Charged Reviews · Quick reference
ECO-WORTHY PowerMega 314
- Brand
- ECO-WORTHY
- Model
- GW-L03L314AHJC-1
- SKU / part number
- GW-L03L314AHJC-1 [1]
- Category
- Batteries
chargedreviews.com/batteries/eco-worthy-gw-l03l314ahjc-1
Energy and chemistry
Charge and discharge
BMS and communication
- BMS continuous current
- ?
- Communication protocols
- CAN; RS485 [4]
- Wireless monitoring
- Bluetooth; WiFi [4]
- Inverter compatibility
- CAN protocols: PYLON, Growatt, Victron, Schneider, Luxpowertek, Sorotec, SMA, GoodWe, STUDER, MUST, GINLONG, Senergy, TBB, MEGAREVO; RS485 protocols: PACE, PYLON, Growatt, Voltronic, Luxpowertek, WOW, Schneider [4]
Operating temperature
Mechanical and mounting
Installation (from the manual)
Conductors
- Cable size
- 2/0 AWG battery-to-inverter cables (included, 1500 mm) [4]
Protection
- Fuse or breaker
- 250 A breaker (2 × 125 A) with shunt trip [4]
Communication
- Communication ports
- RS232 Communication; BMS can communicate with the host computer through the RS232 interface; The default baud rate is 9600bps.; Parallel RS485 Communication; You can view the information of PACK; the default baud r-ate is 9600bps.; CAN Communication; The default baud rate is 500K.; This interface is used to communicate with the inverter.; Independent RS485 Communication; The default baud rate is 9600bps.; This interface is used to communicate with the inverter. [4]
- Address / DIP setting
- DIP switch address on the BMS per pack; addresses must not repeat [4]
Not in the manual: Torque, Clearances and orientation, Grounding
System limits
- Maximum parallel units
- 15 units [5]
- Series connection
- ?
- Maximum system energy
- ?