Printed as "Certified to UL 1741:2005 and to CSA 107.1-01 and carries the c(CSA)us mark." under Regulatory Approvals of Schneider Electric's Conext MPPT 60 Solar Charge Controller Installation Guide (990-6546, June 2022). The same page lists FCC Part 15 and ICES-003 emission limits, CE marking and the Australian C-tick mark. Manufacturer claim as printed.
You can configure the charge controller to be compatible with either negative-grounded or ungrounded (floating) PV arrays.; The factory default configuration of the solar charge controller will ground the PV array negative to the chassis ground through the internal PV-GFP fuse.; Ground the charge controller: connect a grounding conductor between a charge controller ground lug and the grounding electrode
Printed as "You can configure the charge controller to be compatible with either negative-grounded or ungrounded (floating) PV arrays." under PV Grounding of Schneider Electric's Conext MPPT 60 Solar Charge Controller Installation Guide (990-6546, June 2022). The guide describes an internal PV ground fault protection fuse (600 V, 1 A) and jumper that bond the negative to ground, disabled for ungrounded arrays, an external negative bond or a positive-grounded battery (PDF pages 30 to 33).
Where: PDF page 29, PV Grounding; PDF page 31, Internal Ground Fault Protection; PDF page 38, Connecting the Charge Controller, step 2
#6 AWG (16 mm2) minimum, 90°C copper, for a 60 A Isc array
Printed as "For installations where the PV array output is the maximum allowable 60 A Isc, the minimum allowable wire gauge is #6 AWG (16 mm2) copper wire with a 90°C (194°F) insulation rating." under PV Current Rating and Wire Gauge of Schneider Electric's Conext MPPT 60 Solar Charge Controller Installation Guide (990-6546, June 2022). The guide adds that a qualified installer determines the correct wire size for the specific installation.
Where: PDF page 36, PV Current Rating and Wire Gauge
Above and below: 6 inches (150 mm); sides: 6 inches (150 mm) on at least one side of the overall assembly
Printed as "Above and below 6 inches (150 mm)." in Table 1 of Schneider Electric's Conext MPPT 60 Solar Charge Controller Installation Guide (990-6546, June 2022). The table also prints "Sides 6 inches (150 mm) on at least one side of the overall assembly." and, in front, sufficient room to prevent accidental contact with the heat sink and to perform maintenance.
Where: PDF page 25, Table 1 Minimum clearance requirements
W 146 × H 368 × D 138 mm / W 5.75 × H 14.5 × D 5.5 in
Printed as "(368 × 146 × 138 mm)" in the Unit Dimensions (H × W × D) row of Table 4 of Schneider Electric's Conext MPPT 60 Solar Charge Controller Installation Guide (990-6546, June 2022). The row prints the inch figures first. Re-cited on 1 October 2026 to the manufacturer's own document; previously cited to Schneider Electric (download.schneider-electric.com), which stays listed as an additional source. The full row prints "Unit Dimensions (H×W×D) 14½×5¾×5½" (368×146×138 mm)"; the inch figures are kept beside the millimeters. Revised on 13 October 2026: stored as text before; converted to numbers using the axis order the document prints (height x width x depth).
Where: PDF page 60, Table 4 Mechanical specifications, Unit Dimensions row
PV disconnect device between the PV array and the controller; 60 A is recommended
Printed as "A PV disconnect device between the PV array and the solar charge controller must be installed. The disconnect device should be rated according to local electrical codes; 60 A is recommended." under PV Circuit of Schneider Electric's Conext MPPT 60 Solar Charge Controller Installation Guide (990-6546, June 2022).
Where: PDF page 36, Over-current Protection, PV Circuit
Printed as "The charge controller is a Xanbus-enabled device." under Network Installation of Schneider Electric's Conext MPPT 60 Solar Charge Controller Installation Guide (990-6546, June 2022). Devices are connected with standard Ethernet (CAT 5/CAT 5e) patch cables; the network is not an Ethernet system.
Printed as "VMPP = Vbatt +15 VDC to 120 VDC Maximum harvest of solar energy. Charging (MPPT window)" in the MPPT Voltage Range table of Schneider Electric's Conext MPPT 60 Solar Charge Controller Installation Guide (990-6546, June 2022). Between 120 VDC and 140 VDC the controller reduces the charging current, and Table 3 prints the operating maximum as 140 VDC.
