Quick reference

APsmart RSD-S-PLC-B (20A) Rapid Shutdown Device (435101)

Model: RSD-S-PLC-B (20A) · SKU: 435101

Prepared Nov 12, 2026

Common specifications

Device type
Module-level rapid shutdown device, kept connected by the heartbeat signal of an APsmart Transmitter-PLC (PLC)Source [1]
Rapid shutdown compliance
NEC 2017, 2020 and 2023 (690.12); SunSpecSource [1]
Maximum input powerNot documented
Maximum input voltage
80 VSource [1]
Maximum input current
20 ASource [1]
Output voltageNot documented
Maximum output currentNot documented
Communications
PLCSource [1]
EfficiencyNot documented
Operating temperature
-40 to 85 °C-40 to 185 °F convertedSource [1]
Enclosure
NEMA Type 6P/IP68Source [1]
Safety listingNot documented
WeightNot documented
Dimensions
140 D × 32 D × 18 D mm5.51 D × 1.3 D × 0.71 D in convertedSource [1]
Enclosure volume0.08 L** Calculated from recorded external dimensions
Warranty termNot documented

All recorded specifications

Certifications (as printed)
NEC 2017, 2020&2023 (690.12); UL1741; CSA C22.2 No. 330-17; IEC/EN62109-1; 2PFG2305; FCC Part15; ICES-003; IEC/EN61000-6-1/-2/-3/-4Documented claim
Conditions

The safety and EMC compliance rows as printed for the RSD-S-PLC. Manufacturer claims; no issuer directory was checked.

Location: PDF page 2, Technical Data (Model RSD-S-PLC), Features & Compliance, Safety Compliance and EMC Compliance

The safety and EMC compliance rows as printed for the RSD-S-PLC. Manufacturer claims; no issuer directory was checked.

Location: PDF page 2, Technical Data (Model RSD-S-PLC), Features & Compliance, Safety Compliance and EMC Compliance

[1]
Communications
PLCDocumented claim
Conditions

Printed as "Communication PLC"; the description says it receives a heartbeat signal from the APsmart Transmitter.

Location: PDF page 2, Technical Data (Model RSD-S-PLC), Features & Compliance, Communication

Printed as "Communication PLC"; the description says it receives a heartbeat signal from the APsmart Transmitter.

Location: PDF page 2, Technical Data (Model RSD-S-PLC), Features & Compliance, Communication

[1]
Connector
MC4 connectorDocumented claim
Conditions

The 435101 ordering line prints "435101 1500V UL/1000V TUV, MC4 connector, input cable length 250mm"; the Technical Data connector row prints "Input: Stäubli MC4 PV-KBT4&KST4 or Customized" and "Output: APsystems specified or Customized" for the RSD-S-PLC.

Location: PDF page 2, Ordering Information (435101); Technical Data, Connector

The 435101 ordering line prints "435101 1500V UL/1000V TUV, MC4 connector, input cable length 250mm"; the Technical Data connector row prints "Input: Stäubli MC4 PV-KBT4&KST4 or Customized" and "Output: APsystems specified or Customized" for the RSD-S-PLC.

Location: PDF page 2, Ordering Information (435101); Technical Data, Connector

[1]
Device type
Module-level rapid shutdown device, kept connected by the heartbeat signal of an APsmart Transmitter-PLC (PLC)Documented claim
Conditions

The datasheet heading prints "RAPID SHUTDOWN DEVICE RSD-S-PLC" and the description prints "The RSD-S-PLC meets SunSpec requirements, maintaining normal function by continually receiving a heartbeat signal from the APsmart Transmitter." and "The RSD executes rapid system shutdown when the Transmitter signal is absent."

Location: PDF page 1, description and features

The datasheet heading prints "RAPID SHUTDOWN DEVICE RSD-S-PLC" and the description prints "The RSD-S-PLC meets SunSpec requirements, maintaining normal function by continually receiving a heartbeat signal from the APsmart Transmitter." and "The RSD executes rapid system shutdown when the Transmitter signal is absent."

Location: PDF page 1, description and features

[1]
Dimensions
140 D × 32 D × 18 D mm5.51 D × 1.3 D × 0.71 D in convertedDocumented claim
Conditions

Printed as "140 mm x 32 mm x 18 mm" (5.5 by 1.3 by 0.7 inches) without cable and connectors; no axes are named, so the figures are kept in printed order.

Location: PDF page 2, Technical Data (Model RSD-S-PLC), Mechanical Data, Dimensions

Printed as "140 mm x 32 mm x 18 mm" (5.5 by 1.3 by 0.7 inches) without cable and connectors; no axes are named, so the figures are kept in printed order.

Location: PDF page 2, Technical Data (Model RSD-S-PLC), Mechanical Data, Dimensions

[1]
Enclosure
NEMA Type 6P/IP68Documented claim
Conditions

Printed as "Enclosure Rating NEMA Type 6P/IP68".

Location: PDF page 2, Technical Data (Model RSD-S-PLC), Mechanical Data, Enclosure Rating

Printed as "Enclosure Rating NEMA Type 6P/IP68".

Location: PDF page 2, Technical Data (Model RSD-S-PLC), Mechanical Data, Enclosure Rating

[1]
Input voltage range
10.5 to 80 VDocumented claim
Conditions

Printed once for the RSD-S-PLC as "Input Operating Voltage Range 10.5-80V".

