Continental Control Systems WattNode Wide-Range Modbus meter (WND-WR-MB)

Model: WND-WR-MB · SKU: WND-WR-MB

Prepared Oct 24, 2026

Common specifications

Device typeNot documented
Max switched load (A)Not documented
Max switched load (W)Not documented
Measurement channels
Three current transformer inputs (CT1, CT2, CT3); single-phase or three-phase, wye or delta servicesSource [2]
Current sensors
0.333 Vac current transformers or milliamp output CTs (sold separately)Source [2]
Current ratingNot documented
Voltage range
100 to 600 VSource [1]
Accuracy
0.5 %Source [2]
Communications
Modbus RTU over RS-485Source [2]
DisplayNot documented
Power input
Line powered, 100 to 600 Vac, line-to-neutral or line-to-lineSource [1, 2]
Mounting
Indoor; outdoors or wet locations only inside a rated electrical enclosureSource [1]
Safety listing
UL Listed (U.S. and Canada), file E359088: UL 61010-1, 3rd Edition; UL 2808; CAN/CSA-C22.2 No. 61010-1-12, 3rd EditionSource [1]
Weight
0.23 kg0.51 lb convertedCalculatedSource [1]
Dimensions
85 W × 38 H × 153 L mm3.3 W × 1.5 H × 6.02 L in convertedNeeds confirmationSource See note below[1]
Enclosure volume0.49 L** Calculated from recorded external dimensions
Warranty term
5 yearsSource [1]

All recorded specifications

Accuracy
0.5 %Documented claim
Conditions

Printed as "EnergySum, Energy1, 2, 3(1) (active energy) elapsed time(2) >= 30 s ±0.2 ±0.5 %" in Continental Control Systems' WND-WR-MB datasheet (WND-WR-MB-DS1, 2020-02-12), captured October 3, 2026. The value is the maximum (typical ±0.2 %) for active energy at power factor 1.0, 1 to 100 % of rated current, excluding current transformer errors. The datasheet also prints that all models meet ANSI C12.20 class 0.5.

Location: Datasheet 2.1 Accuracy table, active energy row

Printed as "EnergySum, Energy1, 2, 3(1) (active energy) elapsed time(2) >= 30 s ±0.2 ±0.5 %" in Continental Control Systems' WND-WR-MB datasheet (WND-WR-MB-DS1, 2020-02-12), captured October 3, 2026. The value is the maximum (typical ±0.2 %) for active energy at power factor 1.0, 1 to 100 % of rated current, excluding current transformer errors. The datasheet also prints that all models meet ANSI C12.20 class 0.5.

Location: Datasheet 2.1 Accuracy table, active energy row

[2]
Communications
Modbus RTU over RS-485Documented claim
Conditions

Printed as "It communicates using Modbus® RTU over RS-485." in Continental Control Systems' WND-WR-MB datasheet (WND-WR-MB-DS1, 2020-02-12), captured October 3, 2026. Baud rates printed: "1200, 2400, 4800, 9600, 19200, 38400, 57600, 76800, and 115200".

Location: Datasheet page 1, introduction

Printed as "It communicates using Modbus® RTU over RS-485." in Continental Control Systems' WND-WR-MB datasheet (WND-WR-MB-DS1, 2020-02-12), captured October 3, 2026. Baud rates printed: "1200, 2400, 4800, 9600, 19200, 38400, 57600, 76800, and 115200".

Location: Datasheet page 1, introduction

[2]
Current sensors
0.333 Vac current transformers or milliamp output CTs (sold separately)Documented claim
Conditions

Printed as "Works with any 0.333 Vac current transformers and milliamp output CTs" in Continental Control Systems' WND-WR-MB datasheet (WND-WR-MB-DS1, 2020-02-12), captured October 3, 2026. Milliamp output CTs need the meter's MA or R= burden resistor option, as the datasheet's current transformer options describe.

Location: Datasheet page 1, Features

Printed as "Works with any 0.333 Vac current transformers and milliamp output CTs" in Continental Control Systems' WND-WR-MB datasheet (WND-WR-MB-DS1, 2020-02-12), captured October 3, 2026. Milliamp output CTs need the meter's MA or R= burden resistor option, as the datasheet's current transformer options describe.

Location: Datasheet page 1, Features

[2]
Dimensions
85 W × 38 H × 153 L mm3.3 W × 1.5 H × 6.02 L in convertedNeeds confirmationThe installation guide (WND-WR-MB-Inst-1.08) prints 153 mm × 85 mm × 38 mm and the datasheet (WND-WR-MB-DS1) prints 153 mm × 85.1 mm × 38.0 mm for the same 6.02 × 3.35 × 1.50 in. size; the installation guide's figure is shown.
Conditions

Printed as "Size: 6.02 in. × 3.35 in. × 1.50 in. (153 mm × 85 mm × 38 mm)" in the Specifications chapter of Continental Control Systems' WND-WR-MB installation guide (WND-WR-MB-Inst-1.08), captured October 3, 2026. The guide names no axes; the three figures are recorded in printed order.