Where: PDF page 58, MPPT Voltage Range table, Charging (MPPT window) row
Printed as "MPPT Maximum Power Point Tracking" in the abbreviations list of Schneider Electric's Conext MPPT 60 Solar Charge Controller Installation Guide (990-6546, June 2022). Its scope names the "Conext MPPT 60 150 Solar Charge Controller (150 A), part number: 865-1030-1". Re-cited on 1 October 2026 to the manufacturer's own document; previously cited to Schneider Electric (download.schneider-electric.com), which stays listed as an additional source.
Where: PDF page 6, Abbreviations and Acronyms; PDF page 5, Purpose
Printed as "Maximum Output Current 60 A (for all battery voltages except 60 V)" in Table 3 of Schneider Electric's Conext MPPT 60 Solar Charge Controller Installation Guide (990-6546, June 2022). The 60 A figure is printed with that exception for 60 V batteries. Re-cited on 1 October 2026 to the manufacturer's own document; previously cited to Schneider Electric (download.schneider-electric.com), which stays listed as an additional source.
Where: PDF page 57, Table 3 Electrical specifications, Maximum Output Current row
Printed as "Enclosure Type Indoor, ventilated, sheet metal chassis with" in the Schneider Electric Conext MPPT 60 Solar Charge Controller Installation Guide (990-6546, June 2022) (PDF page 60). The full row reads "Indoor, ventilated, sheet metal chassis with ... knockouts and aluminum heat sink" (the knockout sizes are partly lost in the text layer); the manual prints no IP or NEMA rating.
Where: PDF page 60, Table 4 Mechanical specifications, Enclosure Type row
Printed as "The maximum size of the ground conductor is #6 AWG (16 mm2)." under Chassis Grounding of Schneider Electric's Conext MPPT 60 Solar Charge Controller Installation Guide (990-6546, June 2022).
Printed as "The array Isc (short circuit current) must not exceed the 60 A input current rating of the solar charge controller at any time." in the PV Array Requirements of Schneider Electric's Conext MPPT 60 Solar Charge Controller Installation Guide (990-6546, June 2022). Table 3 prints "Array Short Circuit Current 60 ADC maximum".
Where: PDF page 24, PV Array Requirements, hazard box; PDF page 57, Table 3 Electrical specifications
Printed as "Maximum PV Array Open Circuit Voltage 150 VDC" in Table 3 of Schneider Electric's Conext MPPT 60 Solar Charge Controller Installation Guide (990-6546, June 2022). The operating maximum is printed separately as 140 VDC. Re-cited on 1 October 2026 to the manufacturer's own document; previously cited to Schneider Electric (download.schneider-electric.com), which stays listed as an additional source.
Where: PDF page 57, Table 3 Electrical specifications, Maximum PV Array Open Circuit Voltage row
Printed as "Nominal Battery Voltage 12, 24, 36, 48, 60 VDC" in Table 3 of Schneider Electric's Conext MPPT 60 Solar Charge Controller Installation Guide (990-6546, June 2022). Re-cited on 1 October 2026 to the manufacturer's own document; previously cited to Schneider Electric (download.schneider-electric.com), which stays listed as an additional source.
Where: PDF page 57, Table 3 Electrical specifications, Nominal Battery Voltage row
Terminal block: #3 AWG to #14 AWG (25 to 2.5 mm2); in conduit: #6 AWG to #14 AWG (13.5 to 2.5 mm2)
Printed as "Maximum and Minimum Wire Size Rating of Terminal Block #3 AWG to #14 AWG (25 to 2.5 mm2)" in Table 4 of Schneider Electric's Conext MPPT 60 Solar Charge Controller Installation Guide (990-6546, June 2022). The same table prints "Maximum and Minimum Wire Size in Conduit #6 AWG to #14 AWG (13.5 to 2.5 mm2)", and PDF page 37 says wire sizes larger than #6 AWG (16 mm2) should not be installed directly into the solar charge controller. These sizes are printed for the terminal block and conduit, not separately for the battery.
