| Operating temperature | Not documented |
| Enclosure | Not documented |
| Safety listing | Not documented |
| Weight | Not documented |
| Dimensions | Not documented |
| Enclosure volume | Not documented |
| Warranty term | Not documented |
All recorded specifications
| Communications | Encoded 484.84 kHz tone inductively coupled into the string PV+ lineDocumented claim ConditionsPrinted as "The transmitter generates a signal which is inductively coupled into the string PV+ line. The signal consists of an encoded 484.84 kHz tone." The receiver connects the string when it detects a valid signal and shuts off 5 seconds after the signal goes away (page 1); page 7 says the receiver opens the circuit within a few seconds of the signal being interrupted. Location: Page 1, System Function Printed as "The transmitter generates a signal which is inductively coupled into the string PV+ line. The signal consists of an encoded 484.84 kHz tone." The receiver connects the string when it detects a valid signal and shuts off 5 seconds after the signal goes away (page 1); page 7 says the receiver opens the circuit within a few seconds of the signal being interrupted. Location: Page 1, System Function |
|---|---|
| Device type | 600V ReceiverDocumented claim ConditionsPage 1 captions the image "600V Receiver"; page 6 prints "600 Volt receiver shown. Applies to all receivers 600 V and 1000 V."; page 5 Ratings name MNLSOB-R1-600 with 600VDC. Part of the Little SOB transmitter and receiver rapid shutdown system. Location: Page 1, product image captions; page 5, Ratings Page 1 captions the image "600V Receiver"; page 6 prints "600 Volt receiver shown. Applies to all receivers 600 V and 1000 V."; page 5 Ratings name MNLSOB-R1-600 with 600VDC. Part of the Little SOB transmitter and receiver rapid shutdown system. Location: Page 1, product image captions; page 5, Ratings |
| Maximum input current | 12 ADocumented claim ConditionsPrinted as "12 AMPS MAX" for MNLSOB-R1-600 in the page 5 Ratings line "MNLSOB-R1-600 600VDC 12 AMPS MAX - 80 VDC Panel Voltage". No temperature or other condition is printed with it. Location: Page 5, Ratings Printed as "12 AMPS MAX" for MNLSOB-R1-600 in the page 5 Ratings line "MNLSOB-R1-600 600VDC 12 AMPS MAX - 80 VDC Panel Voltage". No temperature or other condition is printed with it. Location: Page 5, Ratings |
| Maximum input voltage | 600 VDocumented claim ConditionsPrinted as "600VDC" for MNLSOB-R1-600 in the page 5 Ratings: total string voltage. Page 1 prints that any module the receiver is attached to "must not exceed 80V open circuit and (depending on receiver model) 600 or 1000 volts total string voltage"; the 80 VDC panel voltage limit is per module, not this string figure. Pages 7 and 8 print "600 Volts Maximum string voltage" and page 9 "MNLSOB-R1-600 600 Volts Maximum string voltage". Location: Page 5, Ratings; page 1, MNLSOB System Overview Printed as "600VDC" for MNLSOB-R1-600 in the page 5 Ratings: total string voltage. Page 1 prints that any module the receiver is attached to "must not exceed 80V open circuit and (depending on receiver model) 600 or 1000 volts total string voltage"; the 80 VDC panel voltage limit is per module, not this string figure. Pages 7 and 8 print "600 Volts Maximum string voltage" and page 9 "MNLSOB-R1-600 600 Volts Maximum string voltage". Location: Page 5, Ratings; page 1, MNLSOB System Overview |
Warranty
Certificate records
No records documented.
Sources and revisions
- MidNite Solar Little SOB (Shut Off Box) Installation and Use Guide (10-349-1 REV N)Official installation manual · Revision 10-349-1 REV N · Checked https://www.midnitesolar.com/pdfs/10-349-1_REV_N_Little_SOB_Instructions.pdf