About brandMorningstar Corporation, based in Newtown, Pennsylvania since 1993, makes solar charge controllers and inverters used in off-grid, industrial and hazardous-location power systems worldwide; its datasheets describe the company as employee-owned with well over three million products made.
SKU detail
locator: Versions line
conditions: Printed as this model's own version, no meter (a meter-equipped 60A version, TS-60M, is built as a separate record: same electrical ratings, only a factory-installed meter).
Use the grounding terminal in the wiring compartment to connect a copper wire to an earth ground or similar grounding point.
Printed as "Use the grounding terminal in the wiring compartment to connect a copper wire to an earth ground or similar grounding point." in Morningstar's TriStar Installation, Operation and Maintenance Manual (MS-001156 v4.7), Step 6 Ground Connection, for all TriStar models. The TriStar negative terminals are common negative.
Where: PDF page 15, section 2.3, Step 6, Ground Connection
25 mm2 (4 AWG) with 75C wire; 16 mm2 (6 AWG) with 90C wire (ambient to 45C)
Printed as "TS-45 75C Wire 90C Wire TS-60 75C Wire 90C Wire" in Morningstar's TriStar Installation, Operation and Maintenance Manual (MS-001156 v4.7), Table 2.3-6b, the TS-60 columns (75C wire, 90C wire) for ambient temperatures to 45C. The table applies to the wires carrying the system current. The power terminals are sized for 35 - 2.5 mm2 (2-14 AWG) wire (PDF page 14).
open space above and below the heat sink, and at least 75 mm (3 inches) clearance around the heat sink
Printed as "There should be open space above and below the heat sink, and at least 75 mm (3 inches) clearance around the heat sink to allow free air flow for cooling." in Morningstar's TriStar Installation, Operation and Maintenance Manual (MS-001156 v4.7), section 2.3, Step 2, for all TriStar models.
Where: PDF page 10, section 2.3, Step 2 (Mounting)
Printed as a single value shared across both models (height, width, depth). Printed as "Dimensions Height: 26.0cm/10.3 in Width: 12.7cm/5.0 in Depth: 7.1cm/2.8 in" in Morningstar's TriStar datasheet. Revised on 13 October 2026: stored as text before; converted to numbers using the axis order the document prints (height x width x depth).
Printed as "must be a maximum of 70 amps for the TriStar-PWM-45, and 90 amps for the TriStar-PWM-60/M" in Morningstar's TriStar Installation, Operation and Maintenance Manual (MS-001156 v4.7), section 2.1, which says solar and battery fuses or DC breakers are required and gives the maximum for the TriStar-PWM-60/M. Section 2.3 (PDF page 15) says the NEC requires manually operated disconnect switches or circuit breakers between the TriStar and the battery.
Where: PDF page 9, section 2.1 (General Information), warning on fuses and DC breakers
Printed as "TS-60/M 8 AWG (8 mm2)" in Morningstar's TriStar Installation, Operation and Maintenance Manual (MS-001156 v4.7), Step 6 Ground Connection, the minimum copper grounding wire size printed for the TS-60. Or a wire of the same or greater cross-sectional area as the PV wires.
Where: PDF page 15, section 2.3, Step 6, Ground Connection
Printed as "Never exceed a Voc (open-circuit voltage) of 125V." in Morningstar's TriStar Installation, Operation and Maintenance Manual (MS-001156 v4.7), the section 2.3 safety notes, for all TriStar models. Re-cited on 1 October 2026 to the manufacturer's own document; previously cited to Morningstar (morningstarcorp.com), which stays listed as an additional source.
Where: PDF page 10, section 2.3 (Installation Steps), safety notes
25 mm2 (4 AWG) with 75C wire; 16 mm2 (6 AWG) with 90C wire (ambient to 45C)
Printed as "TS-45 75C Wire 90C Wire TS-60 75C Wire 90C Wire" in Morningstar's TriStar Installation, Operation and Maintenance Manual (MS-001156 v4.7), Table 2.3-6b, the TS-60 columns (75C wire, 90C wire) for ambient temperatures to 45C. The minimum copper wire the NEC allows for the system current; aluminum must be one size larger. The power terminals are sized for 35 - 2.5 mm2 (2-14 AWG) wire.
Printed as "must be a maximum of 70 amps for the TriStar-PWM-45, and 90 amps for the TriStar-PWM-60/M" in Morningstar's TriStar Installation, Operation and Maintenance Manual (MS-001156 v4.7), section 2.1, which says solar and battery fuses or DC breakers are required and gives the maximum for the TriStar-PWM-60/M. Breakers and fuses may require lower ratings so as not to exceed a wire's ampacity.
Where: PDF page 9, section 2.1 (General Information), warning on fuses and DC breakers
Printed as "Torque terminals 5.65 Nm / 50 in-lb" in Morningstar's TriStar Installation, Operation and Maintenance Manual (MS-001156 v4.7), the Technical Specifications Mechanical list, printed once for all TriStar models; the printed spelling is "Nm".
Where: PDF page 33, Technical Specifications, Mechanical, Torque terminals row
lead-acid (12, 24 or 48 volt) with the standard battery charging programs
Printed as "Charge only 12, 24, or 48 volt lead-acid batteries when using the standard battery charging programs in the TriStar." in Morningstar's TriStar Installation, Operation and Maintenance Manual (MS-001156 v4.7), section 2.3 safety notes, for all TriStar models.