Where: PDF page 60, Table 4 Mechanical specifications; PDF page 37, Long-distance Wire Runs notice
DC-rated fuse or circuit breaker between the battery and the controller rated for 1.25 × 60 A
Printed as "The DC-rated fuse or circuit breaker between the battery and the solar charge controller must be rated for 1.25 × 60 A (the maximum current rating of the solar charge controller)." under Battery Circuit of Schneider Electric's Conext MPPT 60 Solar Charge Controller Installation Guide (990-6546, June 2022). The guide also prints "Over-current protection must be provided, external to the unit, to protect the battery wiring."
Where: PDF page 36, Over-current Protection, Battery Circuit
Printed as "Maximum PV Array Rating 5250 W, oversizing up to 7200 W" in Table 3 of Schneider Electric's Conext MPPT 60 Solar Charge Controller Installation Guide (990-6546, June 2022). Re-cited on 1 October 2026 to the manufacturer's own document; previously cited to Schneider Electric (download.schneider-electric.com), which stays listed as an additional source.
Where: PDF page 57, Table 3 Electrical specifications, Maximum PV Array Rating row
Printed as "Maximum Output Power 3500 W" in Table 3 of Schneider Electric's Conext MPPT 60 Solar Charge Controller Installation Guide (990-6546, June 2022). Re-cited on 1 October 2026 to the manufacturer's own document; previously cited to Schneider Electric (download.schneider-electric.com), which stays listed as an additional source.
Where: PDF page 57, Table 3 Electrical specifications, Maximum Output Power row
Printed as "See Figure 9 on page 34 for the location of the charge controller’s network ports." under Connecting Network Cables Between Multiple Units of Schneider Electric's Conext MPPT 60 Solar Charge Controller Installation Guide (990-6546, June 2022). Figure 10 labels the "BTS Port" for the battery temperature sensor, and PDF page 44 calls the controller a Xanbus-enabled device.
Where: PDF page 46, Connecting Network Cables Between Multiple Units; PDF page 40, Figure 10 Typical Wiring Diagram; PDF page 44, Network Installation
Printed as "Setting Battery Type Flooded1 Gel AGM" in the Default Battery Charging Settings table of Schneider Electric's Conext MPPT 60 Solar Charge Controller Installation Guide (990-6546, June 2022). Its footnote prints "When Custom is selected for the battery type, the default settings are based on the flooded battery type."
Where: PDF page 59, Default Battery Charging Settings, Battery Type columns
Printed as "Maximum PV Array Rating 5250 W" in Table 3 of Schneider Electric's Conext MPPT 60 Solar Charge Controller Installation Guide (990-6546), one figure for the 12, 24, 36, 48 and 60 V battery voltages it lists; the same row adds array oversizing to 7200 W, which is not the rating.
Where: PDF page 57, Table 3 Electrical specifications, Maximum PV Array Rating row
Printed as "Mounting Vertical wall mount" in Table 4 of Schneider Electric's Conext MPPT 60 Solar Charge Controller Installation Guide (990-6546, June 2022). PDF page 28 prints "The charge controller must be vertically mounted to the wall" with three pan-head screws, or on the side of the XW Power Distribution Panel, and PDF page 24 requires an indoor, dry, protected location.
Where: PDF page 60, Table 4 Mechanical specifications, Mounting row; PDF page 28, Mounting the Charge Controller
Printed as "Torque the charge controller’s battery terminals according to the following table: Wire Size Torque Value AWG mm2 in-lb Nm 14-10 2.5-6 15 1.7 8 10 18 2 6 16 20 2.25" in step 9 of Connecting the Charge Controller of Schneider Electric's Conext MPPT 60 Solar Charge Controller Installation Guide (990-6546, June 2022). The torque depends on the wire size, so the table is recorded as text, row by row, inch-pounds first as printed. No PV terminal torque is printed in the guide; it says a label inside the wiring compartment cover gives the torque for each terminal.
Where: PDF page 39, Connecting the Charge Controller, step 9 torque table
Printed as "Battery Voltage Range (Operating) 10 VDC to 80 VDC" in Table 3 of Schneider Electric's Conext MPPT 60 Solar Charge Controller Installation Guide (990-6546, June 2022).
Where: PDF page 57, Table 3 Electrical specifications, Battery Voltage Range (Operating) row
Printed as "Operating Temperature Range -20 to +45°C (-4 to 113°F)" in Table 4 of Schneider Electric's Conext MPPT 60 Solar Charge Controller Installation Guide (990-6546, June 2022). Re-cited on 1 October 2026 to the manufacturer's own document; previously cited to Schneider Electric (download.schneider-electric.com), which stays listed as an additional source.