Location: Installation guide 5.6 Mechanical

Printed as "Size: 6.02 in. × 3.35 in. × 1.50 in. (153 mm × 85 mm × 38 mm)" in the Specifications chapter of Continental Control Systems' WND-WR-MB installation guide (WND-WR-MB-Inst-1.08), captured October 3, 2026. The guide names no axes; the three figures are recorded in printed order.

Location: Installation guide 5.6 Mechanical

[1]
Enclosure
IP40; outdoor use only inside a NEMA 3R or 4 (IP 66) electrical enclosureDocumented claim
Conditions

Printed as "Degree of Protection: IP40 (>1 mm solids, no protection from liquids)" in Continental Control Systems' WND-WR-MB datasheet (WND-WR-MB-DS1, 2020-02-12), captured October 3, 2026. The installation guide prints "Suitable for use outdoors or in wet locations if mounted inside an electrical enclosure (Hammond Mfg., Type EJ Series or equivalent) rated NEMA 3R or 4 (IP 66)".

Location: Datasheet 2.6 Environmental

Printed as "Degree of Protection: IP40 (>1 mm solids, no protection from liquids)" in Continental Control Systems' WND-WR-MB datasheet (WND-WR-MB-DS1, 2020-02-12), captured October 3, 2026. The installation guide prints "Suitable for use outdoors or in wet locations if mounted inside an electrical enclosure (Hammond Mfg., Type EJ Series or equivalent) rated NEMA 3R or 4 (IP 66)".

Location: Datasheet 2.6 Environmental

[1, 2]
Measurement channels
Three current transformer inputs (CT1, CT2, CT3); single-phase or three-phase, wye or delta servicesDocumented claim
Conditions

Printed as "One model can measure 100 to 600 Vac, single-phase or three-phase, wye or delta services" in Continental Control Systems' WND-WR-MB datasheet (WND-WR-MB-DS1, 2020-02-12), captured October 3, 2026. The connection type table maps "CT1 Phase A CT2 Phase B CT3 Phase C".

Location: Datasheet page 1 Features and connection type table

Printed as "One model can measure 100 to 600 Vac, single-phase or three-phase, wye or delta services" in Continental Control Systems' WND-WR-MB datasheet (WND-WR-MB-DS1, 2020-02-12), captured October 3, 2026. The connection type table maps "CT1 Phase A CT2 Phase B CT3 Phase C".

Location: Datasheet page 1 Features and connection type table

[2]
Mounting
Indoor; outdoors or wet locations only inside a rated electrical enclosureDocumented claim
Conditions

Printed as "Indoor Use: Suitable for indoor use. Outdoor Use/Wet Locations: Suitable for use outdoors or in wet locations if mounted inside an electrical enclosure" in the Specifications chapter of Continental Control Systems' WND-WR-MB installation guide (WND-WR-MB-Inst-1.08), captured October 3, 2026.

Location: Installation guide 5.5 Environmental

Printed as "Indoor Use: Suitable for indoor use. Outdoor Use/Wet Locations: Suitable for use outdoors or in wet locations if mounted inside an electrical enclosure" in the Specifications chapter of Continental Control Systems' WND-WR-MB installation guide (WND-WR-MB-Inst-1.08), captured October 3, 2026.

Location: Installation guide 5.5 Environmental

[1]
Operating temperature
-40 to 80 °C-40 to 176 °F convertedDocumented claim
Conditions

Printed as "Operating Temperature: -40°C to 80°C (-40°F to 176°F)" in the Specifications chapter of Continental Control Systems' WND-WR-MB installation guide (WND-WR-MB-Inst-1.08), captured October 3, 2026.

Location: Installation guide 5.5 Environmental

Printed as "Operating Temperature: -40°C to 80°C (-40°F to 176°F)" in the Specifications chapter of Continental Control Systems' WND-WR-MB installation guide (WND-WR-MB-Inst-1.08), captured October 3, 2026.

Location: Installation guide 5.5 Environmental

[1]
Power input
Line powered, 100 to 600 Vac, line-to-neutral or line-to-lineDocumented claim
Conditions

Printed as "Power Supply Input Terminals: VA and VB (the meter supply can operate line-to-neutral or line-to- line)" in the Specifications chapter of Continental Control Systems' WND-WR-MB installation guide (WND-WR-MB-Inst-1.08), captured October 3, 2026. The datasheet prints "Line powered from 100 to 600 Vac". The guide prints "Power Supply Watts: typical 1.0 W, maximum 2.5 W".