Location: PDF page 2, Technical Data (Model RSD-S-PLC), Input Data (DC), Input Operating Voltage Range

Printed once for the RSD-S-PLC as "Input Operating Voltage Range 10.5-80V".

Location: PDF page 2, Technical Data (Model RSD-S-PLC), Input Data (DC), Input Operating Voltage Range

[1]
Maximum input current
20 ADocumented claim
Conditions

Printed as "Maximum Cont. Input Current (Imax) 15A/20A" for the RSD-S-PLC; the ordering information lists 435101 under "20A RSD-S-PLC-B ORDERING INFORMATION", so the 20 A figure is recorded for it.

Location: PDF page 2, Technical Data (Model RSD-S-PLC), Input Data (DC), Maximum Cont. Input Current (Imax); PDF page 2, Ordering Information

Printed as "Maximum Cont. Input Current (Imax) 15A/20A" for the RSD-S-PLC; the ordering information lists 435101 under "20A RSD-S-PLC-B ORDERING INFORMATION", so the 20 A figure is recorded for it.

Location: PDF page 2, Technical Data (Model RSD-S-PLC), Input Data (DC), Maximum Cont. Input Current (Imax); PDF page 2, Ordering Information

[1]
Maximum input voltage
80 VDocumented claim
Conditions

The top of the printed input operating voltage range, "10.5-80V".

Location: PDF page 2, Technical Data (Model RSD-S-PLC), Input Data (DC), Input Operating Voltage Range

The top of the printed input operating voltage range, "10.5-80V".

Location: PDF page 2, Technical Data (Model RSD-S-PLC), Input Data (DC), Input Operating Voltage Range

[1]
Maximum system voltage
1500 V (UL), 1000 V (TUV)Documented claim
Conditions

The maximum system voltage row prints "1000V (Model: RSD-S-PLC-A)" and "1500V (Model: RSD-S-PLC-B)", and the 435101 ordering line, under the RSD-S-PLC-B heading, prints "1500V UL/1000V TUV".

Location: PDF page 2, Technical Data (Model RSD-S-PLC), Output Data (DC), Maximum System Voltage; PDF page 2, Ordering Information

The maximum system voltage row prints "1000V (Model: RSD-S-PLC-A)" and "1500V (Model: RSD-S-PLC-B)", and the 435101 ordering line, under the RSD-S-PLC-B heading, prints "1500V UL/1000V TUV".

Location: PDF page 2, Technical Data (Model RSD-S-PLC), Output Data (DC), Maximum System Voltage; PDF page 2, Ordering Information

[1]
Operating temperature
-40 to 85 °C-40 to 185 °F convertedDocumented claim
Conditions

Printed as "-40°F to +185°F (-40 °C to + 85 °C)".

Location: PDF page 2, Technical Data (Model RSD-S-PLC), Mechanical Data, Operating Ambient Temperature Range

Printed as "-40°F to +185°F (-40 °C to + 85 °C)".

Location: PDF page 2, Technical Data (Model RSD-S-PLC), Mechanical Data, Operating Ambient Temperature Range

[1]
Output voltage range
10.5 to 80 VDocumented claim
Conditions

Printed once for the RSD-S-PLC as "Output Operating Voltage Range 10.5-80V".

Location: PDF page 2, Technical Data (Model RSD-S-PLC), Output Data (DC), Output Operating Voltage Range

Printed once for the RSD-S-PLC as "Output Operating Voltage Range 10.5-80V".

Location: PDF page 2, Technical Data (Model RSD-S-PLC), Output Data (DC), Output Operating Voltage Range

[1]
PV short-circuit current limit
25 ADocumented claim
Conditions

Printed in the Maximum Short Circuit Current (Isc) row as 25A, marked with an asterisk; the page's footnote reads "*Only upgrade the authentication parameters, no other changes."

Location: PDF page 2, Technical Data (Model RSD-S-PLC), Input Data (DC), Maximum Short Circuit Current (Isc)

Printed in the Maximum Short Circuit Current (Isc) row as 25A, marked with an asterisk; the page's footnote reads "*Only upgrade the authentication parameters, no other changes."

Location: PDF page 2, Technical Data (Model RSD-S-PLC), Input Data (DC), Maximum Short Circuit Current (Isc)

[1]
Rapid shutdown compliance
NEC 2017, 2020 and 2023 (690.12); SunSpecDocumented claim
Conditions

Printed in the features as "Meets NEC 2017, 2020&2023 (690.12) requirements" and "Meets SunSpec requirements". Manufacturer claim; no issuer directory was checked.

Location: PDF page 1, features

Printed in the features as "Meets NEC 2017, 2020&2023 (690.12) requirements" and "Meets SunSpec requirements". Manufacturer claim; no issuer directory was checked.

Location: PDF page 1, features

[1]

Warranty

Certificate records

No records documented.

Sources and revisions

  1. APsmart RSD-S-PLC rapid shutdown device datasheet (REV3.3, 2026-05-06) (November 2, 2026 capture)Official datasheet · Revision REV3.3 · Checked https://apsmartglobal.com/wp-content/uploads/2026/05/RSD-S-PLC-Datasheet_EN_REV3.3_2026-05-06.pdf