Where: PDF page 60, Table 4 Mechanical specifications, Operating Temperature Range row
What this shows: what each record says and how far it reaches. It does not mean the product is approved.
StandardEvidenceStatusSource
UL 1741:2005manufacturer claimpresent at observation[1]
Scope
equipment listing
Covered models
Conext MPPT 60 150
Limitations
Printed in the manufacturer's own regulatory approvals section, captured September 28, 2026; no certificate number or issuer file number is given, so it is a manufacturer claim and not issuer-verified.
CSA 107.1-01manufacturer claimpresent at observation[1]
Scope
equipment listing
Covered models
Conext MPPT 60 150
Limitations
Printed in the manufacturer's own regulatory approvals section, captured September 28, 2026; no certificate number or issuer file number is given, so it is a manufacturer claim and not issuer-verified.
c(CSA)usmanufacturer claimpresent at observation[1]
Scope
equipment listing
Covered models
Conext MPPT 60 150
Limitations
Printed in the manufacturer's own regulatory approvals section, captured September 28, 2026; no certificate number or issuer file number is given, so it is a manufacturer claim and not issuer-verified.
FCC Part-15 subpart B, Class Bmanufacturer claimpresent at observation[1]
Scope
equipment listing
Covered models
Conext MPPT 60 150
Limitations
Printed in the manufacturer's own regulatory approvals section, captured September 28, 2026; no certificate number or issuer file number is given, so it is a manufacturer claim and not issuer-verified.
Industry Canada ICES-003, Class Bmanufacturer claimpresent at observation[1]
Scope
equipment listing
Covered models
Conext MPPT 60 150
Limitations
Printed in the manufacturer's own regulatory approvals section, captured September 28, 2026; no certificate number or issuer file number is given, so it is a manufacturer claim and not issuer-verified.
EN50178manufacturer claimpresent at observation[1]
Scope
unresolved document set
Covered models
Conext MPPT 60 150
Limitations
Printed in the manufacturer's own regulatory approvals section, captured September 28, 2026; no certificate number or issuer file number is given, so it is a manufacturer claim and not issuer-verified.
EN61000-6-3manufacturer claimpresent at observation[1]
Scope
unresolved document set
Covered models
Conext MPPT 60 150
Limitations
Printed in the manufacturer's own regulatory approvals section, captured September 28, 2026; no certificate number or issuer file number is given, so it is a manufacturer claim and not issuer-verified.
EN61000-6-1manufacturer claimpresent at observation[1]
Scope
unresolved document set
Covered models
Conext MPPT 60 150
Limitations
Printed in the manufacturer's own regulatory approvals section, captured September 28, 2026; no certificate number or issuer file number is given, so it is a manufacturer claim and not issuer-verified.
Printed in the manufacturer's own regulatory approvals section, captured September 28, 2026; no certificate number or issuer file number is given, so it is a manufacturer claim and not issuer-verified.
Location: PDF page 1 cover; PDF page 5, About This Guide, Purpose
Retrieved Oct 1, 2026
Schneider Electric's own installation guide for the Conext MPPT 60 150 Solar Charge Controller, captured 1 October 2026 from download.schneider-electric.com through se.com's document page MPPT-60_IG_990-6546 (Version A, dated June 30 2022 on that page); document 990-6546, June 2022 as printed (the file name reads 990-9546); its Purpose section names part number 865-1030-1. Manufacturer instructions, not independent tests.
Archived copies
Archived copy of a document published by Schneider Electric. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email [email protected].
Primary source for the Conext MPPT 60 150 (865-1030-1): covers this exact model by name and part number.
Archived copies
Archived copy of a document published by Schneider Electric. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email [email protected].
Earlier revisions, archived captures and copies published by someone other than the manufacturer. Every one stays reachable.
Archived documents
Schneider Electric's own Conext MPPT 60 Solar Charge Controller Operation Guide, document 990-6547, dated June 2022, linked from Schneider Electric's own se.com product page for 865-1030-1.
Archived copy of a document published by Schneider Electric. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email [email protected].
Schneider Electric Conext MPPT 60 Solar Charge Controller Installation Guide (990-6546, June 2022)
Archived copy of a document published by Schneider Electric. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email [email protected].