Energy and chemistry
Charge and discharge
BMS and communication
- BMS continuous current
- ?
- Communication protocols
- CAN [2]
- Wireless monitoring
- ?
- Inverter compatibility
- ?
Operating temperature
Mechanical and mounting
Installation (from the manual)
Conductors
- Cable size
- Single-core outdoor copper cable, 6 mm2 or 10 mm2 (6 mm2 only for a single battery system) [2]
Protection
- Fuse or breaker
- Circuit breakers between inverter and battery and between battery systems per local rules; recommended nominal voltage at least 750 V and nominal current at least 50 A for one battery system, 100 A for two, 125 A for three or more [2]
Clearances and orientation
- Installation clearances
- ?
- Mounting orientation
- Install the equipment vertically, no tilt or upside down. [2]
Grounding
- Grounding
- Connect the PE cable first; customer-supplied single-core outdoor copper cable, 6 mm2 [2]
Communication
- Communication ports
- COM1: communication cable to the inverter; COM2: battery parallel connection (terminal resistor fitted at the factory); COM3: reserved [2]
- Address / DIP setting
- ?
Not in the manual: Torque
System limits
- Maximum parallel units
- 8 count [2]
- Series connection
- ?
- Maximum system energy
- ?