Location: Installation guide 5.2 Electrical

Printed as "Power Supply Input Terminals: VA and VB (the meter supply can operate line-to-neutral or line-to- line)" in the Specifications chapter of Continental Control Systems' WND-WR-MB installation guide (WND-WR-MB-Inst-1.08), captured October 3, 2026. The datasheet prints "Line powered from 100 to 600 Vac". The guide prints "Power Supply Watts: typical 1.0 W, maximum 2.5 W".

Location: Installation guide 5.2 Electrical

[1, 2]
Safety listing
UL Listed (U.S. and Canada), file E359088: UL 61010-1, 3rd Edition; UL 2808; CAN/CSA-C22.2 No. 61010-1-12, 3rd EditionDocumented claim
Conditions

Printed as "Safety: UL Listed: U.S. and Canada, E359088: UL 61010-1, 3rd Edition; UL 2808; CAN/CSA-C22.2 No. 61010-1-12, 3rd Edition" in the Specifications chapter of Continental Control Systems' WND-WR-MB installation guide (WND-WR-MB-Inst-1.08), captured October 3, 2026.

Location: Installation guide 5.4 Regulatory

Printed as "Safety: UL Listed: U.S. and Canada, E359088: UL 61010-1, 3rd Edition; UL 2808; CAN/CSA-C22.2 No. 61010-1-12, 3rd Edition" in the Specifications chapter of Continental Control Systems' WND-WR-MB installation guide (WND-WR-MB-Inst-1.08), captured October 3, 2026.

Location: Installation guide 5.4 Regulatory

[1]
Voltage range
100 to 600 VDocumented claim
Conditions

Printed as "Power Supply Nominal Operating Voltage: 100 to 600 Vac" in the Specifications chapter of Continental Control Systems' WND-WR-MB installation guide (WND-WR-MB-Inst-1.08), captured October 3, 2026. The same section prints "Power Supply Voltage Range: ±15% (85 to 690 Vac)" and "Nominal Line-to-Line Vac: 120 to 600 Vac".

Location: Installation guide 5.2 Electrical

Printed as "Power Supply Nominal Operating Voltage: 100 to 600 Vac" in the Specifications chapter of Continental Control Systems' WND-WR-MB installation guide (WND-WR-MB-Inst-1.08), captured October 3, 2026. The same section prints "Power Supply Voltage Range: ±15% (85 to 690 Vac)" and "Nominal Line-to-Line Vac: 120 to 600 Vac".

Location: Installation guide 5.2 Electrical

[1]
Weight
0.23 kg0.51 lb convertedCalculated233 g / 1000 g/kg = 0.233 kg
Conditions

Printed as "Weight: 233 g (8.2 oz)" in the Specifications chapter of Continental Control Systems' WND-WR-MB installation guide (WND-WR-MB-Inst-1.08), captured October 3, 2026. The datasheet prints the same weight.

Location: Installation guide 5.6 Mechanical

Printed as "Weight: 233 g (8.2 oz)" in the Specifications chapter of Continental Control Systems' WND-WR-MB installation guide (WND-WR-MB-Inst-1.08), captured October 3, 2026. The datasheet prints the same weight.

Location: Installation guide 5.6 Mechanical

[1]

Warranty

Warranty term
5 yearsDocumented claim
Conditions

Printed as "All products sold by Continental Control Systems, LLC (CCS) are guaranteed against defects in material and workmanship for a period of five years from the original date of shipment." in the Specifications chapter of Continental Control Systems' WND-WR-MB installation guide (WND-WR-MB-Inst-1.08), captured October 3, 2026.

Location: Installation guide 5.8 Warranty

Printed as "All products sold by Continental Control Systems, LLC (CCS) are guaranteed against defects in material and workmanship for a period of five years from the original date of shipment." in the Specifications chapter of Continental Control Systems' WND-WR-MB installation guide (WND-WR-MB-Inst-1.08), captured October 3, 2026.

Location: Installation guide 5.8 Warranty

[1]

Certificate records

No records documented.

Sources and revisions

  1. WattNode Wide-Range Modbus Electric Power Meter, Installation Guide, model WND-WR-MB, WND-WR-MB-Inst-1.08 (ctlsys.com, October 3, 2026 capture)Official instruction manual · Checked Oct 3, 2026https://ctlsys.com/wp-content/uploads/2023/07/WND-WR-MB-WattNode-Install-Guide.pdf
  2. WND-WR-MB WattNode Wide-Range Modbus Meter datasheet, Doc ID WND-WR-MB-DS1, 2020-02-12 (ctlsys.com, October 3, 2026 capture)Official datasheet · Checked Oct 3, 2026https://ctlsys.com/wp-content/uploads/2018/12/WND-WR-MB-Meter-Datasheet.pdf