Where: PDF page 10, section 2.3 (Installation Steps), safety notes
Printed as "Torque terminals 5.65 Nm / 50 in-lb" in Morningstar's TriStar Installation, Operation and Maintenance Manual (MS-001156 v4.7), the Technical Specifications Mechanical list, printed once for all TriStar models; the printed spelling is "Nm".
Where: PDF page 33, Technical Specifications, Mechanical, Torque terminals row
The manual and the data sheet print different operating temperature ranges. Morningstar's TriStar Operator's Manual (MS-001156 v4.7) prints an ambient temperature range of –40 to +45ºC; Morningstar's TriStar data sheet prints -40°C to +60°C.
Printed as "Ambient temperature –40 to +45ºC" in Morningstar's TriStar Installation, Operation and Maintenance Manual (MS-001156 v4.7), the Technical Specifications Environmental list, printed once for all TriStar models. Revised on 1 October 2026: The installation and operation manual is the primary source; it prints an ambient temperature range of –40 to +45ºC, while the data sheet prints -40°C to +60°C.
Where: PDF page 33, Technical Specifications, Environmental, Ambient temperature row
Sources
-40°C to +60°C
Printed as a single value shared across both models; both may derate above 55°C.
What this shows: what each record says and how far it reaches. It does not mean the product is approved.
StandardEvidenceStatusSource
CSA-C22.2 No.107.1-95manufacturer claimpresent at observation[1]
Scope
equipment listing
Covered models
tristar-60
Limitations
Printed in the manufacturer's own datasheet Certifications block, captured September 28, 2026; no certificate number or issuer file number is given, so it is a manufacturer claim and not issuer-verified.
IEC 62109-1manufacturer claimpresent at observation[1]
Scope
unresolved document set
Covered models
tristar-60
Limitations
Printed in the manufacturer's own datasheet Certifications block, captured September 28, 2026; no certificate number or issuer file number is given, so it is a manufacturer claim and not issuer-verified.
EN 60335-1manufacturer claimpresent at observation[1]
Scope
unresolved document set
Covered models
tristar-60
Limitations
Printed in the manufacturer's own datasheet Certifications block, captured September 28, 2026; no certificate number or issuer file number is given, so it is a manufacturer claim and not issuer-verified.
EN 60335-2-29manufacturer claimpresent at observation[1]
Scope
unresolved document set
Covered models
tristar-60
Limitations
Printed in the manufacturer's own datasheet Certifications block, captured September 28, 2026; no certificate number or issuer file number is given, so it is a manufacturer claim and not issuer-verified.
UL 1741manufacturer claimpresent at observation[1]
Scope
equipment listing
Covered models
tristar-60
Limitations
Printed in the manufacturer's own datasheet Certifications block, captured September 28, 2026; no certificate number or issuer file number is given, so it is a manufacturer claim and not issuer-verified.
Location: Cover page (MODELS list) and the Technical Specifications appendix
Retrieved Oct 1, 2026
Morningstar's own installation, operation and maintenance manual for the TriStar models TS-45, TS-60 and TS-60M, captured 1 October 2026 from morningstarcorp.com, where the product page links it; revision MS-001156 v4.7 as printed on the back cover. Manufacturer instructions and specifications, not independent tests.
Archived copies
Archived copy of a document published by Morningstar. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email [email protected].
UL 1741Manufacturer claim · equipment listingClaimedListed when checked
Printed in the manufacturer's own datasheet Certifications block, captured September 28, 2026; no certificate number or issuer file number is given, so it is a manufacturer claim and not issuer-verified.
CSA-C22.2 No.107.1-95Manufacturer claim · equipment listingClaimedListed when checked
Printed in the manufacturer's own datasheet Certifications block, captured September 28, 2026; no certificate number or issuer file number is given, so it is a manufacturer claim and not issuer-verified.
IEC 62109-1Manufacturer claim · unresolved document setClaimedListed when checked
Printed in the manufacturer's own datasheet Certifications block, captured September 28, 2026; no certificate number or issuer file number is given, so it is a manufacturer claim and not issuer-verified.
EN 60335-1Manufacturer claim · unresolved document setClaimedListed when checked
Printed in the manufacturer's own datasheet Certifications block, captured September 28, 2026; no certificate number or issuer file number is given, so it is a manufacturer claim and not issuer-verified.
EN 60335-2-29Manufacturer claim · unresolved document setClaimedListed when checked
Printed in the manufacturer's own datasheet Certifications block, captured September 28, 2026; no certificate number or issuer file number is given, so it is a manufacturer claim and not issuer-verified.
Captured by scripts/prepare-brand-sweep-sep21.mjs on 2026-09-28.
Location: Versions block and Technical Specifications block
Retrieved Sep 27, 2026
Primary source for the TriStar PWM models.
Archived copies
Archived copy of a document published by Morningstar. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email [email protected].
Earlier revisions, archived captures and copies published by someone other than the manufacturer. Every one stays reachable.
Archived documents
Morningstar's own TriStar (PWM) datasheet, control no. MS-001798, revision 3/2025, from morningstarcorp.com's own TriStar product page.
Archived copy of a document published by Morningstar. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email [email protected].
Morningstar TriStar Solar Charging System Controller Installation, Operation and Maintenance Manual (MS-001156 v4.7)
Archived copy of a document published by Morningstar. Copyright retained by the publisher; kept for reference and verification only, no endorsement implied. To ask for its removal, email [email protected].